INSTALLATION
ECONOMIZERS WITH EXHAUST
For Use with Bard 3-1/2 thru 6 Ton
Wall Mount Air Conditioners
INSTRUCTIONS
MODEL
EIFM-5B
and Heat Pumps
Bard Manufacturing Company
Bryan, Ohio 43506
Since 1914...moving ahead just as planned.
Manual :
2100-391
Supersedes:
File:
Volume III Tab 19
Date:
04-26-01
© Copyright 2001

Advertisement

loading
Need help?

Need help?

Do you have a question about the EIFM-5B and is the answer not in the manual?

Questions and answers

Summary of Contents for Bard EIFM-5B

  • Page 1 INSTALLATION INSTRUCTIONS ECONOMIZERS WITH EXHAUST MODEL EIFM-5B For Use with Bard 3-1/2 thru 6 Ton Wall Mount Air Conditioners and Heat Pumps Manual : 2100-391 Bard Manufacturing Company Supersedes: Bryan, Ohio 43506 File: Volume III Tab 19 Since 1914...moving ahead just as planned.
  • Page 2: Table Of Contents

    Economizer – WA, WL & WH Series ..... 7 Figure 7 ..............9 TABLES Table 1 ..............1 Table 2 ..............6 Manufactured under U.S. patent number 5,301,744. Other patents pending. COPYRIGHT APRIL 2001 BARD MANUFACTURING COMPANY BRYAN, OHIO USA 43506...
  • Page 3: General

    The EIFM-5 economizer is designed to be used with heating and air conditioning technician. These Bard 3-1/2 thru 5 ton wall mount series air conditioners instructions serve as a guide to the technician installing and heat pumps equipped with low ambient fan cycling the economizer package.
  • Page 4: Installation

    INSTALLATION BASIC INSTALLATION 2. Remove and save the existing exterior blower access and service access panels on the Bard wall 1. Unpack the economizer assembly which includes mount unit. (See Figure 1.) the integral economizer with attached electrical 3. Remove and save existing unit return air filter and harness, mixed air thermistor, miscellaneous center screw in front grille.
  • Page 5 bracket. Once the economizer is fully inserted, slide with wire tie. Connect wires to thermistor. (See the economizer to the right until it is tight against Figure 2.) the back of the control panel. (See Figure 2.) 7. Open unit control panel to gain access to unit low IMPORTANT: Position front lip of economizer on voltage terminal block.
  • Page 6 FIGURE 3 MIS-1356 Manual 2100-391 Page 4...
  • Page 7 Manual 2100-391 Page...
  • Page 8 10. Connect leads with fork terminal to corresponding D. Adjust the enthalpy control to position A, B, points on terminal strip. Re.: C.Y.G. (See wiring C and D to achieve the maximum combination diagram.) of temperature and humidity acceptable for the installation as per Table 2 below.
  • Page 9: Economizer - Wa, Wl & Wh Series

    ECONOMIZER SEQUENCE OF OPERATION ECONOMIZER – WA, WL & WH SERIES Condition A – Cool Outdoors FEATURES First stage cooling closes and powers the economizer • One piece construction – easy to install with no dampers to economizer mode and the indoor blower mechanical linkage adjustment required.
  • Page 10 CONDITION B – WARM OUTDOORS First stage cooling cycles the compressor and dampers remain in mechanical cooling mode. FIGURE 6 MECHANICAL COOLING OPERATION MIS-348 Manual 2100-391 Page 8...
  • Page 11 FIGURE 7 ECONOMIZER OPERATION FOR SINGLE COMPRESSOR UNIT MIS-1351 WALL THERMOSTATS FOR HEAT PUMPS WITH ECONOMIZER FOR AIR CONDITIONING WITH ECONOMIZER Thermostat Part 8403-027 (White Rodgers IF92-71) Thermostat Part No. 8403-021 (Honeywell Electronic Heat Pump Thermostat T874D1934) 2 Stage Cool / 3 Stage Heat Subbase part no.
  • Page 12 Manual 2100-391 Page 10...