Introduction; Package Contents; Regulations; Compatibility - GE ARITECH FP400 Series Installation Manual

Conventional microprocessor controlled fire detection and alarm panels
Hide thumbs Also See for ARITECH FP400 Series:
Table of Contents

Advertisement

The range of FP400 fire alarm and detection panels has five models: FP402 of two
zones, FP404 of four zones, FP408 of eight zones, FP412 of twelve zones and FP416 of
sixteen zones.
The series has been designed to cover the needs of small to mid-sized installations such
as schools, homes, shops, small and medium-size businesses, etc.

1.1 Package contents

Check that the package contents are correct and in good condition before commencing
installation. If any defect exists repack the product and contact your distributor.

1.2 Regulations

This product has been designed according to EN54-2 and EN54-4 standards of 1997.
The EN54-2 standard includes some basic requirements and some optional ones. The
optional requirements this product meets are:
Indications
Controls
Outputs

1.3 Compatibility

This fire panel is compatible with all Aritech fire detectors and manual call points.
Compatibility with third party products cannot be guaranteed.
4
1 I
NTRODUCTION
1 x Fire panel.
4.7K Ohm end-of-line resistors (one per zone plus one for each sounder output).
1 x 5x20 mm 2A fuse.
1 x 5x20 mm 1A fuse.
2 x Keys.
1 x Installation manual.
1 x User Guide.
1 x Multilingual language inserts sheet.
1 x Bridge connection for the batteries.
This product must be installed by qualified personnel adhering to the EN-54
14 (UNE 23007-14) standard and any other applicable local authority laws.
Subject
Chapter
8.4
7.11
10
7.8
Description
Notification of loss of all external power
Output delays
Test status indication
Output for Fire alarm devices
FP400 Series Installation Manual