Fujitsu ASUH18LMAS Design & Technical Manual page 64

Hide thumbs Also See for ASUH18LMAS:
Table of Contents

Advertisement

16) Heat pump backup setting
Enables or disables the heat pump backup instruction from the outdoor unit.
This function will be usable provided that the corresponding outdoor unit is connected.
Function number
72
17) Emergency heat for external output terminal
Enables or disables emergency heat input.
Function number
73
NOTE: When this function is used, IR receiver unit is necessary.
18) Heat insulation condition (building insulation)
Heat insulation conditions differ according to the installed environment.
"Standard insulation" (00) allows system to rapidly respond to the cooling or heating load changes.
"High insulation" (01) is when the heat insulation structure of the building is high and does not re-
quire system to rapidly respond to cooling or heating load changes.
When "High insulation" (01) is selected:
• Overheating (overcooling) is prevented at the start-up.
• All room-temperature control settings (Function 30, 31, 35, and 36) will reset to "No correction
0.0 °F (0.0 °C)".
Function number
95
NOTE: When changing Function 95, perform this setting before other room-temperature control
settings (Function 30, 31, 35, and 36). If Function 95 is not set first, room-temperature con-
trol settings (Function 30, 31, 35, and 36) will be reset and you must re-do them again.
19) Special cooling operation
Stabilizes the cooling operation when the outdoor temperature is low.
• Operation mode: Fixed at COOL
• Airflow: Fixed at HIGH
• Set temperature: 76°F (24°C) to 88°F (30°C)
Function number
96
NOTES:
• Connect the optional wired remote controller to change the setting value to "Enable" (01).
• Do not use the wireless remote controller after changing the setting value to "Enable" (01).
• If the wired remote controller becomes noncommunicable after setting "Enable" (01), the cooling
operation starts automatically.
• If dew condenses on the indoor unit surface after setting "Enable" (01), set the setting value
back to "Disable" (00).
11-1. Function settings by using remote controller
Setting value
00
01
Setting value
00
01
Setting value
00
01
Setting value
00
01
- 60 -
Setting description
Disable
Enable
Setting description
Disable
Enable
Setting description
Standard insulation
High insulation
Setting description
Disable
Enable
Factory setting
Factory setting
Factory setting
Factory setting
11. Function settings