Cautions, warnings, and regulatory information
READ AND SAVE THESE INSTRUCTIONS Follow the instructions in this installation manual. These instructions must be followed to avoid damage to
this product and associated equipment. Product operation and reliability depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX™ PRODUCT THAT APPEARS DAMAGED Upon unpacking your Simplex product, inspect the contents
of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex
product supplier.
ELECTRICAL HAZARD Disconnect electrical field power when making any internal adjustments or repairs. All repairs should be
performed by a representative or an authorized agent of your local Simplex product supplier.
STATIC HAZARD Static electricity can damage components. Handle as follows:
• Ground yourself before opening or installing components.
• Prior to installation, keep components wrapped in anti-static material at all times.
Introduction
The 4009-9814 Class A adapter is an optional daughter card that is added to the 4009 IDNAC Repeater to provide support for Class A wiring
extensions.
Consult manual 579-1019 for more information on the 4009 IDNAC Repeater, referred to as "Repeater" from this point on in the manual.
Card specifications
Card Specifications
Operating
o
32
F - 120
Conditions
Up to 93% relative humidity at 90
o
(32
C), non-condensing.
Electrical
IDNAC Output:
Specifications
29V / Special application 3A Max.
IDNAC Input (for Class A Extension
mode):
4 unit loads
LED1
For Class A Local mode: Indicates a
short on Port A.
For Class A extension mode: Indicates a
Short on Port A or an Open when both
sides of the loop are opened.
LED2
For Class A Local mode: Indicates a
short on Port B.
For Class A extension mode: Indicates
a short on Port B or an open when both
sides of the loop are opened.
Included
4 x Screws (6-32 x 1/4 LG, Slotted Torx)
Hardware
4x Standoffs (M/F6-32 x 3/4 LG)
Installation and configuration
Installing the Class A adapter
The Class A Adapter fits onto the repeater card.
Important:
Make sure the power to the 4009 Repeater is disconnected before proceeding.
1.
Remove the screws on each side of TB1.
2.
Make sure that the connector screws on the repeater's TB1 are tightly screwed down or they will obstruct the installation of the Class A Adapter
card.
3.
Install the 4 standoffs on the repeater card.
Table 1: Card specifications
o
o
o
F (0
C-49
C)
o
F
Figure 1: Card Layout
*05791080F*
579-1080 Rev. F

Advertisement

loading

Summary of Contents for Simplex 4009-9814

  • Page 1 • Prior to installation, keep components wrapped in anti-static material at all times. Introduction The 4009-9814 Class A adapter is an optional daughter card that is added to the 4009 IDNAC Repeater to provide support for Class A wiring extensions.
  • Page 2: Setting The Jumpers

    4009-9814 Class A Adapter Card for the 4009 IDNAC Repeater Installation Guide Insert the 4 connectors on the back of the Class A Adapter card into the 4 connectors on the repeater. Secure the Class A Adapter card with the provided screws.
  • Page 3: Wiring Overview

    4009-9814 Class A Adapter Card for the 4009 IDNAC Repeater Installation Guide Wiring Overview The Class A Adapter has one Signal Line Circuit (SLC) for power and communication wiring Once installed on the repeater, the TB1 on the Class A Adapter replaces the TB1 IDNAC OUT on the repeater. It’s important that nothing be connected to the repeater’s TB1.
  • Page 4: General Wiring Guidelines

    4009-9814 Class A Adapter Card for the 4009 IDNAC Repeater Installation Guide General wiring guidelines • Conductors must test free of all grounds. • Wires must not be run through elevator shafts. • All wiring must be done using copper conductors only, unless •...
  • Page 5: Wiring Configurations

    4009-9814 Class A Adapter Card for the 4009 IDNAC Repeater Installation Guide Wiring configurations Loop Class A loop wiring To create a Local Class A Loop: Route the wire from the “B+” and the “B-”outputs on the Class A Adapter terminal block to the appropriate inputs on a peripheral notification appliance.
  • Page 6 4009-9814 Class A Adapter Card for the 4009 IDNAC Repeater Installation Guide Figure 7: Extended Class A loop wiring page 6 579-1080 Rev. F...
  • Page 7 4009-9814 Class A Adapter Card for the 4009 IDNAC Repeater Installation Guide Programming Software requirements The Class A Adapter must be used with ES Panel FACP System Firmware version 1.04 or later. Consult the ES Panel Programmer’s Manual (574-849) for more information.
  • Page 8 © 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice. Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. Simplex, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA).