Upon reading and following the instructions in this manual, you will be rewarded many years of trouble free service from your new 110-Z3. If reading manuals is not for you, it is essential that you at least read the captions followed by the safety warnings; they are located throughout the manual and are very easy to identify.
25% power output using variable time based zero voltage switching. The chart on the right shows 50% output. INDEECO 110-Z3 variable time base SCR firing. Note how half cycles can be turned on and off providing 0.08 second resolution on 60Hz power lines.
Provide a safety interlock on door to remove power before gaining access to device. The ground/earth connection can be made to the 110-Z3 chassis mounting point on heat sink / side panel. This controller must be installed by a qualified electrician in accordance with any and all local and national electric codes including NEC and any other applicable codes.
Load connections are equally simple; connect the load/ heater to lugs labeled "HTR 1" and "HTR 2" (see figure 1 for correct wire size and torque specs). NOTE: For open delta or 4 wire "wye" connected loads use INDEECO model 110-Z6, 3 phase, 3 leg, 6 SCR control.
THERMOSTAT for FAN FAILURE: On all INDEECO SCR Controls 150 Amps and above, fans are used to cool the SCR heat sinks. INDEECO mounts a Snap-disc thermostat to the heat sink. If the fan fails, air is blocked or a safe ambient temperature is exceeded, the thermostat will activate.
110-Z3 verify 4-20mA signal is hooked up correctly (positive to "+" and negative to "-") on the source and 110-Z3. defective heaters check for output voltage between the three "HTR" lugs. If voltage is present,...
Specify if you need RTV for NEMA 4/4X R Option 10-32 VDC on-off command signal = R32 120 VAC on-off command signal = R120 Third Leg Fuse Option = Example: 110-Z3-480-100 is a zero voltage switched, three phase 2-leg, 480VAC, 100 Ampere SCR Page 9...
16587 Coastal Highway Lewes, DE 19958 Phone 302-703-6865 Fax 302-703-6876 Declaration of Conformity Avatar Instruments A Series SCR Power Controller Avatar Instruments, Inc. 16587 Coastal Highway Lewes, DE 19958 USA Declares that the following product A Series SCR Power Controllers Model Numbers, voltage and current ratings: A1P, A3P, A1Z, A3Z, A6Z - (12, 24, 27, 38, 48, or 60) –...
Page 30
16587 Coastal Highway Lewes, DE 19958 Phone 302-703-6865 Fax 302-703-6876 EN 60947-4-1: 2019: IEC 61000-4-2:2008 Electrostatic discharge immunity IEC 61000-4-3:2006 Radiated, radio frequency electromagnetic field immunity IEC 61000-4-4:2004 Electrical fast-transient / burst immunity IEC 61000-4-5:2006 Surge immunity IEC 61000-4-6:2008 Immunity to conducted disturbances induced by radio-frequency fields IEC 61000-4-11:2004 Voltage dips, short interruptions and voltage variations immunity...