Ethyline Glycol Application - Hitachi RCUE40AG1 Installation, Operation And Maintenance Instructions

Air cooled water chillers screw type
Table of Contents

Advertisement

Model: RCUE300AG1, RCUE330AG1
Ambient
Performance
Temperature
Capacity
35°C
Input
COP
Capacity
30°C
Input
COP
Capacity
25°C
Input
COP
Capacity
20°C
Input
COP
: Standard Condition (Ambient: 35°C, Water Inlet/Outlet: 12/7°C, Full Load)
NOTE:
1. Capacity: Cooling Capacity (kW)
Input:
Total Input Power (Compressor + Fans) (kW)
COP:
Capacity/Input (kW/kW)
2. Operating Conditions:
Chilled Water Outlet Temperature:
Water Flow Rate:
Condenser Fan:
3. Above Table shows the percentage of Capacity, Input and COP
based on the standard condition.
Therefore, each value can be calculated as below example:
Example: Model RCUE100AG1
Standard Condition
Ambient: 30°C, Capacity 70%
Capacity:
246 kW
Capacity:
Input:
84.2 kW
Input:
COP:
2.92
COP:
4. Control marked (*) is available by the optional selection switch.
DSW7-3 / ON: Minimum Load Extension.
16.3. ETHYLENE GLYCOL APPLICATION
" Low Ambient Application
Under the condition where the ambient temperature is low
in winter, there is a case where the unit and piping will
become damaged by freezing during the shutdown periods.
To prevent freezing, it is effective to operate the pump.
This Chiller has the pump ON/OFF operation control to
avoid freezing. This control become available by
connecting Pump Operation circuit. (See Wiring Diagram).
Additionally, in a case where measures such as water
raining are difficult, utilise antifreeze mixture of ethylene
glycol.
Below table shows the ethylene glycol percentage
suggested for the different temperature values.
The table also shows the correction factors, since unit with
antifreeze mixture have a slight different performance
compared with no glycol.
Example:
− Cooling Capacity with ethylene glycol = Kc × Cooling
Capacity without ethylene glycol
− Input Power, Flow Rate and Pressure Drop is calculated
in the same way as Cooling Capacity
10%
(*)
%
12
30
40
50
%
14
35
38
43
%
86
86
105
116
%
13
32
40
50
%
13
32
34
38
%
100
100
118
132
%
13
34
40
50
%
12
29
30
34
%
117
117
133
147
%
14
35
40
50
%
4
26
28
30
%
135
135
143
167
7°C
Constant
All Fans Running
246 × 0.7 = 172 kW
84.2 × 0.5 = 42.1 kW
2.92 × 1.4 = 4.09 kW
APPLICATION DATA
Compressor Load
25~100%
60
70
80
90
48
56
67
80
125
125
119
113
60
70
80
90
42
50
57
67
143
140
140
134
60
70
80
90
37
42
50
59
162
167
160
153
60
70
80
90
32
36
42
50
188
194
190
180
(Water Outlet Temperature: 5 ~ 15°C)
Minimum Ambient
Temperature
Required Ethylene Glycol
Percentage
Cooling Capacity Correction
Factor
Input Power Correction Factor
Flow Rate Correction Factor
Pressure Drop Correction
Factor
"
Low Water Temperature Application (Option)
When utilising water less than 5 °C, antifreezing mixture of
ethylene glycol shall be input to the water system.
Low water temperature Option is categorised 3 level
depending on water outlet temperature.
Therefore, please specify the level when ordering .
Freeze Protection Thermostat has been set in the factory.
Table shows Required Ethylene Glycol percentage for each
category.
16
/91
Full Load
100
100
100
100
106
83
94
120
113
100
112
70
88
143
127
100
110
120
57
67
80
175
164
150
°C
-3
-7
-13
-22
wt%
10
20
30
40
Kc
0.99 0.98 0.97 0.96
Ki
1.00 0.99 0.99 0.98
Kf
1.00 1.01 1.04 1.08
Kp
1.04 1.11 1.18 1.29