DIFFERENTIAL PRESSURE TRANSMITTER
DPT-3wire
Model summary
Each device has 2 or 4 jumper selectable measuring ranges. Each device is individually temperature compensated.
2 range model
- D for display
- AZ for autozero element*
- Q for square root output
DPT100
( -D -AZ -Q)
DPT±100 ( -D -AZ -Q)
DPT250
( -D -AZ -Q)
DPT500
( -D -AZ -Q)
DPT1000 ( -D -AZ -Q)
DPT2,5K
( -D -AZ -Q)
DPT5K
( -D -AZ -Q)
4 range model
- R4 for 4 measuring range
- D for display
- AZ for autozero element*
- Q for square root output
DPT1000 -R4 ( -D -AZ -Q)
DPT3000 -R4 ( -D -AZ -Q)
DPT5000 -R4 ( -D -AZ -Q)
**) %/FS from highest pressure range (including: general accuracy, temperature drift, linearity, hysteresis and repetition
error)
*) -AZ model recommended
The Differential Pressure Transmitter is delivered individually packed with standard accessories (see
accessories).
Measuring
Measuring
range 1
range 2
0...50 Pa
0...100 Pa
-50...+50 Pa
-100...+100 Pa
0...100 Pa
0...250 Pa
0...250 Pa
0...500 Pa
0...500 Pa
0...1000 Pa
0...1500 Pa
0...2500 Pa
0...2500 Pa
0...5000 Pa
range
range
range
1
2
3
250Pa
500 Pa
750 Pa
750Pa
1500Pa
2250Pa
1250Pa
2500Pa
3750Pa
Accuracy %/FS **)
over operation
temp.
-10...+50°C
range 1 and range 2
± 3%
± 1,5%
± 1,5%
± 1,5%
± 1,5%
± 1,5%
± 1,5%
range
Accuracy %/FS **)
4
over operation temp.
-10...+50°C
range 1...4
1000Pa
± 1,5%
3000Pa
± 1,5%
5000Pa
± 1,5%
Long term stability
typical 1 year
-AZ
without -AZ
≤ ± 1 Pa
≤ ± 8 Pa *)
≤ ± 1 Pa
≤ ± 8 Pa *)
≤ ± 1 Pa
≤ ± 8 Pa *)
≤ ± 1 Pa
≤ ± 8 Pa
≤ ± 1 Pa
≤ ± 8 Pa
≤ ± 1 Pa
≤ ± 24 Pa
≤ ± 1 Pa
≤ ± 24 Pa
Long term stability
typical 1 year
-AZ
without -AZ
≤ ± 1 Pa
≤ ± 8 Pa
≤ ± 1 Pa
≤ ± 24 Pa
≤ ± 1 Pa
≤ ± 24 Pa

Advertisement

loading

Summary of Contents for HK Instruments DPT100

  • Page 1 - AZ for autozero element* temp. - Q for square root output -10…+50°C without -AZ range 1 and range 2 DPT100 ( -D -AZ -Q) 0…50 Pa 0…100 Pa ± 3% ≤ ± 1 Pa ≤ ± 8 Pa *) DPT±100 ( -D -AZ -Q)
  • Page 2 Technical data Response Time 0.8 / 4 s selectable by jumper Max. pressure 25 kPa Bursting pressure 50 kPa Suitable media Air and non-aggressive gases Measuring element Piezoresistive Electrical interface Supply voltage 24 VAC or VDC (3-wire) Max. tolerance ± 10% Power consumption <...
  • Page 3 Zero point adjustment is carried out every 10 minutes. During zero point adjustment the output and display values will freeze to the latest measured value. The automatic zero point adjustment takes 4 seconds. Dimensions 90.0 36.0 HK INSTRUMENTS OY FIN-40950 MUURAME FINLAND...
  • Page 4 Installation Electrical Connection: 0-10V Output 0…10 V 4-20mA Output 4…20 mA Supply 24 VAC or VDC Ground ZERO 0-10V 0,1/4s 4-20mA 1000 Push button for zero 24VDC Zero: Push button zero Jumpers Jumpers 4-range model e.g. DPT1000-R4 2-range model Jumpers e.g.