LG ARUN80LN3 Installation Manual page 63

Table of Contents

Advertisement

■ 4 Outdoor Units - 3Ø, 380-415V
■ When the power source is connected In series between the units.
3 Phase 4 Wires
Power supply
50Hz 380-415V
(Main Switch)
R S T N
Switch
Fuse
Power supply
1 Phase 50Hz
220-240V
L
N
Power Line
(4 Wires Cable)
Power Line
(2 Wires Cable)
Pull Box
Pull Box
(Installer option)
(Installer option)
Power Line
Power Line
(2 Wires Cable)
(2 Wires Cable)
Communication Line
WARNING
When the total capacity is over than as follow, the power source do not use in series between the units.
The First terminal block could be burnt out. (Heat Pump : 68 Hp, Cooling Only : 62 Hp)
■ When the power source is supplied to Each outdoor unit individually.
3 Phase 4 Wires
Power supply
50Hz 380-415V
(Main Switch)
R S T N
Switch
Fuse
Power supply
1 Phase 50Hz
220-240V
N
L
Power Line
(2 Wires Cable)
[Master]
[Slave1]
Pull Box
(Installer option)
Power Line
(2 Wires Cable)
(3 Wires Cable)
[Indoor Units]
R S T N
R S T N
Switch
Switch
Switch
Fuse
Fuse
Fuse
Power Line
(4 Wires Cable)
Pull Box
Pull Box
(Installer option)
(Installer option)
Power Line
(2 Wires Cable)
(2 Wires Cable)
[Slave2]
[Slave3]
Pull Box
(Installer option)
Power Line
(2 Wires Cable)
[Master]
[Slave1]
R S T N
Pull Box
(Installer option)
Power Line
Power Line
(2 Wires Cable)
Communication Line
(3 Wires Cable)
[Indoor Units]
Electrical Wiring
Communication Line
(2 Wires Cable)
[Slave2]
[Slave3]
Communication Line
(2 Wires Cable)
Pull Box
(Installer option)
Power Line
(2 Wires Cable)
Installation Manual 63

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents