INSTALLATION AND MAINTENANCE INSTRUCTIONS
WFDTNRN Vane-type Waterflow Detector
SPECIFICATIONS
Contact Ratings:
Triggering Threshold Bandwidth (Flow Rate):
Static Pressure Rating:
Dimensions (Installed):
Operating Temperature Range:
Shipping Weight:
Enclosure Rating:
U. S. Patent Number:
IMPORTANT
Please Read Carefully And Save
This instruction manual contains important information about the installation and
operation of waterflow detectors. Purchasers who install waterflow detectors for use
by others must leave this manual or a copy of it with the user. Read all instructions
carefully before beginning.
The model WFDTNRN is a vane-type waterflow detector for use in wet-pipe fire
sprinkler systems only. Vane-type waterflow detectors shall not be used as the sole ini-
tiating device in both deluge and preaction systems; waterflow detectors used in these
types of systems may result in an unintended discharge caused by a surge, trapped air
or a short retard time.
Installation must be performed by qualified personnel and in accordance with all na-
tional and local codes and ordinances.
Shock hazard: Disconnect power source before servicing. Serious injury or death
could result.
Risk of explosion: Not for use in hazardous locations. Serious injury or death could
result.
PRINCIPLES OF OPERATION
Vane-type waterflow detectors mount to water filled pipes in fire sprinkler systems.
Waterflow in the pipe deflects a vane. Deflection of the vane produces a switched out-
put. All detectors will activate on a sustained flow of water greater than 10 gallons per
minute (gpm) but will not activate if the flow rate is less than 4 gpm.
COMPATIBLE PIPE TEES/RISERS
Model WFDTNRN is supplied with 12 paddles. One paddle is provided for each size
of the threaded, sweat or plastic tee. See Figure 1 and approximate tee depth chart.
Each paddle has an indication that shows the pipe size and type of tee to be used with.
APPROXIMATE TEE DEPTH REQUIREMENTS (SEE FIGURE 1)
Tee Depth
Threaded
Sweat
1 × 1 × 1"
2
1
/
"
1
3
/
"
8
4
1
1
/
× 1
1
/
× 1"
2
1
/
"
2
1
/
"
4
4
2
8
1
1
/
× 1
1
/
× 1"
2
3
/
"
2
1
/
"
2
2
4
4
2 × 2 × 1"
3
1
/
"
2
3
/
"
4
4
10 A @ 125/250 VAC
4 to 10 GPM
250 PSI (Max.)
4in H x 3½ in W x 6¾ in D
32°F to 150°F (0°C to 66°C)
2 lbs
NEMA 4
5,213,205
CAUTION
WARNING
CPVC NIBCO/
CPVC
SPEARS
SPEARS
CPVC/Tyco
(no insert)
(with insert)
2
1
/
"
2
15
/
"
8
32
N/A
N/A
3"
3"
N/A
N/A
;
2.5 A @ 24 VDC
FIGURE 1. MOUNTING DIMENSIONS
2-5/8"
4"
TEE DEPTH
DESIGNED TO FIT WITHIN 2 X 4 STUD WALL CONSTRUCTION
INSTALLATION GUIDELINES
Before installing any waterflow alarm device, be thoroughly familiar with:
NFPA 72:
Installation, Maintenance and Use of Local Protective Signalling Sys-
tems
NFPA 13:
Installation of Sprinkler Systems, specifically Section 3.17
NFPA 25:
Inspection, Testing and Maintenance of Sprinkler Systems, specifically
Chapters 4 and 5, and Section 5.3.3.2
NFPA 13D: Standard for Residential Dwellings
NFPA 13R: Standard for Multifamily Dwellings
FIGURE 2. ASSEMBLY DIAGRAM
COVER
TIMER
ASSEMBLY
2
13
/
"
(P/N FS-RT)
16
N/A
N/A
N/A
GASKET
FLOW
ACTUATOR
LEVER
WATERFLOW
1
3-1/2"
TEE
ADAPTER
INSTALLATION GAUGE
END OF PADDLE TREE MUST
FIT BETWEEN TOP OF TEE
AND BOTTOM OF FLANGE
TEE FITTING
PLASTIC VANE
1" NPT
THREAD
W0390-00
TAMPER PROOF
WRENCH (P/N WFDW)
COVER TAMPER
SWITCH (OPTIONAL P/N CTS)
GROUND SCREW
MOUNTING
PLATE
PADDLE
FILISTER HEAD
SCREW
W0388-01
I56-4044-E
4/21

Advertisement

loading

Summary of Contents for Safe Signal WFDTNRN

  • Page 1 COMPATIBLE PIPE TEES/RISERS NFPA 13D: Standard for Residential Dwellings Model WFDTNRN is supplied with 12 paddles. One paddle is provided for each size NFPA 13R: Standard for Multifamily Dwellings of the threaded, sweat or plastic tee. See Figure 1 and approximate tee depth chart.
  • Page 2 See Figure 1 for mounting dimensions. Fill the fire sprinkler system and check for leaks around the WFDTNRN. If it leaks, check to see that the fittings are tight. If leak persists, drain the system and Locate the detector 6 to 7 feet above the floor to protect from accidental damage.
  • Page 3 SCREW SCREW Under normal conditions Safe Signal waterflow detectors should provide years of trouble-free service. However, if the switch enclosure becomes faulty, request Part No. FS-RT and ensure timer is set to zero. If damage occurs to paddle, order replacement kit.
  • Page 4 SAFE SIGNAL for inspection. Upon a determination by SAFE SIGNAL defective manufacture, labeling, or packaging. that a product is not as warranted, SAFE SIGNAL shall, at its exclusive option, replace or repair said defective product or parts thereof at its own expense except that Purchaser shall pay all...