Troubleshooting; Check Methods - Mitsubishi Electric CITY MULTI PEFY-P06NMAU-E4 Technical & Service Manual

Hide thumbs Also See for CITY MULTI PEFY-P06NMAU-E4:
Table of Contents

Advertisement

[ VIII Troubleshooting ]
VIII Troubleshooting

[1] Troubleshooting

1. Check methods

1. Component and check points
(1) Thermistor
Room temperature thermistor (TH21)
Liquid pipe thermistor (TH22)
Gas pipe thermistor (TH23)
Disconnect the connector and measure the resistance between terminals with a tester.
(Ambient temperature 10°C - 30°C[50°F-86°F])
Normal
4.3k
- 9.6k
(Refer to the thermistor characteristic graph below.)
1) Thermistor characteristic graph
Low-temperature thermistor
Room temperature thermistor (TH21)
Liquid pipe thermistor (TH22)
Gas pipe thermistor (TH23)
Drain sensor (DS)
Thermistor R
= 15 k
0
Multiplier of B = 3480 k
Rt = 15 exp { 3480(
273+t
0°C
32°F 15k
10°C
50°F 9.6k
20°C
68°F 6.3k
25°C
77°F 5.2k
30°C
86°F 4.3k
40°C 104°F 3.0k
(A) Temperature
(B) Resistance
(2) Fan motor (CNMF)
Refer to the page on "DC fan motor (fan motor/indoor control board)."
(3) Linear expansion valve
Disconnect the connector, and measure the resistance between terminals with a tester.
Refer to the next page for details.
CN60
(F)
1
(E)
2
(D)
3
M
(C)
4
LEV
(A)
6
(A)
Red
(C)
Blue
(D)
Orange
HWE20150
Abnormal
Open or short
3%
2%
1
1
) }
273
(°C)[°F]
(k )
Normal
1-6
2-6
White-Red
Yellow-Red
(150Ω) ±10%
(E)
Yellow
(F)
White
50
40
30
20
10
0
-20
-10
0
10
20
30
-4
14
32
50
68
86
(A)
3-6
4-6
Orange-Red
Blue-Red
- 25 -
40
50
104 122
Abnormal
Open or short
GB

Advertisement

Table of Contents
loading

Table of Contents