Download Print this page
WallSenzr LDS-700 Series Installation Instructions

WallSenzr LDS-700 Series Installation Instructions

Line voltage dual-tech wall switch sensor

Advertisement

Quick Links

LDS-700 Series
Line Voltage Dual-Tech Wall Switch Sensor
INSTALLATION INSTRUCTIONS
INDOOR USE ONLY
Utilisation a L'interieur Uniquement
WARNING & CAUTION
Risk of Electric Shock - Disconnect power supply at the circuit breaker
before installing, replacing lamps, or servicing.
DO NOT control a load in excess of specified ratings to avoid damaging the
sensor or the property.
Install and use this sensor in accordance with electrical codes and regulations.
This device is intended to be installed by a qualified electrician. DO NOT
attempt to service or repair.
AVERTISSEMENT & PRUDENCE
Afin d'eviter tout risque de choc electrique ou electrocution, couper le
courant au disjoncteur avant installation, remplacement des lampes ou
tout service d'entretien.
NE PAS contrôler une charge supérieure à la capacité spécifiée pour éviter
d'endommager le capteur ou la propriété.
Installer et utiliser ce capteur conformément aux codes et règlements
électriques.
Ce dispositif est destiné à être installé par un électricien qualifié. NE PAS
tenter de réparer.
FCC NOTICE
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1)This device may not cause harmful interference,
(2)This device must accept any interference received,
Including interference that may cause undesired operation.
Install the sensor at least 1ft. away from any occupant.
www.irtec.com
This product may be covered by one or more U.S. patents or patent applications.
Please visit www.irtec.com for more information.
OVERVIEW
The LDS-700 is a dual technology line voltage wall switch
sensor in the IR-TEC's WALLSENZR family designed to fit
in a standard NEMA wall box for energy efficient automatic
load control. This state-of-the-art wall switch sensor
combines digital Passive Infrared (PIR) and advanced High
Frequency Doppler (HFD) sensing technologies into an
aesthetically pleasing housing to provide second-to-none
occupancy/vacancy sensing performance within its 180°
field of view detection range.
The sensor is factory set to turn ON the load automatically
when PIR sensor detects the presence of an occupant,
and will turn OFF automatically if no motion is detected by
either PIR or HFD sensor before the delay time elapses. To
comply with specific energy code, such as CA Title 24, the
LDS-700 series can be easily programmed to operate as a
Vacancy Sensor. In vacancy sensing mode, the sensor will
only turn ON the load by pressing the push-button
manually and will turn OFF the load automatically as per
sensor delay time set. Various sensing operation and
control modes can be achieved by different DIP switch
setting combinations and push-button operations.
DETECTION COVERAGE
Top view
30'
Minor motion
20'
20'
40'
180°, 30 ft x 40 ft (W x L)
Major motion
Side view
4'
40'
P/N: 058-70004-004
Printed in Taiwan
INSTALLATION NOTES
1.
The sensor is more sensitive to the movements
"crossing" the detection zones than "toward" or "away"
the sensor. To obtain better sensitivity, ensure the sensor
to have clear field of view for the occupant's motion
within the desired coverage.
2.
The closer movement is to the sensor, the more
sensitive the sensor is.
3.
The sensor should be mounted within the specified
mounting height for optimal performance.
4.
Avoid blocking the sensor with any obstacles, such as
door, plant, partition or furniture. As a general rule, every
occupant within the desired range should be able to
clearly see the sensor.
5.
Do NOT mount the sensor directly above or nearby a
heat source, or where unintended motion (e.g. hallway
traffic) will be "seen" by the sensor.
SPECIFICATIONS
Power supply
120/277VAC, 60Hz
Digital PIR & High Frequency Doppler
Sensing technology
Incandescent/Halogen – 800W (VA)
Fluorescent Ballast/CFL – 800W (VA)
Maximum load
Ballast Electronic (LED) – 500/800VA@120/277V
Motor – 1/6 HP
Inrush current
Max. 80A, 16.7 ms @60Hz
Load switching
Zero-cross Hybrid-Switching
Detectable speed
1~10 ft./sec. (0.3~3 m/sec)
Mounting height
3~5 ft. (90~150 cm) above the floor
Major motion - 30 ft x 40 ft (W x L) @4 ft high
Detection coverage
Minor motion - 20 ft x 20 ft (W x L) @4 ft high
Ambient light level
7 levels, from dark to 24 Hour
Delay time setting
T/1'/3'/5'/10'/20'/30', T=10 sec. for testing
7'
Op. humidity
Max. 95% RH, non-condensate
Op. temperature
-40°F ~ 131°F (-40°C ~ 55°C)
Dimensions
4.13"H x 1.77"W x 1.65"D (w/mounting plate)

Advertisement

loading

Summary of Contents for WallSenzr LDS-700 Series

  • Page 1 CA Title 24, the clearly see the sensor. LDS-700 series can be easily programmed to operate as a Do NOT mount the sensor directly above or nearby a Vacancy Sensor. In vacancy sensing mode, the sensor will heat source, or where unintended motion (e.g.
  • Page 2 WIRING DIAGRAM OPERATION The LDS-700 series dual-tech wall switch sensor employs two Via DIP switch setting, the LDS-700 can be programmed Single-Pole Control different sensing technologies (PIR & HFD) to detect the to adjust the HFD sensitivity, operate as a single HFD...