Cv Controller Scheduling And Holidays; Week Schedules - WattMaster Auto-Zone CV Design, Installation And Operation

Table of Contents

Advertisement

Section 3
CV Controller
Scheduling and Holidays
The Constant Volume AHU controllers contain their own built in scheduling capability
for calculating Occupied/Unoccupied periods. All schedules are entered in 24-Hour
Military Format.
See the Constant Volume Menu Operations Screen for information on how to access
these programming functions.
Scheduling/Holiday Menu
Constant Volume Unit

1) Week Schedules

2) Holidays
MENU) Previous Menu
Week Schedules
Start Time
WEEK SCHEDULES
Sunday
Start Time
Value Hrs/Mins:
0
(MILITARY
FORMAT)
Stop Time
WEEK SCHEDULES
Sunday
Stop Time
Value Hrs/Mins:
0
(MILITARY
FORMAT)
Note: The second line displays which day of the week is currently being
programmed. This automatically increments as you finish the Stop Time and
continue to the next Start Time screen.
3-22
This menu appears whenever the user accesses the Scheduling
functions. It allows the user to choose between schedules or
holidays.
The screens will step through the Start Time and then the Stop
Time for each day of the week. You can quit at any point in the
process by pressing the "A" key.
All times are in 24-hour format, so 5:00 PM would be entered
as 1700.
If both the Start and Stop Times are ZERO, the schedule is in a
Continuous OFF mode.
If both the Start and Stop Times are 2359, the schedule is in a
Continuous ON mode.