INSTALLATION AND MAINTENANCE INSTRUCTIONS
WFDTN Vane-type Waterflow Detectors
SPECIFICATIONS
Contact Ratings:
Triggering Threshold Bandwidth (Flow Rate):
Static Pressure Rating:
Dimensions, Installed:
Operating Temperature Range:
Enclosure Rating:
The WFDTN can be installed between 2×4 stud wall construction.
U.S. Patent Number:
IMPORTANT
Please Read Carefully And Save
This instruction manual contains important information about the installation and
operation of waterflow detectors. Purchasers who install waterflow detectors for use
by others must leave this manual or a copy of it with the user. Read all instructions
carefully before beginning.
The model WFDTN is a vane-type waterflow detector for use in wet-pipe fire sprin-
kler systems only. Vane-type waterflow detectors shall not be used as the sole initiat-
ing device in both deluge and preaction systems; waterflow detectors used in these
types of systems may result in an unintended discharge caused by a surge, trapped air
or a short retard time.
Installation must be performed by qualified personnel and in accordance with all na-
tional and local codes and ordinances.
Shock hazard: Disconnect power source before servicing. Serious injury or death
could result.
Risk of explosion: Not for use in hazardous locations. Serious injury or death could
result.
PRINCIPLES OF OPERATION
Vane-type waterflow detectors mount to water filled pipes in fire sprinkler systems.
Waterflow in the pipe deflects a vane. Deflection of the vane produces a switched
output, usually after a specified delay.
All WFDTNs have a pneumatically controlled mechanical delay mechanism. Delays
do NOT accumulate; they reset if the flow of water stops or drops below minimum
triggering flow rate before the entire delay has elapsed. All detectors will activate on
a sustained flow of water of 10 gallons per minute (gpm) or greater downstream of
the device.
COMPATIBLE PIPE TEES/RISERS
The WFDTN is supplied with 12 paddles. One paddle is provided for each size of the
threaded, sweat or plastic tee. See Figure 1 and approximate tee depth chart. Each
paddle has an indication that shows the pipe size and type of tee to be used with. The
WFDTN also fits 1", 1½", and 2" Reliable riser manifolds when used with paddle tree
P02-0032-300 (purchased separately).
APPROXIMATE TEE DEPTH REQUIREMENTS (SEE FIGURE 1)
Tee Depth
Threaded
Sweat
1 × 1 × 1"
2
1
/
"
1
3
/
"
8
4
1
1
/
× 1
1
/
× 1"
2
1
/
"
2
1
/
"
4
4
2
8
1
/
× 1
/
× 1"
2
/
"
2
/
"
1
1
3
1
2
2
4
4
2 × 2 × 1"
3
1
/
"
2
3
/
"
4
4
Two sets of SPDT (Form C); 10 A @ 125/250 VAC
4 – 10 GPM
375 PSI (Max.)
WFDTN – 4in H x 3½ in W x 6¾ in D
32°F to 150°F (0°C to 66°C)
WFDTN – NEMA Type 4, as tested by Underwriters Laboratories, Inc. (UL)
5,213,205
CAUTION
WARNING
CPVC NIBCO/
CPVC
SPEARS
SPEARxS
CPVC/Tyco
(no insert)
(with insert)
2
1
/
"
2
15
/
"
8
32
N/A
N/A
3"
3"
N/A
N/A
; 2.5 A @ 24 VDC
FIGURE 1. MOUNTING DIMENSIONS
2-5/8"
4"
TEE
ADAPTER
TEE DEPTH
DESIGNED TO FIT WITHIN 2 X 4 STUD WALL CONSTRUCTION
INSTALLATION GUIDELINES
Before installing any waterflow alarm device, be thoroughly familiar with:
NFPA 72:
National Fire Alarm Code
NFPA 13:
Installation of Sprinkler Systems
NFPA 25:
Inspection, Testing, and Maintenance of Water-based Fire Protection
Systems, Section 5.3.3.2
NFPA 13D: Standard for 1 and 2 Family Dwellings and Manufactured Homes
NFPA 13R: Standard for Multi-family Dwellings
Also, follow other applicable NFPA standards, local codes and the requirements of the
authority having jurisdiction.
2
13
/
"
16
N/A
N/A
N/A
1
3-1/2"
INSTALLATION GAUGE
END OF PADDLE TREE MUST
FIT BETWEEN TOP OF TEE
AND BOTTOM OF FLANGE
TEE FITTING
PLASTIC VANE
W0390-00
I56-4043-D
4/21

Advertisement

loading

Summary of Contents for Safe Signal WFDTN

  • Page 1 Before installing any waterflow alarm device, be thoroughly familiar with: COMPATIBLE PIPE TEES/RISERS The WFDTN is supplied with 12 paddles. One paddle is provided for each size of the NFPA 72: National Fire Alarm Code threaded, sweat or plastic tee. See Figure 1 and approximate tee depth chart. Each...
  • Page 2 PREOPERATION TESTING FIGURE 2. ASSEMBLY DIAGRAM Fill the sprinkler system with water and check for leaks around the WFDTN. If there is a leak, check to see that the fittings are tight. If leak persists, drain the system and remove the detector (see removal instructions under Maintenance).
  • Page 3 Test detectors at least quarterly as described under Operational Testing to insure proper operation. Test more often if required by the authority having jurisdiction. Under normal conditions Safe Signal waterflow detectors should provide years of GROUND GROUND trouble-free service.
  • Page 4 SAFE SIGNAL for inspection. Upon a determination by SAFE SIGNAL defective manufacture, labeling, or packaging. that a product is not as warranted, SAFE SIGNAL shall, at its exclusive option, replace or repair said defective product or parts thereof at its own expense except that Purchaser shall pay all...