Model 360 Surge Protective Device (SPD) Table of Contents Precautions Introduction Unpacking and Preliminary Inspection Storage Identification Nameplate SPD Location Considerations Environment Audible Noise Mounting Service Clearance Equipment Performance Electrical Voltage Rating Branch Circuit Overcurrent Protection and Disconnect Means Location of Surge Protective Device (SPD)
Page 4
Please Note Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by ASCO Power Technologies for any consequences arising out of the use of this material. A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.
Failure to follow these instructions will result in death or serious injury. Proper installation is imperative to maximize the ASCO 360 SPDs effective- Note: For access to self-service ness and performance. Follow the steps outlined in this instruction bulletin tools and chat support visit se.com/us/en/work/support or...
Failure to follow these instructions will result in death or serious injury. A branch circuit Overcurrent Protection Device (OCPD) either in the form of a circuit breaker or fuse must be provided for the ASCO 360 Type 2 device. The branch circuit OCPD should either provide or include a disconnecting means.
Failure to follow these instructions can result in equipment damage. The ASCO 360 has SPD elements connected from phase to ground. It is critical that there be a robust and effective connection to the building grounding structure.
8/32 x 5/8 in. Thread Cutting Screws provided with the XMFMKIT kit. Proceed with #6 on page 12. Figure 3: Typical Model 360 SPD installation (Dimensions - in./mm.) Insert flushmount screw through hole in each corner or punch a...
Failure to follow these instructions will result in death or serious injury. LED Status Indicators Diagnostic LEDs are located on the front of the ASCO 360 SPD device. They operate as follows: • Verify that all phase voltages are present. If any of the LEDs are not illuminated, the device may not be installed correctly.
Preventive Maintenance DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, NOM-029-STPS or CSA Z462. • This equipment must only be installed and serviced by qualified electri- cal personnel.