1. Description 2. DISPLAY LAYOUT 3. MODES 3.1 Power On 3.2 Standby 3.3 Run Mode 3.3.1 Single Booster with high and low pressure 3.4 Power Off 3.5 Error Mode 4. CONTENT OF MAIN- AND SUBMENUS 5. OVERVIEW OF MAIN- AND SUB-MENUS 5.1 Content of the Info menu 5.2 Content of the Errors menu –...
1. Description This software manual describes the operation of the control panel of the advanced Single Booster unit (SB and SBHL). The advanced SB unit is operated via the control panel (see below illustration). 1. OFF Button (1) switches OFF the unit. 2.
2. Display layout Example: Standard Standard pressure: 25 bar pressure: 25 bar When switched on the display will show an arrow symbol in the top right corner equivalent to the active navigation buttons on the control board. The arrows illustrate that it is possible to scroll up and down between the menus. Scrolling to the right makes it possible to enter a value.
Set date & time 2006-01-01 12:00 Confirm by pressing OK button. 3.2 Standby The start up display will look as the one below. ECOLAB Pegasus 12:00:00 Display for SB model with High- and Low pressure - Select either HP or LP using arrows up & down. 110007941...
3.3 Run Mode 3.3.1 Single Booster with high and low pressure The following screen displays will appear when the unit is in Run Mode. Screen display for High pressure unit in Run Mode. Scroll down to return to STANDARD pressure. HIGH (25 bar) P=0 BAR T=0 °C...
3.4 Power Off When the unit is off the display will only show a small dot in the top right corner. In Off mode it is possible to access all menus without the pump running by pressing the OK button on the panel. Dot is equivalent to the OK confirm button on the panel. 3.5 Error/Warning ERROR WARNING In case of an error, “ ERROR” will appear on the display screen. Press the OFF button to switch of unit. If the error remains when the unit is switched ON again, please Press right arrow to see current error. In case of a warning, “WARNING” will appear on the display screen. When a warning is detected the machine will either stop or run with limited performance until the cause of the warning has been improved (eg.
4. Content of Main- and Submenus The control panel contains the below main menu screen displays. Scroll between the menus using the navigation buttons. Each main menu contains submenus which will be described subsequently. Info Errors Setup Readings 110007941 Software Manual...
5.1 Content of the Info menu Please note that the Info menu is only for display – all data must be typed in via the setup menu! Σ TOTAL Σ ΣCounters Info Power 0kWh Σ Hours total Displays accumulated consumption of power and operation hours.
5.2 Content of the Errors menu – CAUSE & REMEDY Example of Error log screen display: All error occurrences will be stamped with date and time. E indicates Error number. P indicates Pump number. E0\P1 E0\P1 2006-01-01 12:00 2006-01-01 12:00 C1 Inverter C1 Inverter Error...
Page 13
1. Booster start condition changed to flow, due to C14 Warning 1. Check for leakage in pipe system. 2. Press “off” button leakage start leakage in pipe 3. If error reoccurs, contact your local service technician. 1. Pressure signal from pumptop sensor, out of range 1. Press “off” button C20 Low Sensor 2. If error reoccurs, contact your local Signal P-Pump- service technician. 1. Temparature signal from pumptop, sensor, out of 1. Press “off” button C21 Low Sensor 2. If error reoccurs, contact your local Signal T-Pump- range service technician. 1. Pressure signal form inlet sensor, out of range 1. Press “off” button C22 Low Sensor...
5.3 Content of the Setup sub menu Settings The Setup Main menu contains the below submenus, which will be described subsequently. Password Settings Setup 0000 Languages & units Supply tank Communication I/O Settings Installation Reset 110007941 Software Manual...
5.4 Content of Setup menu Password Post run Settings Post run 0000 Time: 20 sec. Time: 20 sec. Password Note: Default user password is Set Post run time. 6802. Enter the settings menu to change the default password. To avoid unintended access to the system the your local service technician.
Page 16
Set auto off Autooff Delay:OFF Delay: OFF Accelleration Set Acc. Ramp: 3 sec Ramp: 3 sec Date & time Set date & time 2006-01-01 12:00 2006-01-01 12:00 Set date and time SERVICE SERVICE Enter TEXT HERE Enter TEXT HERE Enter name and tel. no of Your local service technician. Inverter Inverter power: 11000W...
5.4.1 Submenu Language & Units Language: Languages & Language: units English English Units: Units: Metric Imperial 5.4.2 Submenu Supply tank Supply Tank Tank tank Control: OFF Control: OFF LLA Detect LLA Detect Delay: 3 sec Delay: 3 sec 5.4.3 Submenu Communication * Upgrade Ready Communication Firmware upgrade...
5.4.5 Submenu Installation Installation * For the use of authorised Your local service technician only. 5.4.6 Submenu Reset Reset Reset Reset? trip counters? 5.5 Content of Readings Readings Pump state 82Hz Outlet pres . 24 bar Water temp. 29 °C Supply pressure 2.5 bar Flow status...
6. Upgrade Firmware Upgrading from software 5.02 or higher. 6.1 Upgrade display using USB Cable Connect USB cable (Item No. 110007947) to PC USB port (Remove other USB cables connected to PC) Connect Display cable to USB cable In the menu go to, Setup->”password”->Communication-> Firmware upgrade by cable- >Confirm Firmware upgrade and press “OK” Display should now be looking like this: Upgrade Ready Power Cycle and...
Page 21
Press UPGRADE button in FWU 200 tool 14. After a short while the FWU tool should start upgrading, the upgrade button should turn Yellow and change to “RUNNING” 15. The progress bar “Program” must go to the end before the upgrade is complete (less than 1 minute) 16. When the upgrade is complete the FWU tool should be looking like this, Button turns Green and text changes to “DONE/NEW” Now the display is upgraded 18. To verify software version in display, in the menu go to, Info->Machine info 19. Here you will find display software version and control software version. SW ID “Display software”, HW ID “type of device”, CT ID Controller board software(if display is not connected to a control board, control software will be 0/300) 110007941 Software Manual...
6.2 Upgrade display using IrDA Cable Connect power to equipment In the menu go to, Setup->”password”->Communication-> Firmware upgrade by Infrared- >Confirm Firmware upgrade and press “OK” Display should now be looking like this: Upgrade Ready Power Cycle and Start PC App. Turn Off equipment and turn it on again (Power cycle) Make sure the All three led’s are on (Green “ON”, red “ERROR” and red “OFF”) and the display is blank Connect Irda module (Item No. 110001558) to PC USB port Place Irda module on display module like this Startup PC program FWU200.exe (can be downloaded from Nilfisk Food website) Window should be looking like this...
Page 23
Press UPGRADE button in FWU 200 tool 15. After a short while the FWU tool should start upgrading, the upgrade button should turn Yellow and change to “RUNNING” 16. The progress bar “Program” must go to the end before the upgrade is complete (less than 1 minute) 17. When the upgrade is complete the FWU tool should be looking like this, Button turns Green and text changes to “DONE/NEW” Now the display is upgraded 19. To verify software version in display, in the menu go to, Info->Machine info 20. Here you will find display software version and control software version. SW ID “Display software”, HW ID “type of device”, CT ID Controller board software(if display is not connected to a control board, control software will be 0/300) 110007941 Software Manual...
6.3 Upgrade Inverter Power off unit using service switch (wait for unit to discharge approximately 5 min.) Open Inverter box Disconnect the Display cable connected to either of the two modbus terminals Connect the usb cable (110007946) to either one of the modbus connectors Connect usb cable to PC Power on inverter by using service switch (AWARE OF HIGH VOLTAGE IN INVERTER!) Start up Firmware upgrade program (Can be downloaded from Nilfisk FOOD web) Click browse to select upgrade file *.hex (Can be downloaded from Nilfisk FOOD web) Click in Serial port up/down to select the com port for USB cable, if comport is not showing...
Page 25
13. Power off unit using service switch (wait for unit to discharge approximately 5 min.) Disconnect the usb cable from inverter Connect the display to modbus connector again Mount the lit of the inverterbox Turn unit back on. 110007941 Software Manual...