F170-A-OS LEVEL MONITOR WITH HIGH / LOW LEVEL ALARMS Signal input sensor: (0)4-20mA Signal outputs: 4-20mA ref. level Alarm outputs: maximum four level alarms Options: Modbus communication F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries...
The manufacturer accepts no responsibility whatsoever if the following safety rules and precautions instructions and the procedures as described in this manual are not followed. Modifications of the F170-A-OS implemented without preceding written consent from the manufacturer, will result in the immediate termination of product liability and warranty period. ...
This operation manual describes the standard unit as well as most of the options available. For additional information, please contact your supplier. A hazardous situation may occur if the F170-A-OS is not used for the purpose it was designed for or is used incorrectly. Please carefully note the information in this operating manual indicated by the pictograms: A "warning"...
Safety rules and precautionary measures ....................... 2 About the operation manual ..........................3 Contents manual .............................. 4 Introduction ..........................5 1.1. System description of the F170-A-OS ................... 5 Operational ..........................7 2.1. General ..........................7 2.2. Control panel .......................... 7 2.3.
SYSTEM DESCRIPTION OF THE F170-A-OS Functions and features The level indicator model F170-A-OS is a microprocessor driven instrument designed to display the level and percentage as well as monitoring the level with three alarm values for a low-low, low, high and high-high level.
Page 6
Page 6 Configuration of the unit The F170-A-OS was designed to be implemented in many types of applications. For that reason, a SETUP-level is available to configure your F170-A-OS according to your specific requirements. SETUP includes several important features, such as Span, measurement units, signal settings etc.
All instructions in this manual are to be observed. Take careful notice of the " Safety rules, instructions and precautionary measures " in the front of this manual. This chapter describes the daily use of the F170-A-OS. This instruction is meant for users / operators. 2.2.
In general, the F170-A-OS will always act function at Operator level. The information displayed is dependant up on the SETUP-settings. The sensor signal will be measured by the F170-A-OS in the background, whichever screen refresh rate setting is chosen. After pressing a key, the display will be updated very quickly during a 30 second period, after which it will slow-down again.
Page 9
Page 9 Level alarm: When the actual level is outside the allowed range, an alarm message will be displayed at the bottom line of the display indicating the type of alarm: "LO LEVEL ", "HI LEVEL" or "HI-LO LEVEL". The alarm is terminated automatically as soon as the level is in its range again.
Operating Manual before carrying out its instructions. The F170-A-OS may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
Page 11
Page 11 Matrix structure SETUP-level: SCROLLING THROUGH SETUP-LEVEL Selection function-group and function: SETUP is divided into several function groups and functions. Each function has a unique number, which is displayed below the word "SETUP" at the bottom of the display. The number is a combination of two figures. The first figure indicates the function-group and the second figure the function.
Page 12
Page 12 To change or a select a value or value: To change a value, use to select the digits and to increase that value. To select a setting, both and can be used. When the new value is not valid, the increase sign or decrease-sign will be displayed while you are programming.
Page 14 OTHERS MODEL AND TYPE F170-A SOFTWARE VERSION xx.xx.xx SERIAL NO. xxxxxxx PASSWORD 0000 - 9999 TAGNUMBER 0000000 - 9999999 3.2.3. EXPLANATION SETUP-FUNCTIONS 1 - LEVEL MEASUREMENT UNIT SETUP - 11 determines the measurement unit for level. The following units can be selected: mL - L - m3 - mg - g - kg - ton - GAL - bbl - lb - cf - REV - no unit - scf - Nm3 - NL - P.
Page 15 2 - HEIGHT If desired the height of the level column can be calculated and displayed. MEASUREMENT UNIT SETUP 21 determines the measurement unit for height. The following units can be selected: mm - cm - m - mtr - inch - ft - mmwk - mmwc - cmwk - cmwc mwk - mwc - inwc - ftwc - mbar - bar - psi - no unit.
Page 16 3 - ALARM With these settings, it is determined how the level will be monitored and the functionality of the transistor / relay outputs be determined. Please be aware that the alarm levels are based on the displayed values and can be programmed at operator level as well (see setup 4 –...
When used with the internal battery option, the user may hold the concern of reliable measurement over a long period of time. The F170-A-OS has several smart power management functions to extend the battery life time significantly. Two of these functions can be set:...
Page 18
Page 18 6 - SENSOR (CONTINUED) ILTER VALUE ESPONSE TIME ON STEP CHANGE OF ANALOG VALUE IME IN SECONDS INFLUENCE INFLUENCE INFLUENCE INFLUENCE filter disabled filter disabled filter disabled filter disabled 0.3 seconds 0.5 seconds 1.0 seconds 1.8 seconds 0.5 seconds 1.0 seconds 1.5 seconds 3 seconds...
Page 19 7 - ANALOG OUTPUT A linear 4-20mA signal (option AB: 0-20mA or option AU: 0-10V) output signal is generated according to the calculated level, height or percentage with a 10 bits resolution. Note: When the analog-output is not used, please make sure that setup 71 is disabled, else the battery life-time will be reduced significantly! When a power supply is available but the output is disabled, a 3.5mA signal will be generated.
45 seconds 8 - RELAY OUTPUT With “SETUP 2”, four alarm levels can be entered. Based on the options order, the F170-A-OS will have 2, 3 or 4 alarm outputs. Note: If the unit is Intrinsically Safe, it will have two alarm outputs.
MODEL AND TYPE This window shows the model number of this product (F170-A). VERSION SOFTWARE This window shows the software version running in the F170-A-OS. SERIAL NUMBER This window shows the unique serial number of this F170-A-OS. PASSWORD All SETUP-values can be password protected.
Personnel must read and understand this Operating Manual before carrying out its instructions. The F170-A-OS may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed. ...
Do ground the aluminum enclosure properly as indicated, if the F170-A-OS has been supplied with the 115-230V AC power-supply type PM. The green / yellow wire between the back-casing and removable terminal-block may never be removed.
Page 26 4.4.2. VOLTAGE SELECTION SENSOR SUPPLY For Intrinsically Safe applications: read chapter 5. Option PB / PC / PX (AP) - battery powered and output loop-powered applications: Terminal 11 provides a limited supply voltage of 3.2 V DC for the signal output of the sensor. Note: This voltage MAY NOT be used to power the sensors electronics, converters etc, as it will not provide adequate sustained power! All energy used by the sensors pick-up will directly influence the battery life-time.
4.4.3. TERMINAL CONNECTORS When looking at the back of the F170-A-OS you will see the terminal connectors roughly in the middle of the unit. The number of the terminal connectors installed may vary, depending on options. The following terminal connectors are available: Fig.
Page 28
Page 28 ALARM OUTPUT CONNECTOR OPTIONS Terminal 10-11; relay output R1: This output is an alarm output according setup 81. Terminal 12-13; relay output R2: This output is an alarm output according setup 82. Terminal 14-15; relay output R3: This output is an alarm output according setup 83. Terminal 16-17;...
Page 29
Max. driving capacity 1000 Ohm. ANALOG INPUT OPTIONS: Terminal 03-05; Sensor input option A: The F170-A-OS requires a (0)4-20mA sensor signal which will be processed 4 times a second with a 14 bits accuracy. The input is not isolated. HF170AEN_OS_v0501_04...
Page 30 4.4.4 COMMUNICATION AND BACKLIGHT CONNECTOR When looking at the back of the F170-A-OS you will see the (optional) communication and backlight connector in the bottom right corner. Option – MODBUS communication RS232/RS485: Communication options are CB (RS232), CH (RS485), CI (RS485, 4 wire), CT (RS232 TTL) and CX (no communication).
Operating Manual before carrying out its instructions. The F170-A-OS may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
Page 32 APPENDIX A: TECHNICAL SPECIFICATION GENERAL Display Type High intensity reflective numeric and alphanumeric LCD, UV-resistant. Digits Seven 17mm (0.67") and eleven 8mm (0.31"). Various symbols and measuring units. Refresh rate User definable: 8 times/sec - 30 secs. Option ZB Transflective LCD with green LED backlight.
Page 33
Page 33 Data protection Type EEPROM backup of all setting. Backup of running totals every minute. Data retention at least 10 years. Pass code Configuration settings can be pass code protected. Environment Electromagnetic Compliant ref: EN 61326 (1997), EN 61010-1 (1993). compatibility INPUTS Flowmeter...
Page 34
Page 34 OPERATIONAL Operator functions Displayed functions • level. • height or percentage (or no indication). • low-low alarm value (level, percentage or height) • low alarm value (level, percentage or height) • high alarm value (level, percentage or height) •...
Page 35 APPENDIX B: PROBLEM SOLVING In this appendix, several problems are included that can occur when the F170-A-OS is going to be installed or while it is in operation. Analog output does not function properly: Check: SETUP 71 - is the function enabled? ...
Page 36 APPENDIX C: COMMUNICATION VARIABLES Remarks: Below, an overview of the F170-A-OS specific variables; other common variables are described in the standard table. All numbers are decimal numbers, unless otherwise noted. Following variables of the standard table (var00-var30) are not valid for this product and will be responded with value 1: var00, 03-05, 07,08, 16-22, 24, 26-29.
Page 37
(A8h) tagnumber 0..9999999 Other vars: see standard table OTHER F170-A-OS VARIABLES FOR COMMUNICATION LEVEL - variable number 572 (23Ch) – 4 bytes READ LEVEL: The value difference as mentioned with total/acc. total might appear here too. WRITE LEVEL: Impossible. HF170AEN_OS_v0501_04...
Fig. 8: Grounding aluminum enclosure with type PM 115-230V AC..........25 Fig. 9: switch position voltage selection (option PD and PD-OS)............26 Fig. 10: Overview of terminal connectors of the F170-A-OS.............. 27 Fig. 11: Overview terminal connectors communication option............30 Fig.
Page 39 NOTES LIST OF CONFIGURATION SETTINGS SETTING DEFAULT DATE : DATE : 1 - LEVEL Enter your settings here 11 unit 12 decimals 0000000 13 span 000001 14 decimals span 15 off set 2 - HEIGHT 21 unit 22 decimals 000000 23 span 000001 m...
Page 40
A - OTHERS A5 password 0000 A6 tagnumber 0000000 Fluidwell bv HF170AEN_OS_v0501_04 PO box 6 Voltaweg 23 Website: www.fluidwell.com 5460 AA Veghel 5466 AZ Veghel Find your nearest representative: www.fluidwell.com/representatives The Netherlands The Netherlands Copyright Fluidwell bv - 2012 - HF110AEN_v0501_03...