System (r-410a) mini-split, inverter system (42 pages)
Summary of Contents for Ameristar M4AC3018B1000NA
Page 1
INSTALLATION INSTRUCTIONS 13 SEER Split System Air Conditioner 1.5-5 Tons R410A NOTE: Appearance of unit may vary. RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION WARNING These instructions are intended as an aid to qualified licensed service personnel for proper installation, adjust- ment and operation of this unit.
This document is customer property and is to remain with this unit. These instructions do not cover all the different variations of systems nor does it provide for every possible contingency to be met in connection with installa- tion. All phases of this installation must comply with NATIONAL, STATE, AND LOCAL CODES.
1.1 INSPECTION As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier's delivery receipt. A separate request for inspection by the carrier's agent should be made in writing.
Page 5
AIR DISCHARGE: ALLOW 60” MINIMUM CLEARANCE. AIR INLETS LOUVERED PANELS ALLOW 12” MINIMUM CLEARANCE SERVICE ACCESS ALLOW 24” CLEARANCE NOTE: GRILL APPEARANCE MAY VARY. POWER WIRING SEE DETAIL A CONTROL WIRING DETAIL A 7/8” (22.2mm) KNOCKOUT 1-11/32” (34.5mm) ACCESS VALVE FOR LOW PRESSURE NOTE: ONLY ADOPTED BY HEAT PUMP,...
3.0 UNIT INSTALLATION 3.1 LOCATION Before starting the installation, select and check the suitability of the location for both the indoor and outdoor unit. Observe all limitations and clearance requirements. The outdoor unit must have sufficient clearance for air entrance to the condenser coil, for air discharge and for service access.
The outdoor unit must be connected to the indoor coil using field supplied refrigerant grade copper tubing that is internally clean and dry. Units should be installed only with the tubing sizes for approved system combinations. The refrigerant charge shown in the nameplate is for standard size interconnecting liquid line lengths up to 15 feet.
3.6 FACTORY-PREFERRED TIE-DOWN METHOD Step 1: Prior to installing clear pad of debris. IMPORTANT The pad must meet local codes and must be the proper thickness to accommodate fasteners. Step 2: Center and level unit onto pad. Step 3: Using field supplied L-shaped bracket to locate holes on concrete and drill pilot holes which is at least 1/4”...
3.7 PRECAUTIONS DURING LINE INSTALLATION 1. Install the lines with as few bends as possible. Care must be taken not to damage the couplings or kink the tubing. Use clean hard drawn copper tubing where no appreciable amount of bending around obstruction is necessary, if soft copper must be used, care must be taken to avoid sharp bends which may cause a restriction.
Fig.7 3.8 PRECAUTIONS DURING BRAZING OF LINES All outdoor unit and evaporator coil connections are copper-to-copper and should be brazed with a phosphorous-copper alloy material such as Silfos-5 or equivalent. DO NOT use soft solder. The outdoor units have reusable service valves on both the liquid and suction connections.
Page 11
Connect the refrigerant lines using the following procedure: 1. Remove the cap and Schrader core from both the liquid and suction service valve service ports at the outdoor unit. Connect Iow pressure nitrogen to the liquid line service port. service valve wet rag Fig.8 Heat Protection 2.
10. Replace cap on service ports. Do not remove the flare caps from the service ports except when necessary for servicing the system. 11. Release the refrigerant charge into the system. Open both the liquid and suction valves by removing the plunger cap and with an hex wrench back out counter -clockwise until valve stem just touches the chamfered retaining wall.
Page 13
LINE SIZING TABLE 2: SUCTION LINE LENGTH/SIZE VS CAPACITY MULTIPLIER(R410A) TABLE 3 :LIQUID LINE SIZE (R410A)
6.0 ELECTRICAL CONNECTIONS 6.1 GENERAL INFORMATION & GROUNDING Check the electrical supply to be sure that it meets the values specified on the unit nameplate and wiring label. Power wiring, control (Iow voltage) wiring, disconnect switches and over current protection must be supplied by the installer. Wire size should be sized per require- ments.
6.3 REMOVING THE TOP PANEL AND MOTOR Damage will occur to condenser unit if you remove fan nuts prior to cover removal. Fig.10 COVER AND FAN When motor requires changing follow the steps below: Step 1: Go into electrical panel, disconnect motor power lines. IMPORTANT NOTE Disconnect main power to unit.
5. Compare the measured LIQUID LINE PRESSURE to the TARGET LIQUID PRESSURE, add charge to raise the pressure or recover charge to lower it. 6. After running unit for 20 minutes if the SUCTION LINE PRESSURE changes, go back to step 2 otherwise remove test equipment and cover the valves. 7.2 CHARGING BY WEIGHT For a new installation,evacuation of interconnecting tubing and indoor coil is adequate;...
9.1 CONTROL WIRING PLUG PLATE GROUND LINE VOLTAGE FACTORY STANDARD FIELD INSTALLED BLACK FACTORY OPTIONAL BLACK VOLTAGE FACTORY STANDARD FIELD INSTALLED BLACK FACTORY OPTIONAL USE COPPER CONDUCTORS ONLY YELLOW YELLOW COMPRESSOR CONTACTOR COMP COMPRESSOR BLACK RC 1 RUN CAPACITOR 1 BLACK RC 2 RUN CAPACITOR 2...
Page 18
Orifice/TXV Replacement Information NOTE: The orifice / TXV replacement options noted in this sheet supersede those in the installation guide. Please reference this sheet for all refrigerant metering options. DRILL A SMALL HOLE IN VAPOR LINE FOR EQUALIZER TUBE Step 1: Remove the screws and front coil BULB panel.
Page 21
TABLE 5. Troubleshooting C- Cooling H - Heating P - Primary Causes S - Secondary Causes TABLE 6. Operational And Checkout Procedures...
Page 22
Base Limited Warranty Single Phase R-410A Outdoor Units, Single Phase R-22 Outdoor Units, Air Handlers, Furnaces, Subject to the terms and conditions of this limited warranty, Ingersoll Rand (“Company’) extends a limited warranty against manufacturing defects for the product(s) Table 1 attached hereto (“Products’) that are installed in a residential/multi-family application (personal, family or household purposes) under normal use and maintenance in the United States and Canada.
Page 23
TABLE 1: Warranty Time Periods COVERAGE TERMS FOR RESIDENTIAL APPLICATIONS: Pursuant to the Ingersoll Rand (“Company”) limited warranty terms and conditions, the following Products are covered for the base time periods as stated below (“Base Limited Warranty Period’). If registered, the Base Limited Warranty Periods for certain Products will be extended as stated below (“Registered Limited Warranty Period”).
Need help?
Do you have a question about the M4AC3018B1000NA and is the answer not in the manual?
Questions and answers