Start-Up Operation; Division 1 X-Purge Start-Up Operation - Daisy 9016 X-Purge User Manual

Table of Contents

Advertisement

Model 9016 X-Purge Operator Interface

5 Start-Up Operation

5.1 Division 1 X-Purge Start-Up Operation

1.
Set DIP switches
switches for the size enclosure you are going to purge.
2.
Replace and close all access doors and covers
connections are complete.
3.
Apply AC
Intrinsic Safety Barrier to the purge/pressurization control circuit.
4.
Apply purge gas to the system by opening the shutoff
if needed on the air-in box (see drawing P008) to 40 PSI.
When pressure inside the unit reaches 1.0" WC and > 40
5.
LED should illuminate YELLOW, indicating that it is purging.
IF THE INDICATOR DOES NOT ILLUMINATE a thorough inspection for leakage of
the unit must be made. Panel gaskets can be checked with a soap solution. If
leaks are not visually apparent, verify that the pressurized air is clean, dry and is
40 PSI at the inlet.
DO NOT ATTEMPT TO OPEN THE ENCLOSURE WHILE IT IS PRESSURIZED!
OPENING PRESSURIZED ENCLOSURE CAN RESULT IN SERIOUS INJURY!
6. If the Pre-installation Test (Section 3) was completed successfully and the same results
were seen up to this point in the procedure, you may skip the remaining steps of this
procedure. If not, continue to Step Error! Reference source not found.
7. Slowly increase air pressure with the regulator until the purge process stops.
Note Pressure the pressure at which the purge process stops.
The Purge Status LED will flash red and display an error code -
pressure) or
8. Remove AC power from the enclosure for a minimum of 30 seconds. Decrease
the pressure reading on the pressure gauge by 5 PSI.
This change may vary slightly on some units; if in later testing the unit fails with
an
[3 –2]
Note Pressure for use during start-up.
9. Re-apply AC power. The Purge Status LED will illuminate yellow and should purge
for a minimum of 8 minutes. Time will vary according to the flow rate of the air
into the enclosure.
10. After the purge is complete, the Purge Status indicator will illuminate green.
AC power is now applied to the internal electronics to power on the display or PC.
If the purge status light blinks
11.
page 12 for error code details.
February 2022
(see drawing P008, note 8 and drawing E029 note 3 to set the DIP
power.
The Purge Status LED will illuminate RED
[3 –2]
(over-flow).
(over-flow) error code, decrease the inlet pressure by another 2 PSI.
red, refer to Table 6.1 X-Purge Status Light Key
when the air, signal, and power
valve.
11
Daisy Data Displays, Inc.
indicating power though the
Adjust pressure regulator
SCFH, the Purge Status
[2 – 2]
(over
D010-000002