THERM CONNECT magna
08
WOLF run around coil systems

8. THERM-CONNECT magna

08.01 General description

The high efficiency run around coil system consists of two heat exchangers with a high counterflow ratio and a
series connection of the individual heat transfer stages.
The heat is transferred via an intermediate medium consisting of a water-glycol mixture between the exhaust air coil
and the outdoor air coil.
The brine mass flow is controlled by the integrated control system depending on the power requirement of the BMS,
the air volume flow in supply air and exhaust air and the temperature conditions in the system.
The power and frost protection control is also carried out via the three-way mixing valve with high control accuracy.
This allows the brine mass flow to bypass the supply air register to prevent ice formation on the register.
Optional extensions can be used to integrate an adiabatic exhaust air humidifier, the feeding of external additional
energy into the run around coil circuit, an accurate capacity determination with monthly data backup, a reheater for
dehumidification cold recovery or a redundant double pump for fail-safe operation.
Since the pumps are designed separately for each system, the flow rate must be adapted to the respective system.
This is done during commissioning of the system by a trained technician from WOLF Geisenfeld.
Run around cooler
T
Exhaust air
DN ...
VL
A1
external connections
supply air register
-
Z1
-
Z2
exhaust air register
T
T
-
A1
-
A2
Reheater
-
N1
AB
-
N2
M
B
Heating supply
A
-
H1
-
H2
T
Cooling supply
-
K1
-
K2
Z2
RL
T
optional
DN ..
Outside air
T
Heater
Filter preheater
optional
adiabatic
humidification
V
ABL
T
Exhaust air
supply limit
WOLF Geisenfeld
A2
T
T
AB
A
M
B
1
Z1
N1
K1
K2
N2
External
VL
cooling supply
optional
Reheater
Cooler
optional
Locking min.
P
P
optional
T
2
H1
H2
External
Drainage and venting on site
heat supply
optional
WOLF Anlagen-Technik
Qualitätsmanagement
Supply air
GmbH & Co.KG
Münchener Str. 54
zertifiziert nach
85290 Geisenfeld
DIN EN ISO 9001
Tel. 08452 / 99-0
Fax.08452 / 99-250
2013
Bearb.
Gepr.
Norm
V
T
ZUL
Zust.
Änderung
Datum
Name
Diese Zeichnung darf ohne unsere ausdrückliche Genehmigung weder vervielfältigt, noch dritten Personen oder Konkurrenzfirmen im Original oder
als Kopie ausgehändigt werden. Eigentums- und Urheberrecht vorbehalten.
19
Safety valve 8bar
Expansion tank
MAßSTAB
Maßstab
...
Kom.
Datum
Name
Prinzipschema
12.12.18
F.FRANZ
Hochleistungs-KVS
AB-
Änderungen vorbehalten
Blatt
Bl