- AZ for autozero element* temp. - Q for square root output -10…+50°C without -AZ range 1 and range 2 DPT100 ( -D -AZ -Q) 0…50 Pa 0…100 Pa ± 3% ≤ ± 1 Pa ≤ ± 8 Pa *) DPT±100 ( -D -AZ -Q)
Page 2
Technical data Response Time 0.8 / 4 s selectable by jumper Max. pressure 25 kPa Bursting pressure 50 kPa Suitable media Air and non-aggressive gases Measuring element Piezoresistive Electrical interface Supply voltage 24 VAC or VDC (3-wire) Max. tolerance ± 10% Power consumption <...
Page 3
Zero point adjustment is carried out every 10 minutes. During zero point adjustment the output and display values will freeze to the latest measured value. The automatic zero point adjustment takes 4 seconds. Dimensions 90.0 36.0 HK INSTRUMENTS OY FIN-40950 MUURAME FINLAND...
Page 4
Installation Electrical Connection: 0-10V Output 0…10 V 4-20mA Output 4…20 mA Supply 24 VAC or VDC Ground ZERO 0-10V 0,1/4s 4-20mA 1000 Push button for zero 24VDC Zero: Push button zero Jumpers Jumpers 4-range model e.g. DPT1000-R4 2-range model Jumpers e.g.