INSTALLATION INSTRUCTIONS

INDOOR USE ONLY
Utilisation a L'interieur Uniquement
WARNING & CAUTION
Risk of Electric Shock -
Disconnect power supply before servicing.
DO NOT control a load in excess of specified ratings to avoid
damaging the sensor or the property.
Install and use this sensor in accordance with electrical codes and
regulations.
This device is intended to be installed by a qualified electrician.
DO NOT attempt to service or repair.
AVERTISSEMENT & PRUDENCE
Risque de choc électrique - Débranchez l'alimentation avant
l'entretien.
NE PAS contrôler une charge supérieure à la capacité spécifiée pour
éviter d'endommager le capteur ou la propriété.
Installer et utiliser ce capteur conformément aux codes et règlements
électriques.
Ce dispositif est destiné à être installé par un électricien qualifié. NE
PAS tenter de réparer.
www.irtec.com
This product may be covered by one or more U.S. patents or patent applications.
Please visit www.irtec.com for more information.
OVERVIEW
The LBS-700 is a member of IR-TEC's WALLSENZR family of
line voltage wall switch sensor designed to fit in a standard
NEMA wall box with no neutral connection required. The
sensors combine state-of-the-art passive infrared sensing
technology with décor aesthetics to provide optimal
energy-saving for all applications.
The sensor will turn ON the load automatically when it detects
the presence of an occupant, and will turn OFF automatically
if no motion is detected before the delay time elapses. To
meet compliance of specific energy code, such as CA Title
24, the LBS-700 series can be easily programmed as a
Vacancy sensor. In Vacancy mode the sensor will only turn
ON the load by pressing the push-button manually and will
turn OFF the load automatically per the sensor time delay.
The LBS-700 allows for the push-button operation to be
programmed with different manual control options.
The model LBS-700S comes with an ambient light sensor
(ALS) to inhibit the lighting if ambient light levels are higher
than required. The Accu-Set potentiometers make delay time
(TIME) and ambient light level (LUX) settings fast, easy and
accurate. Hybrid-Switching control allows the LBS-700 series
to control the lighting with high inrush current (HIC) while
switching ON, such as multiple LED or CFL lightings
connected in parallel.
DETECTION COVERAGE
Top view
30'
20'
20'
40'
Major motion
P/N: 058-70000-004
Printed in Taiwan
Minor motion
Side view
7'
4'
40'
INSTALLATION NOTES
1.
The sensor is more sensitive to the movements
"crossing" the detection zones than "toward" or "away"
the sensor. To obtain better sensitivity, ensure the sensor
to have clear field of view for the occupant's motion within
the desired coverage.
The closer movement is to the sensor, the more sensitive
2.
the sensor is.
3.
The sensor should be mounted within the specified
mounting height for optimal performance.
Avoid blocking the sensor with any obstacles, such as
4.
door, plant, partition or furniture. As a general rule, every
occupant within the desired range should be able to
clearly see the sensor.
5.
Do NOT mount the sensor directly above or nearby a heat
source, or where unintended motion (e.g. hallway traffic)
will be "seen" by the sensor.

SPECIFICATIONS

Power supply
120/277VAC, 60Hz
Incandescent/Halogen – 800W (VA)
Fluorescent Ballast/CFL – 800W (VA)
Maximum load
Ballast Electronic (LED) – 500/800VA@120/277V
Motor – 1/6 HP
Infrared sensor
Dual element pyroelectric
Switching control
Zero-cross Hybrid-Switching
Inrush current
Max. 80A, 20 mS
Detectable speed
1~10 ft./sec. (0.3~3 m/sec)
Mounting height
3 ~ 5 ft. (90~150 cm) above the floor
Major motion - 30 ft x 40 ft (W x L) @4 ft high
Detection coverage
Minor motion - 20 ft x 20 ft (W x L) @4 ft high
Ambient light level
7 levels, from dark to 24 Hr., LBS-700S only
Delay time setting
T/1'/3'/5'/10'/20'/30' , T=10 sec. for testing
Op. humidity
Max. 95% RH, non-condensate
Op. temperature
-40°F ~ 131°F (-40°C ~ 55°C)
Dimensions
4.13"H x 1.77"W x 1.65"D (w/mounting plate)