System Parameter Setting - Passion R06SPA User And Service Manual

Table of Contents

Advertisement

11) System parameter setting

 Press "
parameters. Then press"
change the digit of the password. After finishing the last digit, press "
confirm the password.
6. System Parameters:
Parameter
Parameter Name
Code
1
Return Difference for
Target Water Temp.
2
Set Temp. in Cooling Mode
3
Set Temp. in Heating Mode
4
Compensation Value of Inlet Water Temp.
5
Defrosting Cycle
6
Defrosting Start Temp.
7
Defrosting Time
8
Temp.to Quit Defrosting
9
Difference between
Ambient Temp. and Coil Temp.
to Start Defrosting
10
Ambient Temp.to Start
Defrosting
11
Electronic Expansion Valve's
Working Cycle
12
Overheat Degree in Smart/
Powerful Mode
d(13)
Exhaust Gas Temp. of
Electronic Expansion Valve
14
Electronic Expansion Valve's
Steps during Defrosting
( Set Value*10=Actual Steps)
15
Electronic Expansion Valve's
Min. Steps(Set Value*10=Actual Steps)
16
Electronic Expansion Valve's
Working Mode
17
Manual Steps of
Electronic Expansion Valve
(Set Value*10=Actual Steps)
"+"
"for 5 seconds to enter the password interface for setting the
" or "
" to enter the password. Press "
Set Range
1~18℃(2~36℉)
8℃~35℃(46~95℉)
5℃~40℃(41~104℉)
-5℃~15℃(-9~30℉)
20MIN~90MIN
-9℃~-1℃(16~30℉)
5MIN~20MIN
1℃~40℃(33~104℉)
0℃~15℃(0~30℉)
0℃~20℃(32~68℉)
20S~90S
-5℃~10℃(-9~20℉)
70℃~125℃(158~257℉)
2~45
5~15
0 Manual/1 Auto
2~45
- 13 -
" to
" to
Factory Setting
1℃(2℉)
27℃(81℉)
40℃(104℉)
0℃(0℉)
45MIN
-3℃(27℉)
8MIN
20℃(68℉)
5℃(10℉)
17℃(63℉)
30S
Depends on
Actual Model
95℃(203℉)
Depends on
Actual Model
10
1
35

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Passion R06SPA

Table of Contents