ABB SPAD 330 C Manual page 36

Differential relay

Advertisement

Recorded
The leftmost digit of the display shows the
information
address of the register and the other three
digits the recorded data.
The registers 1. . . 4 are set to zero by pressing
the push-buttons STEP and RESET simul-
taneously. The registers are also cleared by an
interruption of the auxiliary power supply of the
relay unit. The address codes of the relay
modules, the data transfer rate and the
password are maintained over an auxiliary
voltage interruption.
8
B
Register/
Recorded data
STEP
1
Differential current at the moment of tripping, as a multiple of the relay rated
current.
2
Stabilizing current i.e. the mean value of the load currents of the HV and the LV
side of the protected object at the moment of tripping, as a multiple of the relay
rated current.
3
Maximum value of the stabilizing current after the latest resetting, as a multiple
of the relay rated current.
4
Maximum value of the second harmonic after the latest resetting, as a multiple
of the relay rated current.
5
Calibration register of the filter. Reserved for use by the manufacturer.
0
Display of the blocking mode (0/1). The rightmost figure of the register indicates
the blocking state. A figure 1 in the register means that the module is blocked.
The module is either internally blocked or blocked by the other relay modules of
the differential relay.
From this register it is possible to move on to the so called test mode, where the
blocking and tripping signals can be activated one by one. For further details
see description "General characteristics of C-type relay modules".
A
Address code of the differential relay module. The address code, which is
required by the serial communication system, is set to zero, unless the serial
communication system is used. A subroutine of this register is the selection of
the data transfer rate, and the setting of the password for the remote setting.
-
Display dark. By pressing the STEP push-button the display menu is re-entered
from the beginning.
The harmonics restraint threshold I
the high-set stage starting value I
transfer rate, the serial communication address
of the module and the password of the remote
settings are set in the so called setting mode,
see description "General characteristics of C-
type relay modules".
> value and
hr
>>, the data
d