Power Requirements …………………………………..…………….……...….……… Extension Cord Requirements ………………………..…………….……...…………. Flex-Duct Length ………………………………………...…………………….……...…. Determining Maximum Allowable Leakage ….………..……………...…….….……… FREE Oriflow duct test summary form (SMACNA or DW/143) ………….….………. Determining Which Orifice Plate to Use ……………..……………..……..…………. 6 - 7 Duct Leakage Test Setup and Procedure Install Orifice Plate and Upper Tube Section ……………………………..………..….
Introduction The COBRA duct leakage tester is the most widely used tester in the U.S. It is the simplest to use tester on the market backed by unparalleled customer service and technical support. Call us, find out. The recommended recalibration interval for the plates is 5 years. Note the authority having jurisdiction may override this requirement, and if so, Oriflow has reasonable rates for re- calibrating orifice plates manufactured by Oriflow.
If the specification uses SMACNA Leakage Class or Pressure Classification, you will need to calculate the total duct system surface area. Oriflow has a FREE Adobe test summary sheet that will calculate duct surface area, leakage factor, allowable leakage, actual leakage and Pass/Fail criteria. You can find this test summary sheet using the QR code to the right.
Page 18
(for this example, the constant is "134.42"). The exact leakage is 134.42 x (square root of 2.46) = 210.8 cfm. Better yet, download Oriflow’s test summary sheet described on the bottom of page 5 of this manual.
Open duct end that was supposed to be sealed/capped-off for the leak test. A non-toxic smoke machine is an excellent tool for locating significant sources of leakage. Call ORIFLOW at 727-400-4881 or to our website at www.oriflow.com for more information.
Use the next larger sized orifice. GFI/GFCI trips This happens when using a Cobra duct leakage tester with the variable speed option. The supply wiring has ground wired to neutral which causes the GFI to activate when the tester is operating.
UFL/OFL displays when TESTER is ON (airflow through orifice tube) Are you using another blower in series with the tester? The digital gauges used on the Cobra tester can read up to about 11 in.wg. maximum. Cobra Tester User Manual...