God, failure due to power surge, or cosmetic damage. Improper or incorrectly performed maintenance will void this limited warranty. OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
Polyester powder coating resists the corrosion process. Maintenance of the positioner is easy because of modularized inner structure. OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
Be careful not to apply volatile solvent (hardener of instant adhesive, acetone, WD-40, etc.) to the sticker nameplate. Printed contents may be erased. OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
This option is just the normal operating temperature of the product and is not related to explosion proof temperature. See “2.6 Certificates” for explosion proof temperature. OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
7. Pilot Block 3. Main PCB 8. Base body 4. Torque Motor 9. Feedback Lever 5. Main Shaft 10. Gauge Block OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
“mm” marked on the feedback lever. Improper setting may cause poor linearity OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
3. Connect connection bar to the actuator clamp. The hole gap on the feedback lever is 6.5mm so the connection bar’s outer diameter should be less than 6mm. OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
Page 16
Fig. 3-5: Proper way to insert connection bar between feedback lever and lever spring OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
Page 17
※ The effective linear feedback lever angle is 60 degree Stroke : 75mm Stroke : 45mm Fig. 3-7: Linear feedback lever and location of the connection bar OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
Page 18
Fig. 3-8: Feedback lever should not touch lever stopper on 0% ~ 100% valve stroke. 9. After the installation, tighten all of the bolts on the bracket and the connection bar. OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
Bolts and washers to attach bracket to actuator – not supplied with the positioner Fig. 3-9: Rotary Namur type OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
50mm H : 50 H : 50 H : 50 H : 50 Fig. 3-10: Rotary brackets and positioner OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
Fig. 3-13: Main shaft center alignment 5. Tighten the positioner and the bracket with bolts after checking the positioner’s position. OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
An external ground bolt is located next to the conduit entry. Please make sure that the resistance is less than 100 ohm. OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
The diameter of orifice hole is 1 mm. Fig. 6-1: Plate type Orifice installment OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
5. After PTM sub-PCB is installed newly, values of TR_ZERO and TR_END must be calibrated for correct output signals. For the calibration of TR_ZERO and TR_END, please refer to section 8.7.2 of this manual. OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
The four symbols located on the left are the symbols that display alarm messages classified in four groups in accordance with NAMUR NE107. OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
Use to select the current menu or function, or to store the ENTER value of a modified parameter. Used go directly to parent menu from current menu. OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
ESC button to return to parent menu after completing configuration. Pressing the ESC button anywhere in the menu structure several times returns the user to the uppermost menu, Run Mode Monitor menu. OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
# Normal condition LCD display. # When the condition changed or alarm occurred. # Explaining contents of alarm display OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
<DOWN> button if the above is not if the above is not displayed. displayed. <UP>/<DOWN> <ESC> 3 times OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
Push any button Press <UP> or <DOWN> button if the above is not displayed. OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
<DOWN> button if the above is not if the above is not displayed. displayed. <UP>/<DOWN> <ESC> 3 times OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
<DOWN> button if the above is not if the above is not displayed. displayed. <UP>/<DOWN> <ESC> 3 times OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
<DOWN> button if the above is not if the above is not displayed. displayed. <UP>/<DOWN> <ESC> 3 times OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
<DOWN> button if the above is not if the above is not displayed. displayed. <UP>/<DOWN> <ESC> 3 times OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
<DOWN> button if the above is not if the above is not displayed. displayed. <UP>/<DOWN> <ESC> 3 times OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
This function is activated by saving the Split Range Mode (SPLIT) of above Section 8.9.2 as “CSt”. OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
<DOWN> button if the above is not if the above is not displayed. displayed. <UP>/<DOWN> <ESC> 3 times OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
This function is activated by saving the Valve Flow Characterization Curves (CHAR) of above Section 8.9.5 as “U5”. OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
This function is activated by saving the Valve Flow Characterization Curves (CHAR) of above Section 8.9.5 as “U21”. OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
<DOWN> button if the above is not if the above is not displayed. displayed. <UP>/<DOWN> <ESC> 3 times OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
The following graph shows the operation of the valve stroke when the input signal corresponding to Tight Shut Open or Tight Shut Close is applied to the device. OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
<DOWN> button if the above is not if the above is not displayed. displayed. <UP>/<DOWN> <ESC> 3 times OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
<DOWN> button if the above is not if the above is not displayed. displayed. <UP>/<DOWN> <ESC> 3 times OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
<DOWN> button if the above is not if the above is not displayed. displayed. <UP>/<DOWN> <ESC> 3 times OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
<DOWN> button if the above is not if the above is not displayed. displayed. <UP>/<DOWN> <ESC> 3 times OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
“CLr”, the message has been cleared. NVMW at the bottom is an alarm message that has occurred. See "8.14 Status and Alarm Code" for alarm details. OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
Press <UP> or <DOWN> button <DOWN> button if the above is not if the above is not displayed. displayed. OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
“CLr” means that the event has been removed. The “TMPH” displayed on the bottom section indicates an abbreviation for the alarm. OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
It is active when auto-calibration has failed. Retry auto- CALF Failure calibration after checking if there is no problem with OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...
Page 63
It is active if the input current exceeds 20.5 mA. LPCL Loop Current Lo Limit It is active if the input current falls below 3.8 mA. OMC S.p.A: Via G. Galilei, 18 - 20060 - Cassina de Pecchi (MI) - ITALY - www.omcvalves.com - Tel.: (+39) 02.95.28.468...