Download Print this page

Technical Data - Viking MicrofastHP VK316 Technical Data Manual

Quick response fusible element upright high pressure sprinkler

Advertisement

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
The Viking MicrofastHP
international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
Sprinkler Temperature
Classification
Ordinary
Intermediate
High
Sprinkler Finishes: Brass, Chrome, White Polyester
Corrosion Resistant Sprinkler Coatings: ENT
The sprinkler temperature rating is stamped on the deflector.
1
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
2
Refer to specific installation standards.
The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart(s).
3
these tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are
compatible with or suitable for the proposed environment. Note that the spring is exposed on sprinklers with ENT coatings. For ENT coated automatic
sprinklers, the waterway is coated.
For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only.
4
cULus Listed as corrosion resistant.
5
Form No. F_062814
20.06.04
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Quick Response Upright High Pressure Sprinkler VK316 is available through a network of domestic and
®
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Nominal
Temperature Rating
165 °F (74 °C)
205 °F (96 °C)
280 °F (138 °C)
, Black Polyester
4
3,5
Protective Sprinkler Cap
Wrench Flat
Standard Sprinkler Wrench 21475M/B
Rev 20.1

TECHNICAL DATA

1
, and ENT
4
3,5
Footnotes
Figure 1:
MicrofastHP
RESPONSE FUSIBLE ELEMENT
UPRIGHT HIGH PRESSURE
SPRINKLER VK316 (K5.6)
Maximum Ambient
Ceiling Temperature
2
100 °F (38 °C)
150 °F (65 °C)
225 °F (107 °C)
Page 2 of 3
QUICK
®
Frame Paint
Color
None
White
Blue

Advertisement

loading

This manual is also suitable for:

13953