BSL07/13/14/20
Installation Instructions
Self-Testing Emergency LED Driver
1. This product is for use with an emergency LED lighting load in compliance with NFPA-101 and
NEC 700.12. See table on Page 2 for product ratings.
2. Make sure all connections are in accordance with the National Electrical Code or Canadian Electrical Code
and any local regulations.
3. To reduce the risk of electric shock, disconnect both normal and emergency power supplies before servicing.
Follow the instructions in the OPERATIONS section to disable the output of this LED driver.
4. This emergency driver is intended to be mounted on or enclosed within a luminaire and is suitable for both
factory or fi eld installation. Emergency driver with separate battery is intended to be enclosed within a
luminaire and is suitable for both factory or fi eld installation. For fi eld installation, please see "Step #1
Determine Suitability" on Page 2 of these instructions.
5. This product is suitable for use in damp locations product is also suitable for installation in sealed and
gasketed fi xtures. Product is not suitable for heated air outlets, outdoors, wet, or hazardous locations.
Maximum allowable case temp is 65ºC. See the unit label for Tcase measurement location. See Page 2 for
rated ambient temperature ranges.
6. An unswitched AC power source is required (120-277 VAC, 50/60 Hz).
7. Do not install near gas or electric heaters.
8. Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not fi eld
replaceable. Contact the manufacturer for information on service.
9. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
10. Do not use this product for other than intended use.
11. Installation and servicing should be performed by qualifi ed personnel.
12. Equipment should be mounted in locations and at heights where it will not be subjected to tampering by
unauthorized personnel.
13. For Canadian application the output terminals should be in compliance with the accessibility requirement of
the Canadian Electric Code.
14. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1)
this device may not cause harmful interference, and (2) this device must accept any interference that may
cause undesired operation.
15. This product must be grounded. See the wiring diagrams for details.
236 Mt. Pleasant Rd. • Collierville, TN USA 38017-2752 • Tech Support 888-263-4638 • Fax 901-853-5009 • www.bodine.com
THIS PRODUCT CONTAINS A RECHARGEABLE LITHIUM-ION BATTERY.
THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY.
Bodine © 2020 Signify Holding. All rights reserved.
WHEN USING ELECTRICAL EQUIPMENT, BASIC
SAFETY PRECAUTIONS SHOULD ALWAYS BE
FOLLOWED, INCLUDING THE FOLLOWING:
03/24/21
442295482661

Advertisement

loading
Need help?

Need help?

Do you have a question about the BSL07B and is the answer not in the manual?

Questions and answers

Summary of Contents for Bodine BSL07B

  • Page 1 THIS PRODUCT CONTAINS A RECHARGEABLE LITHIUM-ION BATTERY. THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY. 03/24/21 Bodine © 2020 Signify Holding. All rights reserved. 236 Mt. Pleasant Rd. • Collierville, TN USA 38017-2752 • Tech Support 888-263-4638 • Fax 901-853-5009 • www.bodine.com 442295482661...
  • Page 2 Make sure the necessary branch circuit wiring is available. An unswitched source of power is required. The emergency driver must be fed from the same branch circuit as the AC driver. Order Code Product 12NC Output Output Operating Rated Conduit Output Rating Voltage...
  • Page 3 NOTE: This product has been designed to reliably interface with a wide selection of LED loads and is electrically compatible with every simple LED array that meets criteria 1 and 2 above. However, compatibility cannot be guaranteed with all current and future LED systems.
  • Page 4 To perform a manual self-diagnostic test, push and hold the test switch for a minimum of 5 seconds while AC power is applied. Once the test switch is released the emergency driver will perform a 30 second diagnostic test. During this test, the unit will monitor the operation of the LED load, battery voltage, and LED load connections.
  • Page 5 TYPICAL SCHEMATICS ONLY. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS. For short-term testing of the emergency function, the battery must be charged for at least one hour. The emergency driver must be charged for at least 24 hours before conducting a long-term test.
  • Page 6 TYPICAL SCHEMATICS ONLY. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS. For short-term testing of the emergency function, the battery must be charged for at least one hour. The emergency driver must be charged for at least 24 hours before conducting a long-term test.

This manual is also suitable for:

Bsl20bBsl13bBsl14bBsl20b2uek55c1i1Bsl20b2uek55l1i1Bsl20b2uck55c1i1 ... Show all