Modbus Communication; Modules Wiring Diagram While Using Modbus Protocol (Fig. 6) - LG multi V ARUM Series Installation Manual

A set for the application of an outdoor compressor condensation unit for a nonoriginal evaporation / hvac unit
Table of Contents

Advertisement

5.4 CONTROL / COMMUNICATION MODBUS
In order to control up to 23 modules from the
superior
system
you
communication as an option to control or monitor the
equipment.
Input/output "MODBUS" (terminals 23+24)
The address for MODBUS communication is set using
the "SETTINGS" button. The setting procedure to be
found in paragraph 6.
PARAMETRY KOMUNIKACE MODBUS
Serial line: 9.6 kbps, 8 bits, no parity, 1 stop bit
Station address: hex91 - hexA7 (default hex91)
Supported functions:
Fig.6 - MODBUS communication wiring diagram
for controlling multiple modules
READING REGISTRIES
Address
Name
(decadically)
VERSION
4096
ERROR
4097
TEMP1
4098
TEMP2
4099
DEFROST
4100
RECORDING REGISTRIES
Address
Name
(decadically)
POWER
4101
FUNCTION
4102
2020/07/23
may
use
the
MODBUS
- 3 (Multi_Read)
- 6 (Single_Write)
- 16 (Multi_Write)
Properties/description
Software version
Errors according to the device's self-diagnostics (see the service manual of the
LG device), (error 99 + Modbus communication error)
Refrigerant input temperature to the exchanger +15 °C (blue sensor, smaller
diameter)
Refrigerant output temperature to the exchanger +15 °C (red sensor, bigger
diameter)
1 = active defrost mode of the outdoor unit
Properties/description
The value of the required power 0 to 7 corresponds with analogue input
Bit 0
0 = cooling; 1 = heating (heat pump)
Power value 0,1,2,3 (this value is used to control the power only if the
Bit 1+2
value in the registry POWER is = 0)
Bit 3
0 = OFF; 1 = ON
Bit 6
1 = RESET
I&C
page 13