For R32/R410A model, use piping, flare nut and tools which is specified for R32/R410A refrigerant. Using of existing (R22) piping,
flare nut and tools may cause abnormally high pressure in the refrigerant cycle (piping), and possibly result in explosion and injury.
For R32 and R410A, the same flare nut on the outdoor unit side and pipe can be used.
Since the working pressure for R32/R410A is higher than that of refrigerant R22 model, replacing conventional piping and flare nuts
11.
on the outdoor unit side are recommended.
If reuse piping is unavoidable, refer to instruction "IN CASE OF REUSING EXISTING REFRIGERANT PIPING"
Thickness of copper pipes used with R32/R410A must be more than 0.8 mm. Never use copper pipes thinner than 0.8 mm.
It is desirable that the amount of residual oil less than 40 mg/10 m.
Engage authorized dealer or specialist for installation and servicing. If installation or servicing done by the user is incorrect, it will cause
12.
water leakage, electrical shock or fire.
For refrigeration system work, Install according to this installation instructions strictly. If installation is defective, it will cause water
13.
leakage, electrical shock or fire.
Use the attached accessories parts and specified parts for installation and servicing. Otherwise, it will cause the set to fall, water
14.
leakage, fire or electrical shock.
Install at a strong and firm location which is able to withstand weight of the set. If the strength is not enough or installation is not properly
15.
done, the set will drop and cause injury.
For electrical work, follow the national regulation, legistration and this installation instructions. An independent circuit and single outlet
16.
must be used. If electrical circuit capacity is not enough or defect found in the electrical work, it will cause electrical shock or fire.
Do not use joint cable for indoor/outdoor connection cable. Use the specified indoor/outdoor connection cable, refer to instruction
CONNECT THE CABLE TO THE INDOOR UNIT and connect tightly for indoor/outdoor connection. Clamp the cable so that no external
17.
force will have impact on the terminal.
If connection or fixing is not perfect, it will cause heat up or fire at the connection.
Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will
18.
cause fire or electrical shock.
This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD),
19.
with sensitivity of 30mA at 0.1 sec or less. Otherwise, it may cause electrical shock and fire in case of equipment breakdown or
insulation breakdown.
During installation, install the refrigerant piping properly before running the compressor. Operation of compressor without fixing
20.
refrigeration piping and valves at opened position will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in
explosion, injury etc.
During pump down operation, stop the compressor before removing the refrigeration piping. Removal of refrigeration piping while
21.
compressor is operating and valves are opened will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in
explosion, injury etc.
Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare
22.
may break and cause refrigerant gas leakage.
After completion of installation or service, confirm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant
23.
contacts with fire.
24.
Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant contacts with fire.
25.
Be aware that refrigerants may not contain an odour.
This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and telephone.
26.
Otherwise, it may cause electrical shock in case of equipment breakdown or insulation breakdown.
27.
Do not modify the machine, part, material during repairing service.
28.
If wiring unit is supplied as repairing part, do not repair or connect the wire even only partial wire break. Exchange the whole wiring unit.
29.
Do not wrench the fasten terminal. Pull it out or insert it straightly.
30.
Must not use other parts except original parts describe in catalog and manual.
Do not install the unit in a place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding
1.
of the unit, it may cause fire.
2.
Prevent liquid or vapor from entering sumps or sewers since vapor is heavier than air and may form suffocating atmospheres.
Do not release refrigerant during piping work for installation, servicing, reinstallation and during repairing a refrigerant parts.
3.
Take care of the liquid refrigerant, it may cause frostbite.
4.
Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
Do not touch the sharp aluminium fin, sharp parts may cause injury.
5.
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the
6.
furniture.
WARNING
CAUTION
4