Error Codes - LG Therma V R32 Gen3 Installation And Setup

Table of Contents

Advertisement

Code No.
1
Problem in remote room air sensor
Problem in refrigerant (inlet side) sensor
2
6
Problem in refrigerant (outlet side) sensor
8
Problem in
water
13
Problem in solar pipe sensor
16
Problems in sensors
17
Problem in
water-inlet
Problem in
water-outlet
18
19
Problem in electric heater outlet sensor
10
BLOC Water pump Lock
Bad communication between remote
3
controller and unit.
5
Bad communication between Main PCB
assembly(Heater) and Main PCB assembly(lnverter)
of the unit.
53
PCB program (EEPROM) fault
9
14
Problem in flow switch
15
Water pipe overheated
W:
www.seconrenewables.com
Description
tank sensor
sensor
sensor
T: 0191 516 6554

Error Codes

Cause
• Incorrect connection between
sensor and PCB(Heater).
• PCB(Heater) fault
• Sensor fault
Restriction of BLOC Water pump
• Incorrect connection between
sensor and PCB(Heater)
• PCB(Heater) fault
• Sensor fault
• The connector for transmission is
disconnected
• The connecting
wires
are
misconnected
• The communication line is broken
• Main PCB assembly(lnverter) is
abnormal
• Main PCB assembly(Heater) is
abnormal
• Electrical or mechanical damage a
the EEPROM
• Flow switch is open
while
internal
water
pump is
working
• Flow switch is closed
while
internal
water
pump is not
working
• Flow switch is open
while
DIP
switch No. 5 of Main PCB
assembly(Heater) is set as on
• Abnormal operation of electric
heater
• Leaving
water
temperature is
above 72
°C.
Normal Condition
• Resistance: 10 kO at 25 centigrade
(unplugged) -+ for Remote room air
sensor
• Resistance: 5 kO at 25 centigrade
(unplugged)-+ for all sensors EXCEPT
remote room air sensor
• Voltage: 2.5
V
DC at 25 centigrade
(plugged) (for all sensors)
• Refer resistance-temperature table to
check in different temperature
• BLOC Water pump defect/
assembly condition abnormal
• Fan lock by foreign material
• Wire connection between remote
controller and Main PCB
assembly(Heater) should be tight
• Output
voltage
of PCB should be 12 V
DC
• Wire connection between remote
control panel and Main PCB
assembly(Heater) should be tight.
• This error can not be permitted
• Flow switch should be closed
internal
water
pump is
working
switch No. 5 of Main PCB
assembly(Heater) is set as on
• Flow switch should be open
internal
water
pump is not
• If there is no problem in electric heater
control, possible maximum leaving
water
temperature is 72
°C