ECC-50DA Remote Amplifier
Class A (Style Z)
Figure 1.5 illustrates how to wire speakers to the ECC-50/100 using Class A (Style Z) wiring.
1.1.5 Audio Riser Wiring
The Audio Riser is an analog voice bus that carries the recorded voice messages from the display
board to the ECC-50DAs, or the voice messages generated from a system microphone to the ECC-
50DAs. The maximum resistance on the Audio Riser is 20Ω.
Connect the Audio Riser from TB22 on the ECC-50/100 main control board to the ECC-50DAs as
shown in Figure 1.6.
To next ECC-50DA
UL-Listed 15KΩ ELR
installed at last panel
on the audio riser.
10
Supervised,
Power-limited
Figure 1.5 Class A (Style Z) Speaker Configuration
ECC-50/100
main control board
–
+
–
+
–
+
OUT
IN
ECC-50DA
Figure 1.6 ECC-50DA Audio Riser Wiring
ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:D 5/21/2015
firealarmresources.com
IN
OUT–
A
B
–
+
–
+
SBUS
OUT
IN
ECC-50DA
Installation
BATTERY
+ –
Supervised,
Power-limited
–
+
A
B
SBUS