Complete Start Up Procedure - UTICA BOILERS OLSSV-050 Installation, Operation & Maintenance Manual

Table of Contents

Advertisement

!
WARNING
Asphyxiation hazard. Carbon monoxide is odorless,
tasteless, clear colorless gas, which is highly toxic.
Verify cap is firmly placed on combustion analyzer
port to prevent CO emission. Failure to do so could
result in death or serious injury.
FIGURE 9-5 Combustion Analyzer Port
Shown 50/75/100 Model
Combustion
Analyzer Port
FIGURE 9-6 Burner Flame
9 - START UP PROCEDURE
Burner

9.7 Complete Start Up Procedure

1.
Reset control parameters to operating settings if
adjusted to allow startup and operation test.
2.
Follow instructions TO TURN OFF GAS TO APPLIANCE
(page 42) if boiler is not being placed into
immediate operation.
3.
Enter installer information on Warranty Registration
Card.
4.
Gather all instructions, manuals, wiring diagrams,
warranty registration card and other supporting
information. Review with user and/or affix in
conspicuous location adjacent to boiler.
FIGURE 9-7 Control Module J7 Connector
Look for BLUE flame with slight
YELLOW tips evenly spaced
around burner
41
J7 CONNECTOR
P/N# 2400010616, Rev. F [10/26/2015]

Advertisement

Table of Contents
loading

This manual is also suitable for:

Olssv-075Olssv-100Olssv-150Olssv-200

Table of Contents