Advertisement

FIRE ALARM SYSTEM
INSTRUCTION/OPERATING MANUAL
Copyright © 1988
Published in the U.S.A.
All rights reserved
Serial Number____________________
301 2nd Ave. Waltham, MA 02451-1133 USA TEL: (781) 487-0088 FAX: (781) 370-4132
FC-72 SERIES
firealarmresources.com
Part Number: 9000-0007
Version 5.1

Advertisement

Table of Contents
loading

Summary of Contents for FCI FC-72 Series

  • Page 1 FC-72 SERIES FIRE ALARM SYSTEM INSTRUCTION/OPERATING MANUAL Copyright © 1988 Part Number: 9000-0007 Published in the U.S.A. Version 5.1 All rights reserved Serial Number____________________ 301 2nd Ave. Waltham, MA 02451-1133 USA TEL: (781) 487-0088 FAX: (781) 370-4132 firealarmresources.com...
  • Page 2 firealarmresources.com...
  • Page 3: Table Of Contents

    23.0 Central Station Transmitter Connections ................22 24.0 Proprietary Protective Signaling System Connections ............23 25.0 FCI Approved UL Listed (Multiple Listed), Compatible Two-wire Smoke Detectors ....24 25.1 Model PSD/CPD Smoke Detector wiring information ............24 25.2 Model SBS Smoke Detector wiring information ..............26 25.3 Model 301 Smoke Detector wiring information ..............26...
  • Page 4: Important Information

    A copy of these instructions is included with each product and is available from the manufacturer. This equipment is Listed by various listing agencies for use in fire alarm systems. Use only components which are compatible with the FCI system. The installation MUST be in accordance with the instructions in this manual. THEREFORE: •...
  • Page 5 We do not recommend the use of overhead or outside aerial wiring due to the increased susceptibility to nearby lightning strikes. Consult with the FCI Technical Support Department if any problems are anticipated or encountered.
  • Page 6 FCI reserves the right to change hardware and/or software design, which may subsequently affect the contents of this manual. FCI assumes no responsibility for any errors that may appear in this manual. Neither this manual nor any part of it may be reproduced without the advance written permission of Fire Control Instruments, Inc.
  • Page 7: Diagram 1. Bmfc-6 Diode Matrix

    9000-0007 Page 5 of 28 firealarmresources.com...
  • Page 8: Diagram 2. Bmfc-6 Test Points

    NOTE: All the above voltages are approximate and it is entirely possible to have a trouble condition with readings other than shown. If your voltage readings differ and you cannot solve your trouble condition by consulting this manual, please contact your local authorized FCI Distributor. Page 6 of 28 9000-0007 firealarmresources.com...
  • Page 9: Functional Switches

    1.0 FUNCTIONAL SWITCHES 1.1 BMFC Switches Operational switches located on the BMFC basic fire card are as follows: • Trouble Silence Switch (Fig. 1) This switch, when operated, will silence the System Trouble audible sounder. Upon correction of the trouble condition, the audible will sound again to indicate that the switch should be returned to the normal position.
  • Page 10: Jumpers And Matrix

    4.0 JUMPERS AND JUMPER MATRIX The jumpers and jumper matrix for the BMFC are shown in Table 1. Table 1 JUMPER FUNCTION J-11 Cut if TCM-6, BMC-6 or CCM-6 module is installed. J-12 Cut when Reversing Relay is being used to transmit an alarm via telephone lines. J-13 Cut if RTI (Remote Trouble Indicator)is NOT used.
  • Page 11: Troubleshooting The City Box Circuit

    Terminal 4 is negative ( - ) and Terminals 3 and 5 are positive (+). Connect only the notification appliances listed in FCI Addendum, P/N 9000-0427 to these terminals per Figure 2: To make any zone activate the Auxiliary Notification Appliance Outputs, Install a J4A, J4B diode jumper to the right of each zone used for this output.
  • Page 12: Notification Appliance Circuits

    7.0 NOTIFICATION APPLIANCE CIRCUITS The voltage on these circuits is 24 VDC (nominal). Connect only the UL Listed notification appliances shown in FCI Addendum, P/N 9000-0427 to these circuits. Follow the installation instructions furnished with each appliance. The BMFC contains two notification appliance circuits, each rated at 1.75 amps, which operate only in unison.
  • Page 13: Troubleshooting The Notification Appliance Circuit

    Notification Appliance Circuit 2 - Remove the 3.9K ohm, 1/2 watt, resistor from Terminals 10 ( - ) and 13 (+), and connect resistor to Terminals 11 and 12. Connect field wiring to terminals per Figure 3. Class B, Style Y Wiring Notification Appliance Circuit 1 - Remove the 3.9K ohm, 1/2 watt, resistor from Terminals 6 ( - ) and 9 (+), then connect it in parallel within the last device on the circuit.
  • Page 14: Notification Appliance Wiring Estimator

    7.3 Notification Appliance Circuit Wiring Estimator Use the chart (Figure 5) to determine the required wire size for each notification appliance circuit. 1) Compute the required current. (Number of appliances multiplied by appliance current = amperes) 2) Compute the distance in feet from panel to the last appliance. 3) Locate the total appliance load (amperes) on the vertical axis of the chart.
  • Page 15: Remote Trouble Indicator

    10.0 REMOTE TROUBLE INDICATOR CONNECTION Terminals 17, 18 and 19 are for the connection of the optional 3-wire remote trouble indicator (RTI). The RTI is supervised for grounds and opens. Should an open occur, the system will indicate trouble. To use the RTI, install trouble relay K1 (4500-0024). Cut the jumper (JRTI) which is located to the LEFT of Terminals 17, 18 and 19.
  • Page 16: Smoke Detector Output

    FCI approved, U.L. Listed compatible, two-wire photoelectric and ionization smoke detectors that use the supervisory current from the initiating circuit as their power source can be used. Each zone is capable of powering a specified number of FCI approved detectors. See FCI Addendum, P/N 9000-0427 for a list of approved detectors.
  • Page 17 J3A and J3B. The J10A, J10B jumper to the LEFT of each zone should be removed for supervision. D. WIRING U.L. Listed N.O. Detection Devices or 4- wire smoke detectors may be used. For FCI approved, U.L. Listed, and Multiple Listed 2-wire smoke detectors, see FCI Addendum, P/N 9000-0427.
  • Page 18: Verification Zone Detector Module (Vzm)

    Class A, Style D or Class B, Style B at Terminals 37 through 40 of the BMFC or ZMC. Each zone is capable of powering a specific number of FCI approved two-wire detectors.
  • Page 19: Double Density Zone Detector Module (Zdm-D)

    (consult factory). Each zone on the ZDM-D is capable of powering a specific number of two-wire smoke detectors. NOTE: When using two-wire smoke detectors, ONLY FCI Approved, U.L. Listed (Multiple Listed) two-wire smoke detectors should be used. See FCI Addendum, P/N 9000-0427.
  • Page 20: Sprinkler Supervisory Service

    A. CODED OPERATION All ZDM-D modules are normally configured in the “latching” mode of operation. If coded operation (from coded initiating devices) is desired, cut the latch resistor: R23 for Zone A and R24 for Zone B. B. WATERFLOW DETECTION When using the ZDM-D module for waterflow alarm detection, the maintenance switch of the appropriate zone must be bypassed (per U.L.
  • Page 21: Remote Zone Annunciation

    18.0 ACCESSORY ZONE SIGNAL OUTPUT A. Alarm by Zone Output - Terminal 42. This is to be used only with FC-72 series accessories, SRB-6, RB-6, etc. It provides a power limited 24 VDC alarm output per zone. NOTE: When using ZDM-D module, Terminal 33 is used as alarm output for Zone A and Terminal 42 for Zone B.
  • Page 22: Standby Battery Connections

    19.0 STAND-BY BATTERY CONNECTIONS These (non-power limited) terminals are for the connection of sealed lead calcium (gel type) rechargeable batteries. BE SURE TO OBSERVE POLARITY. Terminal 43 is positive (+) and 44 is negative ( - ). The automatic float charge circuitry is capable of maintaining batteries with capacity ratings between 1.9 and 17 ampere/hours.
  • Page 23 Table 2 FC-72 System Battery Standby Calculation Chart Supv. Alarm Total Supv. Total Alarm Qty Model Description Current Current Current Current FC-72-1 1 Zone Control Panel .063 A .370 A(*) .063 A .370 A BMFC-6 Basic Master Fire Card —— ——...
  • Page 24: Central Station Transmitter Connections

    23.0 CENTRAL STATION TRANSMITTER CONNECTIONS The FC-72 control panel may be used in conjunction with the below listed units to meet the requirements for Central Station protective Signaling Service per NFPA 72. Signals for fire and trouble are transmitted over two (2) separate circuits •...
  • Page 25: Proprietary Protective Signaling System Connections

    24.0 PROPRIETARY SUPERVISING STATION SYSTEM CONNECTIONS The FC-72 control may be used in conjunction with Keltron Model DMP703 or DMP704 Proprietary alarm receiving units to meet the requirements for Proprietary Alarm Service per NFPA 72. Signals are transmitted for fire, trouble and supervisory functions over three (3) separate circuits. See Figure 23 for connections for fire and trouble transmissions.
  • Page 26: Fci Approved Ul Listed (Multiple Listed), Compatible Two-Wire Smoke Detectors

    Only FCI approved, compatible two-wire photoelectric and/or ionization smoke detectors, which are U.L. Listed, and Multiple Listed for use with the FC-72 Control may be used. FCI Addendum, P/N 9000-0427 lists those models that should be used, together with the maximum that may be connected to each zone.
  • Page 27 2-WB Base less options 2WRLT Base with Remote Indicator option 2WRLT Base with Remote Indica- and Remote Test Switch options 2WRB Base with relay option 9000-0007 Page 25 of 28 firealarmresources.com...
  • Page 28: Model Sbs Smoke Detector Wiring Information

    25.2 Model SBS Smoke Detectors Figure 22 Typical Wiring diagram - Model SBS Detectors • Installation wiring to detector is NON-POLARIZED unless a remote indicator is used. • For best system performance, it is recommended that the circuit wires be twisted pair and installed in separate grounded conduit to protect the circuit from extraneous electrical interference.
  • Page 29 NOTE: To determine the maximum number of FCI approved, UL Listed, (compatible) two-wire photoelectric or ionization detectors, FCI CPD, PSD, 301 and SBS series per circuit, see FCI Addendum, P/N 9000-0427. When configuring the initiating circuits for Class A, Style D, the FCI model VEOL (P/N 1120-0141) may be required.
  • Page 30 NOTES 1. JT Cut to transmit system trouble to remote station via telephone line. (Terminals 25 & 26) Relay K1 required. 2. JL Cut if reversing relay (K2) latch is NOT desired. 3. J12 Cut when using remote station signal via telephone line. (Terminals 25 & 26) 4.
  • Page 31 firealarmresources.com...
  • Page 32 301 2nd Ave. Waltham, MA 02451-1133 USA TEL: (781) 487-0088 FAX: (781) 370-4132 firealarmresources.com...

Table of Contents