Quick installation
Use four 1/4" bolts (not included) to mount the inverter
5
vertically on a solid wall. Allow at least 4 inch space
around the apparatus!
Combi 2000
Combi 4000
A
300mm / 11.8 inch
B
405.5mm / 16 inch
6
Open the connection compartment; Steps:
1 Loosen the two Philips screws that secure
the front cover plate for two turns;
2 Slide the front cover plate from the cabinet.
7
Select the appropriate wiring and fuses from the tables below
AC WIRING AND FUSES
AC Load rating for cables up to 10ft length @ 77ºF:
AC load rating
0-12 Amps
12-18 Amps
18-25 Amps
25-37 Amps
37-50 Amps
The maximum current passing the Mass Combi must
be limited. Therefore the AC-input must be protected
by a fuse, as specified below.
Model Mass Combi
All models
Recommended wire colours (refer to local rules):
Wire color
Meaning
Black
Hot or Line
White
Neutral
Green
Ground
Mastervolt International B.V,
P.O.Box 22947, NL-1100 DK Amsterdam, The Netherlands.
All manuals and user guides at all-guides.com
Mass Combi 120V
Minimum cross section:
AWG 16
AWG 14
AWG 12
AWG 10
AWG 8
Maximum rating of the
AC input fuse
50 Amps
Must be
connected to:
L1
N
PE / GND
A
TR
B
Step 2
DC WIRING AND FUSES
Model Mass Combi
12/2000-100
12/4000-200
24/2000-60
24/4000-120
Model Mass Combi
12/2000-100
12/4000-200
24/2000-60
24/4000-120
Recommended wire colours (refer to local rules):
Wire color
Meaning
Red
Positive
Black
Negative
Tel.: +31-20-3422100
Email: info@mastervolt.com
English
Step 1
2x
DC Cable cross section:
2x 70mm² / AWG2/0
4x 70mm² / AWG2/0
2x 50mm² / AWG0
2x 70mm² / AWG2/0
Recommended DC fuse
250A
2 x 250A
125A
250A
Must be
connected to:
+ (POS)
– (NEG)
Web: www.mastervolt.com v1.0 080731US