Table of content Table of content Declaration of performance Product presentation KAMOUFLAGE P Range and dimensions KAMOUFLAGE 1V P Evolution - kits Options - at the time of order Storage and handling Installation Operation: manual opening Operation: manual closing Electrical connection...
Product presentation KAMOUFLAGE P Product presentation KAMOUFLAGE P Aesthetic smoke evacuation shutter suitable for ceiling mounting into the bottom of smoke shafts. Smoke evacuation shutters and dampers are suitable for use in ventilating protected lobbies, venting to shafts either naturally or mechanically.
Evolution - kits Evolution - kits Natural magnet 24 V DC KITS VD24-VA Natural magnet 48 V DC KITS VD48-VA Electromagnet 24 V DC (not applicable for ME model) KITS VM24-VA Electromagnet 48 V DC (not applicable for ME model) KITS VM48-VA End and begin of range switch KITS FDC-VA...
∎ Rf-t smoke dampers may be applied to ducts that have been tested according to EN 1366-8 and EN 1366-9 as appropriate, con- structed from similar materials with a fire resistance, thickness and density equal or superior to these of the tested materials.
Installation 1. Resetting 1V 2. Insert the key in the lock. Turn the key 35° clockwise, the key Remove the finishing cap from the shutter. To do this, use the gets blocked in the lock. hook with key ring that is delivered with the product. You may attach this tool to the key through its handy key ring.
S 61-932. Position in the shaft ≥105 ≥105 Kamouflage P KAP Kamouflage P KAP 1. The shutter is affixed to the smoke evacuation shaft through a sleeve. That sleeve can be indifferently installed: in the shaft, in the axis of the shaft or outside the shaft (or shaft extension).
Kamouflage 60 P Shaft Promatect L500 ≥ 30mm EI 60 (h i n o) S 1500 AA multi 350x385 mm ≤ Kamouflage P 1V ≤ 700x775 mm; 550x1075 mm Kamouflage 120 P Shaft Promatect L500 ≥ 50mm EI 120 (h i n o) S 1500 AA multi 1.
Page 10
S 1500 AA multi Kamouflage 120 P Shaft Geoflam ≥ 45mm EI 120 (h i n o) S 1500 AA multi 350x385 mm ≤ Kamouflage P Kamouflage 60 P 1V ≤ 700x775 mm; 550x1075 Shaft Geotec ≥ 30mm EI 60 (h...
Classification Kamouflage 60 P Shaft Tecniver ≥ 35mm EI 60 (h i n o) S 1500 AA multi 350x385 mm ≤ Kamouflage P 1V ≤ 700x775 mm; 550x1075 mm Kamouflage 120 P Shaft Tecniver ≥ 50mm EI 120 (h i n o) S 1500 AA multi 1.
Kamouflage 60 P Shaft Glasroc F V500 ≥ 35mm EI 60 (h i n o) S 1500 AA multi 350x385 mm ≤ Kamouflage P 1V ≤ 700x775 mm; 550x1075 mm Kamouflage 120 P Shaft Glasroc F V500 ≥ 50mm EI 120 (h i n o) S 1500 AA multi 1.
The product was tested and approved in: Product Range Wall type Classification Kamouflage 120 P 350x385 mm ≤ Kamouflage P Shaft Desenfire HD ≥ 35mm EI 120 (h i n o) S 1500 AA multi 1V ≤ 700x775 mm; 550x1075...
Installation Finishing 1. The upper face of the shutter consists of a sheet of plaster- board, which you can decorate to match the wall in which the shutter is installed (paint or wallpaper). Covering plate of plasterboard: fill the holes of the screws with a suitable filler.
Operation and mechanisms Operation and mechanisms Operation: general points ∎ See under 'Installation'. View also the video on our website: www.rft.be (product: Kamouflage, menu: Installation). Caution : please note dampers must be fully open before starting supply and/or extract fans. ...
Weights Weights KAMOUFLAGE 1V P Hn\Wn [mm] 385 kg 10,77 11,03 11,29 11,95 12,60 13,49 14,37 415 kg 11,47 12,09 12,70 13,31 13,93 14,54 15,15 445 kg 10,90 11,67 12,44 13,20 13,97 14,74 19,03 19,80 475 kg 11,22 12,02 12,81 13,61 14,40 15,19...
Page 17
Selection graphs ATOUT RAL9010 Hn\Wn [mm] 385 kg 415 kg 445 kg 475 kg 505 kg 535 kg 565 kg 595 kg 625 kg 655 kg 685 kg 715 kg 745 kg 775 kg 805 kg 835 kg 865 kg 895 kg 925 kg 955 kg...
Selection data Selection graphs Kamou age 1V v [m/s] H n [mm] 8 9 10 11 12 1075 1045 1015 4 5 6 7 60 80 100 450 500 550 600650 700 p[Pa] W n [mm] KAMOUFLAGE 1V P ∆p = 0,6 x v² x ζ Hn\Wn [mm] 385 ζ...
0,4830 0,5340 0,5850 1075 Sn [m²] 0,3400 0,3920 0,4450 0,4970 0,5500 Sample order KAMOUFLAGE P VD24 FDCB ATOUT RAL 9010 product 1 shutter (1V) fire resistance of 60 or 120 minutes width height option: type magnet and voltage option: bipolar end of range switch (FDCU included)
Approvals and certificates Approvals and certificates All our products are submitted to a number of tests by official test institutes. Reports of these tests form the basis for the approvals of the products. 1812_CPR_1043 05.23 Clapets coupe-feu et Volets de désenfumage D.A.S. Organisme Certificateur AFNOR Certification - www.marque-nf.com The NF-label guarantees: conformity with the standard NF S 61-937 Parts 1 and 10: “Systèmes de Sécurité...
Need help?
Do you have a question about the KAMOUFLAGE P and is the answer not in the manual?
Questions and answers