15073 OWNER'S MANUAL
You can select which input controls which output, and which inputs are Style Z (Class A) and Style Y
(Class B) using the 10 position DIP switch on the printed circuit board. Refer to Section 5 for DIP switch
settings.
Auxiliary Power Output
The 15073 has a dedicated, power-limited, auxiliary output that can be configured in two different ways.
The auxiliary output can either be non-resettable (always on), or configured to switch off when the AC
power goes off to conserve the battery standby power. When the auxiliary power is configured to switch
off, there is a 30-second delay before the auxiliary power is turned off after the AC power goes off.
The Auxiliary Power Output is rated at 3 amps. Only a total of 6 amps maximum can be drawn from the
15073 outputs. The yellow Aux PS LED (DS5) will indicate an over-current condition on the output.
Trouble Relay
The 15073 includes a form C trouble relay that will de-energize for the following trouble conditions:
No or Low AC power.
No and Low battery condition.
Ground fault to the output wiring.
Auxiliary Power Supply output over-current condition.
NAC output open, shorted and over-current condition.
Battery Charging and Supervision
The 15073 provides a battery charging circuit for charging sealed lead-acid batteries. The unit also
supervises for no and low battery conditions.
Ground Fault Detection
The 15073 monitors for ground faults to the output wiring. When detected, the unit lights the yellow
GRND LED (DS6) and de-energizes the trouble relay and the input supervision relays.
Environmental
All hardware is suitable for use in an interior or protected location.
Power Limiting
The AC power and battery wiring are not power limited. All other circuits leaving the control unit are
power limited, provided the proper installation rules are maintained.
Transient Protection
Transient protection devices are provided where needed to meet the requirements of UL864.

1.2 REGULATORY STANDARDS

The 15073 meets the requirements of industry and government regulatory agencies as noted.
Federal Communications Commission
The 15073 meets the class A requirements of the Code of Federal Regulations (CFR 47), Part 15,
subpart J, for electromagnetic field emissions.
Underwriters Laboratories
The 15073 control unit is listed under UL Standard 864 for compliance to NFPA Standard 72 for fire
service.