7.5. Addressing

The detector address is set via three rotary switches in the detector housing. To set the address,
turn the rotary switch to the desired position using a pan head slotted screwdriver. Permissible
address range: 001 to 254. Settings between 255 and 299 trigger an error message on the fire pan-
el.
Manual addressing: All detectors in a loop or stub line receive an address between 1 and 254.
Automatic addressing: All detectors receive the address '000'. The address is allocated automati-
cally by the fire panel.
Addressing for BZ 500 LSN, UEZ 2000 LSN, UGM 2020: For connection to these fire panels, all de-
tectors receive the address 'CL00'.
It is not permissible to use different addressing modes at the same time.
Address
Mode
0 0 0
Loop/stub in LSN improved mode with automatic addressing
(T branches not possible)
001...254
Loop/stub/T branches in
LSN improved mode with manual addressing
CL 0 0
Loop/stub in Classic" LSN mode
Mode/
X
X
X
XX
X
X
XX
If LSN "improved version" elements are used in conjunction with the FPA−5000, unshiel-
ded cables can be used. Otherwise, shielded cables must be used.

8. Notes on maintenance and service

For maintenance and inspection work on security systems, the regulations of DIN VDE 0833
apply in Germany; these regulations refer to the maintenance intervals as per the manufac-
turer's instructions.
D Bosch ST recommends a functional and visual inspection at least once a year.
D Maintenance and inspection work should be carried out regularly and by trained personnel.

8.1. Repair

In the event of a defect, the entire unit is exchanged.

8.2. Disposal

Unusable units should be disposed of in accordance with regulations.