Electrical Connections; Line Voltage Connections; External Connections - UTICA BOILERS OLSSV-050 Installation, Operation & Maintenance Manual

Table of Contents

Advertisement

8.1 General
Electrically bond boiler to ground in accordance with
requirements of authority having jurisdiction. Refer to:
• USA- National Electrical Code, ANSI/NFPA 70.
• Canada - Canadian Electrical Code, Part I, CSA C22.1:
Safety Standard for Electrical Installations.
8.2 Electric Knockouts (figure 8-1)
• Six knockouts located on bottom of chassis.
A. Four knockouts located under junction box are
reserved for high voltage wires. Choose connectors
using total diameter of wire bundles.
B. Two knockouts located to right of high voltage
knockouts (outside of junction box) are reserved
for low voltage wiring. Use supplied grommets
when using these knockouts.
8.3 Line Voltage Connections (figure 8-2)
• Boiler
A. Provide individual 120V, 15 amp circuit
(recommended) with fused disconnect or service
switch as required by authority having jurisdiction.
B. Open High Voltage Junction Box (see figures 3-4
and 3-5) to access line voltage terminal strip.
C. Connect 120 VAC circuit to line voltage terminal
strip 120 VAC L,N,G.
• Central Heating Pump
A. Isolate pump from control module if pump FLA (Full
Load Amps) exceeds maximum allowable current
draw. See Figure 8-3 and Table 9.
B. Connect pump to line voltage terminal strip CH
PUMP L,N,G.
• Domestic Hot Water Pump
A. Isolate pump from control module if pump FLA
exceeds maximum allowable current draw. See
Figure 8-3 and Table 9.
B. Connect pump to line voltage terminal strip DHW
PUMP L,N,G.
• Primary Pump
A. Isolate pump from control module if pump FLA
exceeds maximum allowable current draw. See
Figure 8-3 Table 9.
B. Connect pump to line voltage terminal strip primary
pump, L, N, G.
8.4 External Connections (figure 8-4)
• User Interface Terminals
A. Factory wired to USER INTERFACE terminals
B. Optional - Remote mount user interface for
improved access. Use low voltage knockout.
C. Maximum wire length is 100 ft (30m) for 22 ga.
wire, or 150 ft (45m) for 18 ga. wire.

8 - ELECTRICAL CONNECTIONS

Electrical shock hazard. Turn OFF electrical power
supply at service panel before making electrical
connections. Failure to do so could result in death
or serious injury.
Wiring diagrams can be found in Section 14 of this
Manual.
FIGURE
5.26"(134mm) 50-100mbh
8.17"(208mm) 150/200mbh
FIGURE
Table 9 - Maximum Allowable Current Draw
MBH
50
75
100
150
200
If CH or DHW pump current is more than the maximum
allowable current draw install proper field sourced relays as
shown in figure 8-3.
Maximum allowable total amperage of all 3 pumps must not
exceed 20 amps.
34
!
WARNING
NOTICE
8-1
Electric Knockouts Bottom Of Boiler
Front of Boiler
High Voltage
Knockouts
8-2

Line Voltage Connections

CH
DHW
PUMP
PUMP
1 A*
1 A*
10 A**
10 A**
Low Voltage Knockouts
(Use supplied
grommets when using
these knockouts)
Back of Boiler
PRIMARY
NOTE
PUMP
*Powered by
10 A**
Control Board
**Powered by
10 A**
installed 10 Amp
relay
P/N# 2400010616, Rev. F [10/26/2015]