Corporation’s (“Eaton”) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser.
Page 3
A 2Mx bus, used to communicate with SAS application Sync A 2Mx bus used to communicate with the second 2Mx unit when PA/GA system is confi gured as A&B, AB+ or N+1 system SONIX HMI26 TECHNICAL MANUAL TM375 / A June 2022 www.eaton.com...
Should this product reach you in an unsatisfactory condition please This item is shipped with the following items. report this to Eaton to enable us to rectify and investigate the fault in a speedy manner. 1 x Hmi 26 access panel •...
3 About the product Routine speech • Zone control including All-Call and a default zone list • The Sonix Hmi-26 is a Human Interface access panel 12 configurable zoning buttons • for connection into the Sonix PA/GA system. It provides Emergency speech •...
Alarm Alarm Cancel Attenuate The Health indicator has no confi gurable options. MS12 / Fault Local Att LED Test Monitor MS12 / Fault Important Local Att LED Test SONIX HMI26 TECHNICAL MANUAL TM375 / A June 2022 www.eaton.com Monitor Message...
Solid Orange – Alarm cancel is active on the system • and been activated from this access panel Flashing Orange (~ 0.5 Hz) – Alarm cancel is active on • the system but was activated by a different source SONIX HMI26 TECHNICAL MANUAL TM375 / A June 2022 www.eaton.com...
Fault cal Att LED Test MS12 Fault Important cal Att LED Test Auto- Health Comms Initiate Message Auto- Busy Intercom Inhibit SONIX HMI26 TECHNICAL MANUAL TM375 / A June 2022 www.eaton.com Fault cal Att LED Test...
PTT button has been accidentally depressed or is no longer functioning correctly. The PTT timeout fault can be disabled in confi guration, see SAS Product Manual for details. SONIX HMI26 TECHNICAL MANUAL TM375 / A June 2022 www.eaton.com...
PTT broadcast on the PA/GA system. This approach Alarm PUSH TO TALK allows the user to hear any overriding broadcasts if they Cancel are not the one active on the system. SONIX HMI26 TECHNICAL MANUAL TM375 / A June 2022 www.eaton.com...
The setting allows the sending of the button press to the rest of the system. Disabling this feature doesn’t prevent the fault buzzer from being muted remotely or locally. Key settings: Global Fault Acknowledge Enable SONIX HMI26 TECHNICAL MANUAL TM375 / A June 2022 www.eaton.com...
ID is not important). It must also be connected to local where a fault has already been rectified but the system system ONLY. Eaton suggests that only the ‘A’ side is is showing a historical fault (Flashing Red health LED) as connected no matter whether to an A or B system, but it allows the clearing of the historical issue.
PTT Release delay • PTT Timeout • The other setup options should be the same for both • sides: Zoning • Alarms • Available buttons • Fault monitoring • SONIX HMI26 TECHNICAL MANUAL TM375 / A June 2022 www.eaton.com...
Zone button 5 Zone 1 Zone buttons 6-12 Disabled 1 + ∑ = 1 - 32 Table 14 - Zoning example 2 - Zone Button Configuration 11-30 Not available for selection SONIX HMI26 TECHNICAL MANUAL TM375 / A June 2022 www.eaton.com...
All zones without exception. In order to achieve this zone map, Multi Zone mode must be enabled allowing buttons 1 and 2 to be available to activate multiple zones. SONIX HMI26 TECHNICAL MANUAL TM375 / A June 2022 www.eaton.com...
• pitch). Do not use sharp objects, water, Notice: aggressive cleaning agents or solvent to clean Eaton firmware for target unit – Verify firmware is for • the unit. correct unit. Power source for Hmi-26 access panel, can be rack •...
Page 25
Printed in UK T: +44 (0) 1623 444 400 All specifications, dimensions, weights and tolerances are nominal (typical) Publication and Eaton reserve the right to vary all data without prior notice. www.crouse-hinds.com/hac No.TM375 / A MEDCSales@Eaton.com June 2022...