Fault Code Table - andrews COMBIflo 100/300 Installation, Operation And Maintenance Manual

Indirect high effi ciency boiler & stainless steel storage water heater
Hide thumbs Also See for COMBIflo 100/300:
Table of Contents

Advertisement

6.6 FAULT CODE TABLE

Fault
Fault Description
Code
10
Outside sensor, error
20
Boiler temperature 1, sensor error
22
Water pressure 3 too low
26
Common fl ow temperature sensor
error
28
Flue gas temperature, sensor
error
40
Return temperature 1, sensor
error
50
DHW temperature 1, sensor error
60
Room temperature 1, sensor error
81
LPB short-circuit or no power
supply
82
LPB address collision
83
BSB short circuit
84
BSB address collision
98
Extension module 1, error
99
Extension module 2, error
100
More than one clock time master
102
Clock master without power
reserve
105
Maintenance message
ANDREWS COMBIfl o
Sub
Notes
Code
Any
Outside temperature sensor (B9) is faulty or missing. Check sensor
and wiring for operation (a resistor is pre fi tted which has a value
equivalent to 0
C. When an outside sensor is installed the pre fi tted
O
resistor should be removed).
Other
Boiler fl ow sensor (B2) is outside normal limits
439
Boiler fl ow sensor (B2) is short-circuit
440
Boiler fl ow sensor (B2) is open-circuit
Any
Water pressure in primary system is low and requires refi lling to a
minimum of 1.0 bar
Any
Check connections or replace faulty sensor located in fl ow pipe work
up stand section (B10)
539
Flue gas sensor (B8) is short-circuit
543
540
Flue gas sensor (B8) is open-circuit
544
Other
Boiler return sensor (B7) is outside normal limits
441
Boiler return sensor (B7) is short-circuit
442
Boiler return sensor (B7) is open-circuit
Any
Check connections or replace faulty DHW tank sensor (B3)
Any
Check connections or replace faulty room unit (R1)
Any
LPB Short circuit or no bus power supply. Check operation of OCI345
modules and cables
Any
LPB address duplicated on another Control PCB - Check address of
all PCB parameter 6600
Any
No BSB communication or wires shorted - Check operation of room
units and display modules
Any
Two room units have the same allocation address
Any
AGU2.5 confi guration error - Check parameters
Any
AGU2.5 confi guration error - Check parameters
Any
Only one device should be set as the time master, check all LMS14s
(parameter 6640) and any OZW672 connected (in case of connection
to an OZW672, this device should be the master)
Any
The control PCB battery backup for the time clock has been depleted
following the restoration of power to the heater. If this message has
not cleared within 10 minutes of power being turned on, turn the
power off , wait 10 seconds and turn the power on again. This mes-
sage does not prevent the operation of the heater in any way.
Any
Item requiring attention but not preventing heater operation (e.g. 12
Month service due). Check details of message on the heater Front
GUI screen.
70