1. Safety Instructions
To ensure sufficient convection cooling, always maintain a safety
distance of >20mm from all ventilated surfaces while the device is
in operation.
The device is not recommended to be placed on low thermal
conductive surface, for example, plastics.
Note that the enclosure of the device can become very hot
depending on the ambient temperature and load of the power
supply.
Do not touch the device while it is in operation or immediately after
power is turned OFF. Risk of burning!
Do not touch the terminals while power is being supplied. Risk of
electric shock.
Prevent any foreign metal, particles or conductors to enter the
device through the openings during installation. It can cause:
- Electric shock; Safety Hazard; Fire; Product failure
Warning: When connecting the device, secure Earth connection
before connecting L and N. When disconnecting the device, remove
L and N connections before removing the Earth connection.
2. Device Descriptions
Refer to Fig. 1:
1
Input & Output terminal block connector
2
DC voltage adjustment potentiometer
3
DC OK control LED (green)
Ventilated surface
Base surface
Fig. 1 Device Descriptions
3.
Side surface
4.
Top
3
2
1
Installation of the Device
Refer to Fig. 2:
A Mounting holes for power supply assembly onto the mounting surface. Power
supply shall be mounted on minimum 2 mounting holes using M3 screw,
minimum 5mm length.
B
This surface belongs to customer's end system or panel where the power
supply is mounted.
C Connector
Side Mounting (Vertical)
Base Mounting (Vertical)
Fig. 2 Mounting Orientation
Use flexible cable (stranded or solid), AWG no. 22-12. The torque at the
Connector shall not exceed 13Kgf.cm The insulation stripping length should
not exceed 0.275" or 7mm
Lug
Fig. 3 Wire Type
Installation of Mounting Accessories
Only use M3 screw < 6mm through the base mounting holes. This is to keep
a safety distance between the screw and internal components.
Refer to Fig. 4:
Recommended mounting tightening torque: 4 ~ 8Kgf.cm
Fig. 4 Mounting Screw
PMC-24V100W1AA
Side Mounting (Horizontal)
Stripped wire
www.delta.com.tw/industrialautomation

Advertisement

loading

Summary of Contents for Delta PMC-24V100W1AA

  • Page 1 Instruction Manual PMC-24V100W1AA 1. Safety Instructions Installation of the Device • Refer to Fig. 2: To ensure sufficient convection cooling, always maintain a safety distance of >20mm from all ventilated surfaces while the device is A Mounting holes for power supply assembly onto the mounting surface. Power in operation.
  • Page 2 PMC-24V100W1AA 依據圖二: • 與通風表面保持至少 20mm 的安全距離,以確保對流冷卻充分。 • 本產品不適合擺放在低熱導體,例如:塑膠。 在把產品安裝在固定表面時,將螺絲鎖入此固定孔. 產品應該用長度至少 5mm 的 M3 • 受環境溫度及產品負載的影響,本機外殼溫度會很高,因此在上電時或切 螺絲鎖入至少兩個固定孔。 斷電源後短時間內不要觸摸本機,以免燙傷。 此固定表面為客戶系統表面。 • 請勿在上電時觸摸連接端子,以防電擊危險。 • 安裝過程中,應避免金屬元件或金屬導體通過空隙或通風孔進入到產品 輸入/輸出連接端子 內,否則會引起下列狀況。 -電擊 ; 安全危害 ; 火災 ; 產品異常 • 警告:在連接產品電源供應時,產品必須先接地然後才接 L 和 N。當要解 開電源供應時,必須先把 L 和 N 解開然後才把接地解開。...