6 T
ECHNICAL SPECIFICATIONS
Mechanical
Box size FP402 & FP404 ....................................................................................................297 x 307 x 105 mm
Weight without batteries ............................................................................................................................ 3.6 Kg
Box size FP408, FP412 & FP416........................................................................................420 x 335 x 110 mm
Weight without batteries ............................................................................................................................ 6.2 Kg
Cable input holes ..................................................................................................... 4 x 20 mm at top of housing
Environmental
Working temperature .................................................................................................................... -5°C to +40°C.
Relative humidity .......................................................................................95% maximum without condensation
Protection index ............................................................................................................................................ IP30
Type class conditions ....................................................................................................3K5 of CEI 721-3-31978
Zone output
FP402 ...................................................................................................................................................... 2 zones
FP404 ...................................................................................................................................................... 4 zones
FP408 ...................................................................................................................................................... 8 zones
FP412 .................................................................................................................................................... 12 zones
FP416 .................................................................................................................................................... 16 zones
Maximum number of detectors per zone ..........................................................................................................20
Zone output voltage (nominal)................................................................................................................. 24 VDC
Zone output voltage (maximum).............................................................................................................. 28 VDC
Zone output voltage (minimum)............................................................................................................... 22 VDC
Maximum zone current .............................................................................................................................. 94 mA
Maximum length of zone line........................................................................................................................2 km
Maximum resistance of zone line ............................................................................................................44 Ohm
Maximum capacitance of zone line .......................................................................................................... 500 nF
Recommended cable...................................................................................... Stranded 2-wire cable of 1.5 mm²
Sounder output
Number of outputs in main board .......................................................................................................................2
Supervised...................................................................................................................For open and short circuit
End-of-line resistor................................................................................................................................ 4k7 1/4W
Maximum Output Current .............................................................................................................. 250 mA each
Maximum voltage (standby) ...................................................................................................... 5 VDC to 9 VDC
Maximum voltage (Activated) .............................................................. 18 VDC to 28 VDC (nominal of 24 VDC)
Recommended cable...................................................................................... Stranded 2-wire cable of 1.5 mm²
Alarm relay output
Potential free relays ............................................................................................1 relay (C/NO/NC contact type)
Maximum commutation power .........................................................................................................1 A, 30 VDC
Fault relay output
Potential free relays ............................................................................................1 relay (C/NO/NC contact type)
Maximum commutation power .........................................................................................................1 A, 30 VDC
Working conditions ........................................................................................... Normally energized (fail to safe)
FP400 Series Installation Manual