Advertisement

Quick Links

KA01312D/06/EN/03.22-00
71574815
2022-08-01
Products
Brief Operating Instructions
Flowmeter
Proline 500
HART transmitter
with electromagnetic sensor
These instructions are Brief Operating Instructions; they are
not a substitute for the Operating Instructions pertaining to
the device.
Brief Operating Instructions part 2 of 2: Transmitter
Contain information about the transmitter.
Brief Operating Instructions part 1 of 2: Sensor →  3
Solutions
Services

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Flowmeter Proline 500 and is the answer not in the manual?

Questions and answers

Summary of Contents for Endress+Hauser Flowmeter Proline 500

  • Page 1 Products Solutions Services KA01312D/06/EN/03.22-00 71574815 2022-08-01 Brief Operating Instructions Flowmeter Proline 500 HART transmitter with electromagnetic sensor These instructions are Brief Operating Instructions; they are not a substitute for the Operating Instructions pertaining to the device. Brief Operating Instructions part 2 of 2: Transmitter Contain information about the transmitter.
  • Page 2 Flowmeter Proline 500 Order code: XXXXX-XXXXXX Ser. no.: XXXXXXXXXXXX Ext. ord. cd.: XXX.XXXX.XX Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 Endress+Hauser...
  • Page 3 These Brief Operating Instructions are Brief Operating Instructions Part 2: Transmitter. The "Brief Operating Instructions Part 1: Sensor" are available via: • Internet: www.endress.com/deviceviewer • Smart phone/tablet: Endress+Hauser Operations App Detailed information about the device can be found in the Operating Instructions and the other documentation: • Internet: www.endress.com/deviceviewer •...
  • Page 4: Table Of Contents

    Table of contents Flowmeter Proline 500 Table of contents About this document ............. . 5 Symbols .
  • Page 5: About This Document

    Flowmeter Proline 500 About this document About this document Symbols 1.1.1 Safety symbols DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury. WARNING This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury.
  • Page 6 About this document Flowmeter Proline 500 Symbol Meaning Potential equalization connection (PE: protective earth) Ground terminals that must be connected to ground prior to establishing any other connections. The ground terminals are located on the interior and exterior of the device: •...
  • Page 7: Safety Instructions

    Flowmeter Proline 500 Safety instructions Safety instructions Requirements for the personnel The personnel must fulfill the following requirements for its tasks: ‣ Trained, qualified specialists must have a relevant qualification for this specific function and task. ‣ Are authorized by the plant owner/operator.
  • Page 8: Workplace Safety

    Verification for borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability as minute changes in the temperature, concentration or level of contamination in the process can alter the corrosion resistance properties.
  • Page 9: Security

    Flowmeter Proline 500 Safety instructions IT security Our warranty is valid only if the product is installed and used as described in the Operating Instructions. The product is equipped with security mechanisms to protect it against any inadvertent changes to the settings.
  • Page 10: Product Description

    Product description Flowmeter Proline 500 Product description The measuring system consists of a Proline 500 transmitter and an electromagnetic Proline Promag sensor. The transmitter and sensor are mounted in physically separate locations. They are interconnected via two connecting cable(s). Transmitter with integrated ISEM (intelligent sensor electronics module)
  • Page 11: Mounting

    Flowmeter Proline 500 Mounting Mounting For detailed information about mounting the sensor, see the Sensor Brief Operating Instructions →  3 Mounting the transmitter housing CAUTION Ambient temperature too high! Danger of electronics overheating and housing deformation. ‣ Do not exceed the permitted maximum ambient temperature .
  • Page 12 Mounting Flowmeter Proline 500 4.1.2 Post mounting WARNING Order code for "Transmitter housing", option L "Cast, stainless": cast transmitters are very heavy. They are unstable if they are not mounted on a secure, fixed post. ‣ Only mount the transmitter on a secure, fixed post on a stable surface.
  • Page 13: Turning The Transmitter Housing

    Flowmeter Proline 500 Mounting Turning the transmitter housing To provide easier access to the connection compartment or display module, the transmitter housing can be turned. 4 mm 7 Nm (5.2 lbf ) A0043150  3 Ex housing Loosen the fixing screws.
  • Page 14: Turning The Display Module

    Mounting Flowmeter Proline 500 Turning the display module The display module can be turned to optimize display readability and operability. – – – 3 mm A0030035 Depending on the device version: Loosen the securing clamp of the connection compartment cover.
  • Page 15: Cover Locking

    Flowmeter Proline 500 Mounting Cover locking NOTICE Order code , option L "Cast, stainless": The covers of the transmitter housing are provided with a borehole to lock the cover. The cover can be locked using screws and a chain or cable provided by the customer on site.
  • Page 16: Transmitter Post-Installation Check

    Mounting Flowmeter Proline 500 Transmitter post-installation check The post-installation check must always be performed after the following tasks: • Mounting the transmitter housing: • Post mounting • Wall mounting • Turning the transmitter housing • Turning the display module Is the device undamaged (visual inspection)? ...
  • Page 17: Electrical Connection

    Flowmeter Proline 500 Electrical connection Electrical connection WARNING Live parts! Incorrect work performed on the electrical connections can result in an electric shock. ‣ Set up a disconnecting device (switch or power-circuit breaker) to easily disconnect the device from the supply voltage.
  • Page 18 Electrical connection Flowmeter Proline 500 Signal cable Current output 4 to 20 mA HART A shielded cable is recommended. Observe grounding concept of the plant. Current output 0/4 to 20 mA Standard installation cable is sufficient Pulse /frequency /switch output...
  • Page 19 Flowmeter Proline 500 Electrical connection Cable length (max.) Depends on the medium conductivity, max. 200 m (656 ft) Cable lengths (available for 5 m (15 ft), 10 m (32 ft), 20 m (65 ft) or variable length up to max. 200 m (656 ft)
  • Page 20 Electrical connection Flowmeter Proline 500 5.2.4 Terminal assignment Transmitter: supply voltage, input/outputs The terminal assignment of the inputs and outputs depends on the individual order version of the device. The device-specific terminal assignment is documented on an adhesive label in the terminal cover.
  • Page 21 Flowmeter Proline 500 Electrical connection In the case of the coil current cable: Insulate one core of the three-core cable at the level of the core reinforcement. You only require two cores for the connection. For cables with fine-wire cores (stranded cables): Fit the cores with ferrules.
  • Page 22 Electrical connection Flowmeter Proline 500 Sensor Electrode cable Coil current cable 70 (2.76) 80 (3.15) 17 (0.67) 40(1.57) 8 (0.31) 8 (0.31) ≥ 1 (0.04) A0029438 A0029439 Engineering unit mm (in) A = Terminate the cable B = Fit ferrules on cables with fine-wire cores (stranded cables) 1 = Red ferrules, ...
  • Page 23 Flowmeter Proline 500 Electrical connection Preparing the connecting cable: Promag P and Promag W Transmitter Electrode cable Coil current cable (3.54) 100 (3.94)* 70 (2.76) 80 (3.15) 50 (1.97) 17 (0.67) 50 (1.97) 8 (0.3) 10 (0.4) 8 (0.3) A0029329...
  • Page 24 Electrical connection Flowmeter Proline 500 Sensor Transmitter Coil current cable 20 (0.8)* 20 (0.8)* 160 (6.30)* 170 (6.7)* 80 (3.15) 70 (2.76) 50 (1.97) 50 (1.97) 18.5 (0.73) 10 (0.4) 6 (0.24) 8 (0.3) ³1 (0.04) A0029337 A0029336 Engineering unit mm (in)
  • Page 25: Connecting The Measuring Device

    Flowmeter Proline 500 Electrical connection Connecting the measuring device NOTICE Limitation of electrical safety due to incorrect connection! ‣ Have electrical connection work carried out by appropriately trained specialists only. ‣ Observe applicable federal/national installation codes and regulations. ‣ Comply with local workplace safety regulations.
  • Page 26 Electrical connection Flowmeter Proline 500 Proline Promag P and Promag W E2 S2 41 42 37 36 n.c. n.c. n.c. 41 42 E1 E2 A0029145 Coil current cable Signal cable Connecting the connecting cable to the sensor connection housing Connection via terminals with order code for "Housing"...
  • Page 27 Flowmeter Proline 500 Electrical connection Connecting the sensor connection housing via terminals 10 (0.4) 3 mm 22 mm 24 mm A0029612 Loosen the securing clamp of the housing cover. Unscrew the housing cover. Push the cable through the cable entry . To ensure tight sealing, do not remove the sealing ring from the cable entry.
  • Page 28 Electrical connection Flowmeter Proline 500 Connecting the sensor connection housing via terminals 10 (0.4) 8 mm 22 mm 24 mm A0029617 Release the securing screw of the housing cover. Open the housing cover. Push the cable through the cable entry . To ensure tight sealing, do not remove the sealing ring from the cable entry.
  • Page 29 Flowmeter Proline 500 Electrical connection Connecting the connecting cable to the transmitter 10 (0.4) 3 mm 22 mm 24 mm A0029592 Loosen the securing clamp of the connection compartment cover. Unscrew the connection compartment cover. Push the cable through the cable entry. To ensure tight sealing, do not remove the sealing ring from the cable entry.
  • Page 30 Electrical connection Flowmeter Proline 500 5.3.2 Connecting the signal cable and the supply voltage cable A0026781 Terminal connection for supply voltage Terminal connection for signal transmission, input/output Terminal connection for signal transmission, input/output or terminal connection for network connection via service interface (CDI-RJ45) Protective earth (PE) –...
  • Page 31 Flowmeter Proline 500 Electrical connection N ic N ic t e r t e r e r g ö f f e r g ö f f iz e iz e t e n t e n r ir r ir...
  • Page 32: Ensuring Potential Equalization

    Electrical connection Flowmeter Proline 500 22 mm 24 mm – A0029816 10. Connect the cable according to the terminal assignment.  Signal cable terminal assignment: The device-specific terminal assignment is documented on an adhesive label in the terminal cover. Supply voltage terminal assignment: Adhesive label in the terminal cover or →...
  • Page 33 • Grounding rings can be ordered separately as an accessory from Endress+Hauser . When ordering make sure that the grounding rings are compatible with the material used for the...
  • Page 34 Electrical connection Flowmeter Proline 500 Potential equalization via grounding electrodes on process connection A0028972 Hexagonal-headed bolts of process connection Integrated grounding electrodes O-ring seal Sensor 5.4.2 Promag P and Promag W CAUTION Insufficient or faulty potential equalization. May destroy the electrodes and thus result in the complete failure of the device! ‣...
  • Page 35 Flowmeter Proline 500 Electrical connection Metal, grounded pipe A0016315  4 Potential equalization via measuring tube Unlined and ungrounded metal pipe This connection method also applies in situations where: • The customary potential equalization is not used • Equalizing currents are present...
  • Page 36 Electrical connection Flowmeter Proline 500 A0029339  6 Potential equalization via ground terminal and ground disks (PE = P Connect the ground disks to the ground terminal via the ground cable. Connect the ground disks to ground potential.  PE = P...
  • Page 37: Ensuring The Degree Of Protection

    Flowmeter Proline 500 Electrical connection Ensuring the degree of protection The measuring device fulfills all the requirements for the degree of protection IP66/67, Type 4X enclosure. To guarantee the degree of protection IP66/67, Type 4X enclosure, carry out the following steps after the electrical connection: Check that the housing seals are clean and fitted correctly.
  • Page 38: Operation Options

    Operation options Flowmeter Proline 500 Operation options Overview of operation options A0034513 Local operation via display module Computer with Web browser (e.g. Internet Explorer) or with operating tool (e.g. FieldCare, DeviceCare, AMS Device Manager, SIMATIC PDM) Field Xpert SFX350 or SFX370...
  • Page 39: Structure And Function Of The Operating Menu

    Flowmeter Proline 500 Operation options Structure and function of the operating menu 6.2.1 Structure of the operating menu Operating menu for operators and maintenances Language Operation task-oriented Setup Diagnostics Operating menu for experts Expert function-oriented A0014058-EN  7 Schematic structure of the operating menu 6.2.2...
  • Page 40: Access To The Operating Menu Via The Local Display

    Operation options Flowmeter Proline 500 Access to the operating menu via the local display X X X X X X 19.184 mA 12.5 X X X X X X Language 20.50 Ã English Deutsch Español Français Xxxxxxx A B C D E F G H I J K M N O P Q R S T U V W +0.000 Xx...
  • Page 41 Flowmeter Proline 500 Operation options 6.3.1 Operational display Explanatory symbols for the measured value Status area • Depends on the device version, e.g.: The following symbols appear in the status area of the • : Volume flow operational display at the top right: •...
  • Page 42 Operation options Flowmeter Proline 500 Numeric editor Confirms selection. Moves the input position one position to the left. Exits the input without applying the changes. Inserts decimal separator at the cursor position. Inserts minus sign at the cursor position. Clears all entered characters.
  • Page 43: Access To The Operating Menu Via The Operating Tool

    Flowmeter Proline 500 System integration Keys and meaning Minus/Enter key combination (press the keys simultaneously) With an operational display: • If keypad lock is active: Pressing the key for 3 s deactivates the keypad lock. • If keypad lock is not active: Pressing the key for 3 s opens the context menu including the option for activating the keypad lock.
  • Page 44: Setting The Operating Language

    Commissioning Flowmeter Proline 500 • Checklist for "Post-mounting check" →  16 • Checklist for "Post-connection check" →  37 Setting the operating language Factory setting: English or ordered local language X X X X X X X 20.50 Main menu...
  • Page 45: Protecting Settings From Unauthorized Access

    Flowmeter Proline 500 Diagnostic information Example: Available submenus, wizards Meaning Status input Current output 1 to n Pulse/frequency/switch output 1 to n Relay output Double pulse output Display Configuration of the display format on the local display Low flow cut off...
  • Page 46 Diagnostic information Flowmeter Proline 500 X X X X X X X X X X X X X X 20.50 S801 Supply voltage Menu Diagnostic list Diagnostics 1 S801 Supply voltage Diagnostics 2 Diagnostics 3 Supply voltage (ID:203) S801 0d00h02m25s...
  • Page 48 *71574815* 71574815 www.addresses.endress.com...

Table of Contents