INSTALLATION INSTRUCTIONS ECONOMIZER WITH EXHAUST MODEL WGEIFM-3C WGEIFM-5C WGSEIFM-5 For Use with Bard 3 - 5 Ton Step Capacity 2 - 5 Ton Single Stage Wall Mount Air Conditioners with Gas Heat Bard Manufacturing Company, Inc. Manual : 2100-498B Supersedes:...
They are not intended as a step equipped with fan cycling controls. The WGSEIFM-5 by step procedure with which the mechanically inclined economizer is designed to be used with Bard WG*S 2- owner can install the package. stage cooling and W42-60G 1-stage cooling, 1-stage...
INSTALLATION BASIC INSTALLATION 1. Unpack the ventilator assembly which includes the WARNING integral ventilator with attached electrical harness, blank-off plate and miscellaneous hardware. Open and lock unit disconnect switch before 2. Remove and save the existing exterior blower installing this accessory to prevent injury or access and service access panels (see Figure 1).
6. Open control panel to gain access to unit low 5. Install ventilator sheet metal assembly by inserting the ventilator into the unit – centering between the voltage terminal block. tubing on the left and the control panel on the right. 7.
FIGURE 3 INSTALL LOOSE PIECE WIRE HARNESS PLUG ROUTE WIRES THROUGH WIRE MOUNT, AND INTO HOLE AT REAR OF UNIT INTO LOW VOLTAGE TERMINAL BLOCK AREA PLUG TO SECURE INTO FILTER TRAY MIS-2415 Manual 2100-498B Page 6 of 17...
FIGURE 4 WGSEIFM-5 WIRING DIAGRAM EIFM CONTROL PANEL DANGER ORANGE ENTHALPY SENSOR * ELECTRICAL SHOCK HAZARD * DISCONNECT POWER BEFORE SERVICING BLACK CONROL RELAY BLACK BROWN ORANGE YELLOW PURPLE UNIT PINK 24 VOLT TERMINAL STRIP BLUE LOGIC MODULE UNIT BLOWER SECTION 4056-197 B 9.
EXAMPLE: Adjust the thermostat temperature to engage the first stage of cooling only (Y). This will 1. Measure return air temperature (RAT) cause the dampers to modulate to achieve (assume 75° F for example). mixed air temperature of 55° provided outside 2.
W24G EIFM Airflow Versus Position - Low Speed Free Blow .15" ESP .30" ESP closed Open Damper Position W24G EIFM Airflow Versus Position - Medium Speed Free Blow .15" ESP .30" ESP closed Open Damper Position W24G EIFM Airflow Versus Position - High Speed Free Blow .15"...
W30-36G EIFM Airflow Versus Position - Low Speed Free Blow .15" ESP .30" ESP closed Open Damper Position W30-36G EIFM Airflow Versus Position - Medium Speed Free Blow .15" ESP .30" ESP closed Open Damper Position W30-36G EIFM Airflow Versus Position - High Speed Free Blow .15"...
W42-60G EIFM Airflow Versus Position - Low Speed Free Blow 0.15" ESP 0.30" ESP closed Open Damper Position W42-60G EIFM Airflow Versus Position - Medium Speed Free Blow 0.15" ESP 0.30" ESP closed Open Damper Position W42-60G EIFM Airflow Versus Position - High Speed Free Blow 0.15"...
ECONOMIZER SEQUENCE OF If second stage closes on the thermostat, the dampers return to the closed or minimum position setting and the OPERATION compressor starts for mechanical cooling. CONDITION A — COOL OUTDOORS First stage cooling closes and powers the economizer dampers to economizer mode and the indoor blower starts.
CONDITION B — WARM OUTDOORS First stage cooling cycles the compressor and dampers remain in mechanical cooling mode. FIGURE 8 CALL FOR COOLING OPERATION Manual 2100-498B Page 17 of 17...