Operating Instruction Manual(V1.0) ◼ Please read the instruction manual carefully and understand the contents so as to be able to correctly install, connect the circuit, operate and maintain, etc.. ◼ The technical specifications of this product may change without notice. ◼...
Thank you for using HRS Series intelligent AC motor soft starter produced by HNC ELECTRIC LIMITED. HRS Series soft starter is a intelligent AC motor soft starter with international leading technology newly developed by HNC ELECTRIC LIMITED. HRS Series soft starter uses power electronic technology, microprocessor technology and modern control theory technology, and has a new type of starting equipment with the international advanced level.
Excellent Performance ● Multi-start mode: The voltage ramp starting mode can obtain the max. output torque, the constant current soft starting mode can obtain the max. limited starting current, and the sudden jump starting mode can be applied to loads with large static friction during starting.
Typical Applications ●Water pump Using the soft stop function, the water hammer phenomenon of the pump is relieved when the pump is stopped, and the cost of system maintenance is saved. ●Ball Mill Using voltage ramp to start, reduce the wear of gear torque, reduce maintenance workload, save time and save money. ●Fan Reduce belt wear and mechanical shock, saving maintenance costs.
1. Overview This soft start controller takes an advanced microprocessor as the core, applies advanced software design methods and the latest hardware technology, uses thyristor phase shift technology, and realizes the soft start and soft stop functions of AC asynchronous motors, which has the multiple protection functions such as voltage, under-voltage, over-current, overload, three-phase unbalance, short circuit, etc.
1.3 Introduction of product typical applications ⚫ The products are widely used in thermal power generation, hydropower, transmission and distribution equipment, metallurgy, chemical industry, mining, construction and other industries. ⚫ Water pump---Using the soft stop function, the water hammer phenomenon of the pump is relieved when the pump is stopped, and the cost of system maintenance is saved.
1.6 Working principle The principle block diagram of this soft starter is shown as in Fig. 2. The power part is composed of three pairs of anti- parallel thyristors as shown in Figure 1. The core microprocessor of the control part collects the synchronization signal, voltage signal, current signal and motor power factor angle of the power grid.
2. Product Selection 2.1 Product nameplate 2.2 Model and definition 2.3 Precautions for selection The soft starter must provide a force greater than the load resistance moment to complete the start-up. For ordinary loads such as water pumps, fans, etc., it is recommended to configure soft starters with the same or higher gear specifications, and for heavy loads such as ball mills, grade 6 fans and crushers, it is recommended to configure soft starters with high or second gear specifications.
3. Installation 3.1 Outer dimension of soft starter ①Structure and dimension of product for HRS Series 5.5KW-55KW Outer dimension(mm) Installation dimension(mm) Gross Rated Rated weight Model power current (kg) (kw) HRS-5R5-B-G3 HRS-7R5-B-G3 HRS-011-B-G3 HRS-015-B-G3 HRS-018-B-G3 18.5 HRS-022-B-G3 HRS-030-B-G3 HRS-037-B-G3 HRS-045-B-G3...
②Structural dimension of product for HRS Series 75KW or more Rated Rated Gross power (kw) current Outer dimension(mm) Installation dimension(mm) weight(kg) Model HRS-075-B-G3 HRS-090-B-G3 HRS-115-B-G3 HRS-132-B-G3 HRS-160-B-G3 HRS-185-B-G3 HRS-200-B-G3 HRS-220-B-G3 HRS-250-B-G3 HRS-280-B-G3 HRS-320-B-G3 HRS-400-B-G3 HRS-450-B-G3 HRS-500-B-G3 1000 HRS-630-B-G3 1200 3.2 Requirements of installation Direction of installation ①The soft starter must be installed in the vertical direction, not upside down, it should be installed on a firm structure with...
4.1.2 Configuration diagram of terminals (1) Terminal diagram of main circuit 5.5kW-55Kw 75kW-630kW (2) Terminal diagram of control circuit (3)Terminal wiring of control circuit - 16 -...
5. Display for Keyboard Interface 5.1 Description for displaying the keyboard 5.2 Buttons Button name Description of functions 1. In the ready state, press [YES] to enter the help menu, and then press[YES] to exit. You can also press [Stop Reset] to exit. 2.
Button name Description of functions 1. In the setting menu, when the colon is not flashing, press [▲], [▼] button to change the function number; when the colon is flashing, press [▲], [▼] button to change the data, press [▲],[▼]button for and hold more than 1 second, the data will be increased or decreased in rapid succession.
Page 21
Factory Function code Name Setting range Description value Under-voltage Under voltage protection when it is lower than the 49-90% prote4ction set value, when it is set to 49%, turn off the function Over-voltage protection when higher than the set Over-voltage protection 100-131% 120% value, when set to 131%, turn off the function...
5.4 Functions selection and description 5.4.1 Code FE (programming output) The programmable relay output function has two working modes: ①Programmable timing output mode and programmable state output mode ②When the setting item FE is 0~4 (10~14), the programmable output work is the timing output mode, and the starting time of the output is set as follows: FE setting value 0(10)
Page 23
Fig 5.4.2 5.4.3 Code F2 (soft stop time) When the stopping time is set to 0, it is a free stop. Too long stopping time will bring instability to the system. (Fig.5.4.3 ) Fig. 5.4.3 5.4.4 Code F5 (Starting limit current) When using this function, code F9 must be set to 0 or 2 or 4, and the starting current of the starter will run below the set value (50%- -500%).
Page 24
the motor rated current|1 or below, and the starting process is completed. When the motor load is lighter or the set current limit value is large, it is normal that the maximum current at starting may not reach the set current limit value. Current limiting starting mode is generally used in occasions that have strict requirements on starting current.
Page 25
When the setting item F9 is 4, set the starting mode to this mode. Fig. 5.4.6c is the output current waveform of the current ramp start mode, where 11 is the current limit value set by F5, and T1 is the time value set by F1. The current ramp starting mode has a strong acceleration capability, which is suitable for two-pole motors and can also shorten the starting time within a certain range.
Page 26
The different protection levels and thermal protection time set by the setting item FA are as follows: Table 5.4.7 FA setting 0(primary) 1(light load) 2(standard) 3(heavy load) 4(Advance) Description Based on the None Level 2 Level 10 Level 20 Level 10 Running standard of overload...
5.5 Parameter modification 5.5.1 Modification of function parameter (1) Operating flow chart Power ON→ Power-on→Press the SET button→Press UP/DOWN button→Press the SET button→Press UP/DOWN button→Press “YES” button Enter code options →Select code function →Determine modified code →Modify the setting range→Save the modified data (Exit) 5.6 Help information and description Display...
Page 28
· Overheating protection of soft starter: When starting the soft start, if the temperature rises to 80° C± 5° C, the protection will act. When the temperature drops to 55° C (minimum), the overheating protection will be released. (The thermal protection temperature switch needs to be connected to the J4 terminal of the controller) By setting the parameter F3 (start interval delay) to define the min.
6. Faults Analysis 6.1 Overview · When there is a problem with the soft starter application, this chapter will be used as a guide. · When there is a problem with the soft starter application, the fault type will be displayed on the LCD. 6.2 Common problems and countermeasures Abnormal Content of inspection...
Please reduce the load Please set FO (starting voltage), F5 (starting current limit) F1 The load is too heavy (soft starting time) Starting time is too The code is set incorrectly Please check specification instruction and nameplate long Check whether motor specification is abnormal When the load is light, the starting time is often less than the set...
Page 31
Error03 Too low current limit makes the starting time too long (more than 60s) Soft starting time is too long The starting parameter setting is inappropriate or the load is too heavy, current capacity is insufficient, etc. Error04 Input phase loss Check input or main circuit fault, bypass contactor stuck in closed position and SCR open Error05 circuit...
7. MODBUS Communication Protocol 7.1 Overview about Modbus RTU communication protocol Modbus is a serial asynchronous communication protocol. Its physical interface is RS485. Modbus is designed for modiconPL C and has the structural characteristics of PLC. In Modbus network control, the soft starter can be compared to a PLC for reading and writing.
Page 33
7.2.2 Support code Soft start only supports the following codes. If other codes are used, the exception code 01 will be given. Code Function description Read register Write a single register Code 03 is only read by a single word (WORD) 7.2.3 Description of register ·...
Function parameter register 40XXX of soft starter 40256-40274 are function registers, the corresponding address is 0X0100-0X0112, the high byte address is 01, the low byte address is 0X00-0X12, and the corresponding function code F0-FL is consistent with the function code table 4.2. For example, address 0X109 corresponds to function code F9 (start mode).
Number of Number of Slave-station Starting address starting address Function code registers registers CRC Check address High byte Low byte High volume Low volume 0x01 0x04 0x01 0x80 0x00 0x07 04 function code register address is wrong, so the slave station responds: Slave-station address Function code Abnormal code...
8. Precautions of Use and Daily Maintenance for HRS 8.1 Precautions for application use ● Prevent electric shock After the input terminal of the HRS soft starter is connected to the power supply, when the load is open circuit or phase loss, even in the stopping state, the output terminal will still have a fairly high induced voltage.
8.2 Daily maintenance of soft starter ● Prevent electric shock and dust If there is too much dust, the insulation level of the soft starter will be reduced and the soft starter may not work properly. a. Creepage and arcing in the primary circuit will endanger the equipment; b.
Page 38
Schedule 2. Specification and parameter of peripheral accessories HRS Series Soft Starter( 5.5KW~ 55KW ) Supporting Rated Rated Supporting circuit bypass SCPD Specification of Model power current breaker contactor Remark specification primary cable (kw) model(QF) model (KM) HRS-5R5-B-G3 RS0-20 TGM1-63L /16 CJ20-16 2.5mm...
Page 39
KW~630KW HRS Series Soft Starter( 400 Supporting Rated Rated SCPD bypass Specification Supporting circuit Model power current specificati contactor of primary Remark breaker model(QF) (kw) model cable (KM) DZ20Y^1250/3300 50 x 6mm HRS-400-B-G3 CJ40-800 1000A copper wire For 400KW and above,...
Page 40
Warranty Agreement 1. If the product fails within 12 months from the date of purchase, but not more than 18 months after the date of manufacture recorded on the nameplate, the company provides free maintenance services if the product fails under normal storage and use.
Page 41
Thanks for choosing HNC product. Any technique support, PLS feel free to contact our support team Tel: 86(20) 84898493 Fax: 86(20)61082610 URL: www.hncelectric.com - 41 -...