DL9120 / DL9130 Operating Instructions Figure 2 Earth Continuity/Insulation Measurement Figure 3 Voltage measurement using test probes - 3 -...
Page 4
DL9120 / DL9130 Operating Instructions Figure 4 Voltage, RCD, Zs and line impedance measurement at a mains outlet Figure 5 Voltage, RCD, Zs, Ze and line impedance measurement at a distribution board - 4 -...
DL9120 / DL9130 Operating Instructions Limited Warranty & Limitation of Liability DI-LOG Test Equipment guarantees this product to be free from defects in material and workmanship under normal use and service for a period of 2 years. The period of warranty will be effective from the date of purchase.
6.7 Voltage/Frequency Measurement ..........37 7 Environmental Conditions ..............38 8 Maintenance ..................39 8.1 Preparing to work on the DL9120 / DL9130EV......39 8.2 Securing the DL9120 / DL9130EV ..........39 8.3 Cleaning ................... 39 8.4 Battery Replacement ..............40 8.6 Service and Calibration.
Page 8
DL9120 / DL9130 Operating Instructions Disposal of Old Product This product has been designed and manufactured with high quality materials and components that can be recycled and reused. Please familiarise yourself with the appropriate local separate collection system for electrical and electronic products.
DL9120 / DL9130 Operating Instructions 1 User Notes This instrument and its operating instructions are intended for use by trained personnel. The following symbols are used in these operating instructions and on the DL9120 / DL9130EV. Warning of electrical danger! Indicates instructions must be followed to avoid danger to persons.
Prior to any resistance measurement, always ensure that the circuit under test is electrically isolated. Where safe operation of the DL9120 / DL9130EV is no longer possible it should be immediately shut down and secured to prevent accidental operation.
DL9120 / DL9130 Operating Instructions 3 Accessories 3.1 Standard Accessories The DL9120 / DL9130EV is supplied with the following items: DL9120 or DL9130EV unit Padded neck strap Professional carry case DI-LOG mains lead 1.2 M blue test lead 1.2 M red test lead 1.2 M green test lead...
DL9120 / DL9103EV. Note: The DL9120 / DL9130EV will power off if it is inactive for a period of time. In order to re-power the DL9120 / DL9130EV you must rotate the Rotary Switch to off then rotate the Rotary Switch to the required test position.
DL9120 / DL9130 Operating Instructions 4.2 LCD display 1. Icons for function key F1. These icons are used to display the available options for the selected test. Repeatedly pressing function key F1 cycles through the available options. 2. Icons for function key F2. These icons are used to display the available options for the selected test.
Page 15
13. Warning Icons. These icons are used to inform the user of the potential of any hazard or warning which may restrict the operation of the DL9120 / DL9130EV. Details are provided in the relevant parts of these operating instructions.
5 Using the DL9120 / DL9130EV 5.1 Power On To turn the DL9120 / DL9130EV on, simply rotate the rotary switch to the required test position, the DL9120 / DL9130EV will display the battery voltage for a short period of time.
Rotate the rotary switch until the Continuity test is selected. When the continuity test is selected, the DL9120 / DL9130EV will display the user selectable test options for a short period of time; Buzzer, R max, Lead Zero and 15/200mA (15mA DL9130EV only). If the Buzzer or Lead Zero was previously enabled, then the icon will remain on the display when the continuity test is selected.
Lead Zero function has failed, and the display icon will not be shown. Note: For ease of use, the DL9120 / DL9130EV will store the Lead Zero compensation when switched off and recall this value when next switched on. The stored value is only applicable to the test leads used when the compensation measurement was made.
Page 19
1Mohm. Test Lock (F3) The Test Lock is used to ‘lock’ the DL9120 / DL9130EV in a continuous measurement mode, with a single press of the TEST key. When Test Lock is enabled, the LCD shows the padlock icon. When Test Lock is active the TEST key is locked until the option is disabled or the rotary switch is moved to another position.
Not Used Not Used Not used Rotate the rotary switch until the V test is selected. The DL9120 / DL9130EV will automatically measure any voltage present on the test probes. The TEST key is not required. The function keys do not perform any operations while in Voltage mode.
Page 21
Auto Start select The DL9120 / DL9130EV is capable of performing both 2 wire and 3 wire High Current Loop / Line Impedance tests on single phase installations. In order to perform 2 wire tests the correct connection setting (F1) must match the 2 wire connection being made.
/ DL9130EV is connected to the correct mains supply via a mains plug or the test probes. The Auto Start function remains enabled if the switch position is changed or the DL9120 / DL9130EV is powered off. To disable the Auto Start function press F4.
/ DL9130EV is connected to correct mains supply via a mains plug or the test probes. The Auto Start function remains enabled if the switch position is changed or the DL9120 / DL9130EV is powered off. To disable the Z Auto Start function press F4.
Page 24
/ DL9130EV is connected to the correct mains supply via a mains plug or the test probes. The Z Auto Start function remains enabled if the switch position is changed or the DL9120 / DL9130EV is powered off. To disable the Z Auto Start function press F4.
5.9 Auto RCD Test Sequence The DL9120 / DL9130EV will only allow the RCD test to be performed if the correct voltages are detected between line- earth (L-PE illuminated), line-neutral (L-N illuminated) and neutral-earth (N-PE not illuminated).
Page 26
Recall (F3) The RCL (Recall) key is used to recall the results of the last automatic RCD test performed by the DL9120 / DL9130EV. The LCD will update to show all of the relevant parameters for the result displayed. Repeat press the F3 key to cycle through the results.
During the sequence if any test passes and does not trip the RCD then the DL9120 / DL9130EV will move on to the following test. If any test passes and does trip the RCD then the DL9120 / DL9130EV will move onto the following test as soon as the RCD has been reset.
Page 28
Recall (F3) The RCL (Recall) key is used to recall the results of the last automatic RCD test performed by the DL9120 / DL9130EV. The LCD will update to show all of the relevant parameters for the result displayed. Repeat press the F3 key to cycle through the results.
Page 29
DL9120 / DL9130 Operating Instructions TEST When the required settings have been selected, press the TEST key to begin the sequence. The test sequence will perform the following tests at set test current. 6mA DD Setting 30mA Setting Display +6mA...
Shows the status of the RCD under test. 5.11 RCD Trip Time Tests (x1/2, x1 and x5) The DL9120 / DL9130EV will only allow the RCD test to be performed if the correct voltages are detected between line- earth (L-PE illuminated), line-neutral (L-N illuminated) and neutral-earth (N-PE not illuminated).
Page 31
RCD Type A Selective (Pulsating Waveform) RCD Type B (DC) During selective tests the DL9120 / DL9130EV will display a delay timer which counts down from 30s to 0s. Pressing the Test key or turning the rotary switch while the DL9120 / DL9130EV is counting will terminate the count.
DL9120 / DL9130 Operating Instructions 5.12 RCD Variable Mode The DL9120 / DL9130EV will only allow the RCD test to be performed if the correct voltages are detected between line- earth (L-PE illuminated), line-neutral (L-N illuminated) and neutral-earth (N-PE not illuminated).
RCD Type A Selective (Pulsating Waveform) RCD Type B (DC) During selective tests, the DL9120 / DL9130EV will display a delay timer which counts down from 30s to 0s. Pressing the Test key or turning the rotary switch while the DL9120 / DL9130EV is counting will terminate the count.
Page 34
RCD Type A Selective (Pulsating Waveform) RCD Type B (DC) During selective tests the DL9120 / DL9130EV will display a delay timer which counts down from 30s to 0s. Pressing the Test key or turning the rotary switch while the DL9120 / DL9130EV is counting will terminate the count.
5.14 Warning / Test Active Indications The following indications are used across a number of functions in the DL9120 / DL9130EV. Indicates that the DL9120 / DL9130EV is hot. Please allow to cool before proceeding. Indicates that a hazardous test is in progress with by the DL9120 / DL9130EV.
Operating temperature range of 0°C to 40°C. Operating humidity up to 75% without condensation. The DL9120 / DL9130EV can be stored at any temperature in the range -25°C to +65° The batteries should be taken out of the instrument for storage.
Electric shock danger! 8.1 Preparing to work on the DL9120 / DL9130EV. Make the DL9120 / DL9130EV is voltage free as follows, before opening the instrument; Power the unit off using the rotary switch by selecting the Off position on the rotary switch.
Power the unit off by selecting the Off position on the rotary switch. Disconnect all the test leads from the unit Position the DL9120 / DL9130EV face down and release the 4 captive screws in the battery compartment cover. Remove the battery compartment cover.
Power the unit off by selecting the Off position on the rotary switch. Disconnect all the test leads from the unit. Position the DL9120 / DL9130EV face down and release the captive 4 screws in the battery compartment cover. Remove the battery compartment cover.
DL9120 / DL9130 Operating Instructions 8.7 Spare Parts. Part No. 3 wire lead set c/w croc clips (unfused) LS3W9100 3 wire lead set c/w croc clips (fused) FL9100 Mains lead ML9100 Remote Probe RP9100 Carrying Case CCDL9100 For help or advice on Service and Calibration contact:...