Read this document carefully before using this device. The guarantee will be expired by damaging of the
device if you don't attend to the directions in the user manual. Also we don't accept any compensations for
personal injury, material damage or capital disadvantages.
ENDA EPDA1 / EPAA1 Panel Mountable Solid State Relays
Thank you for choosing
* 12-25-40-50-70-100-120A AC load current.
* 280-480 AC load voltage.
* 8-30V AC/DC or 90-240V AC input voltage.
* LED status indicator for input voltage.
* Zero-cross switching.
* Applicable for three phase loads.
* Built-in varistor protection.
* Panel mountable.
* CE marked according to European Norms .
ORDER CODE
Product Basic Code
Panel type SSR
EP
Input voltage
8-30V AC/DC
D
90-240V AC
A
Load voltage
AC
A
Pole number
Single-pole
1
ENVIRONMENT AL CONDITIONS
Ambient-storage temperature
Relative humidity
Pollution degree
Overvoltage category
Altitude
Protection
Do not use the device in locations subject to corrosive and flammable gases.
OUTPUT
Order Code
Load curent, AC51/25ºC (Arms)
Load voltage (Vrms)
Overload current t=1s/25°C (Arms)
Non rep.surge current/25°C (Arms)
On-state voltage drop (Vrms)
Leakage current (mArms)
I²t For fusing t=10ms (A²s)
Frequency (Hz)
Minimum operating current (mArms)
THERMAL
SPECIFICA TIONS
T
Junction temperature (°C)
j
Rth
(j-c)Junction-case thermal resistance (°C/W)
Rth
(j-a)Junction-ambient thermal resistance (°C/W)
INPUT
Order code
Input voltage
Pick-up voltage
Drop-out voltage
Input current
Turn-on time
Turn-off time
LED indicator
GENERAL
Order code
Weight
Isolation voltage
Connection
Terminal screw torque
Product standard
Mounting
Enclosure material
While cleaning the device, solvents (thinner , benzine, acid etc.) or corrosive materials must not be used .
ENDA EPDA1 / EPAA1
EP D A 1 - 2 25 Z
Switching
Zero crossing
Load current
12A AC
25A AC
40A AC
50A AC
70A AC
100A AC
120A AC
Load voltage
24-280V AC
50-480V AC
-25... +60 C / -30... +100 C (In the environment icing and condensation should not be.)
°
At +4 °
0 C
%50, temperature was reduced at +2 °
2
II
Max. 1000m
IP20 According to EN60529
EPxA1-212Z
EPxA1-225Z
12
25
24 - 280
50
85
120
250
1,6
5
78
340
50 - 60
160
1,2
0,7
20
< 17mAac/10mAdc
Ma imum ½ Period
Maximum ½ Period
If the input voltage >6V ac/dc, LED lights up.
EPxA1-xxxZ
W45xH62xD31mm
For EPxA1-2xx/4xxZ 95g , For EPxA1-550/570Z 110g , For EPxA1-5100/5120Z 115g (After packaging)
2500Vrms between I/O terminals for 1 min.
For power line 16mm² (with cable terminal 25mm² ) cable, for signal line 4mm² cable can be connected.
For power line max. 2,2Nm, for signal line max. 1,2Nm.
EN 60947-4-3
With M4 screws is mounted to the panel .
Self extinguishing plastics ( . (
series Solid State Relays
Z
12
25
40
50
70
100
120
2
4
°
0C could be
EPxA1-240Z
EPxA1-425Z
EPxA1-440Z EPxA1-450Z
40
25
150
70
400
190
1,8
8
880
265
50 - 60
200
1,2
1,0
20
20
20
EPDA1-xxxZ
8 - 30Vac/dc
> 6Vac/dc
< 2Vac/dc
x
EN 60695-11-10 V-O)
According to
1. / 2
90 .
(Condensation should not be.)
%
EPxA1-470Z EPxA1-4100Z EPxA1-4120Z
70
40
50
50 - 480
110
360
150
290
380
900
1,8
10
15
610
4000
720
50 - 60
300
400
0,6
0,4
20
20
EPAA1-xxxZ
90 - 240Vac
> 75Vac
< 6Vac
< 8mAac
Ma imum 1 Period
x
Maximum 2 Period
If the input voltage >75V ac, LED lights up.
english
100
120
540
720
1350
1800
20
20
9100
16200
500
500
0,3
0,25
20
20
EPDA1-E-10052019
Need help?
Do you have a question about the EPDA1 and is the answer not in the manual?
Questions and answers