Settings Sequence and Menus
Order
Indicator
Settings Item
Shown
Code
1
Rated Current
rc
2
CT Ratios
ctr
2)
Operating
3
chA
Time Characteristics
oc-t
4-1
Activation Delay
3)
Time Profile for
4-2
cLS
Inverse Time
3)
5
Startup Delay
oc-d
6
Lock Protection
Loc
7
Lock Activation Delay
Lc-t
4)
8
Stall Protection
StL
9
Stall Activation Delay
4)
St-t
10
Phase Failure
PF
Phase Failure
11
PF-t
Activation Delay
4)
12
Phase Unbalance
Ub
Phase Unbalance
13
Ub-t
Activation Delay
4)
14
Reverse Phase
rP
15
Undercurrent
Uc
Undercurrent
16
Uc-t
Activation Delay
17
Earth Leakage (ZCT)
EL
5)
Earth Leakage (ZCT)
18
EL-t
Activation Delay
5)
19
Ground Fault (NCT)
gF
Ground Fault (NCT)
20
gF-t
Activation Delay
Ground Fault Delay
21
gF-d
During Startup
22
Instantaneous
Sc
6)
Instantaneous Delay
23
Sc-d
During Startup
6)
24
Overcurrent Warning
AL
25
Electrical Reset
ErSt
26
Automatic Reset
ArSt
27
Motor Runtime Warning
rhS
28
Motor Runtime
rh
29
Total Runtime
t-rh
30
Comm. Address
4)
Addr
31
Comm. Speed
bPS
4)
32
Comm. Data SWAP
SAP
4)
33
Clock Setting - year
4)
2016
Clock Setting –
34
1228
month/day
4)
Clock Setting –
35
1038
hour/minute
4)
36
Main Terminal Settings
cont
Auxiliary Terminal
37
Au-c
Settings
38
Password Settings
PASS
1)
To enhance user convenience, time settings for certain features will not be displayed when certain protection features are deactivated.
2)
CT ratio setting (ctr) can be set to less than 2,000 A in conjunction with the rc setting.
3)
The menu indicates oc-t when overcurrent settings are set at definite time (dEF), and cLS when set to inverse time (thr, nthr)
Code
Displayed
Set the rated current for the protection characteristics.
Enter the CT ratio for external CT.
Select current Operating time characteristics between definite time/inverse time/
thermal inverse time - dEF (definite time), thr (thermal inverse time),
nthr(non-thermal inverse time).
Set the activation delay (operation time) for the overcurrent characteristics.
Select the overcurrent time class for inverse time.
Set the motor expected startup time (delay time)
Set the lock current value under operation to a percentage of rated current
(200 to 1,000 %). Only applicable under definite time (dEF).
Set the activation delay for the lock protection feature.
The oc-d takes priority before Lc-t is applied.
Set the stall current value under operation as a percentage of the rated current
(150 to 700 %). Only applicable under definite time (dEF).
Set the activation delay for the stall protection feature.
The oc-d takes priority before St-t is applied.
Activate the phase failure protection function.
Set the activation delay for the phase failure protection function.
Activate the phase unbalance protection feature, set current value.
Set the activation delay for the phase unbalance protection feature.
Activate reverse phase protection function.
Activate the undercurrent protection function, set current value to percentage of
rated current (30 to 90 %)
Set the activation delay for the undercurrent protection function.
Set the activation current value for the earth leakage (ZCT) protection function.
Set the activation delay for the earth leakage (ZCT) protection function.
Set the activation current value for the ground fault (NCT) protection function.
Set the activation delay for the ground fault (NCT) protection function.
Set the application of oc-d for the ground fault (NCT) protection function.
The oc-d takes priority before gF-t when set to ON;
Set the activation current value for the instantaneous protection function to
percentage of rated current (600 to 1,500 %).
Set the application of oc-d for instantaneous protection.
The oc-d is applied with set to ON, and not applied when set to OFF.
SET the activation current value for the overcurrent warning function to
percentage of rated current (60 to 110 %).
Activate electrical reset feature.
Set the activation parameters for the automatic reset feature between
0.5 seconds to 20 minutes.
Set motor runtime alert function. If motor runs under load for more than the set
duration, "orh" will be displayed on the screen.
Total cumulative runtime after relay is energized; reset to zero when
power is turned OFF and ON.
Total cumulative runtime after relay installation; cannot be reset.
Set Modbus communication address for the relay.
Set Modbus communication speed baudrate
-0.96: 9,600 bps, 1.92: 19,200 bps, 3.84: 38,400 bps
Activate Modbus communication data swap feature.
Set relay internal clock – year.
Clock resets when the relay is powered OFF/ON.
Set relay internal clock – month/day.
Clock resets when the relay is powered OFF/ON.
Set relay internal clock – hour/minute.
Clock resets when the relay is powered OFF/ON.
Select terminal output for main terminals (95-96, 97-98).
Set terminal output for auxiliary terminals (07-08).
- AL-c: overcurrent warning (Alert), gF-c: for ground fault, Sc-c: for instantaneous
Set security password 4 digits
Electronic Motor Protection Relays
Description
4)
This feature is only available on the advanced type.
5)
Feature not offered for the instantaneous model.
6)
Feature not offered for the ground fault model.
11
Initial
Settings Range
Unit
Value
0.5, 0.6, ... 60.0
60
A
0.25, 0.5, 1, 2, ... 200
1
dEF, thr, nthr
dEF
oFF, 0.2, 0.5, 1, 2,
60
sec
... 60
oFF, 1, 2, ... 60
60
0, 1, 2, ... 200
200
sec
oFF, 200, 300, ... 1,000
oFF
%
0.1, 0.2, ... 10.0
10
sec
oFF, 150, 200, 300,
oFF
%
... 700
0.5, 1, 2, ... 10.0
10
sec
oFF, on
oFF
0.5, 1, 2, ... 10.0
10
sec
oFF, 10, 20 ... 70
oFF
%
0.5, 1, 2, ... 10.0
10
sec
oFF, on
oFF
oFF, 30, 40, ... 90
oFF
%
0.5, 1, 2, ... 30.0
30
sec
oFF, 0.1, 0.2, ... 2.5
oFF
A
0.1, 0.2, ... 10.0
10
sec
oFF, 0.5, 0.6, ... 60
60
A
0.1, 0.2, ... 10.0
10
sec
oFF, on
on
oFF, 600, 700, ... 1,500
oFF
%
oFF, on
on
oFF, 60, 70, ... 110
oFF
%
oFF, on
on
oFF, 0.5, 1, 2, ... 1,200
oFF
sec
oFF, 1, 2, ... 9,999
oFF
hour
-
-
hour
-
-
hour
1, 2, ... 247
1
0.96, 1.92, 3.84
0.96
oFF, on
oFF
2016, 2017, ... 2099
2016
0101, 0102, ... 1231
0101
0000, 0001, ... 2359
0000
1a1b, 2a, 2b
1a1b
AL-c, gF-c, Sc-c
AL-c
0000 ... 9999
9999