LEVEL INDICATOR
Signal input sensor: (0)4-20mA.
Options: Intrinsically Safe.
F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries

Advertisement

Table of Contents
loading

Summary of Contents for Fluidwell F070-A

  • Page 1 F070-A LEVEL INDICATOR Signal input sensor: (0)4-20mA. Options: Intrinsically Safe. F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries...
  • Page 2: Safety Instructions

     This unit must be installed in accordance with the EMC guidelines (Electro Magnetic Compatibility).  Do connect a proper grounding to the aluminum casing as indicated if the F070-A has been supplied with the 115-230V AC power-supply type PM. The green / yellow wire between the back-casing and removable terminal-block may never be removed.
  • Page 3: About The Operation Manual

    This operation manual describes the standard unit as well as most of the options available. For additional information, please contact your supplier. A hazardous situation may occur if the F070-A is not used for the purpose it was designed for or is used incorrectly. Please carefully note the information in this operating manual indicated by the pictograms: A "warning"...
  • Page 4: Table Of Contents

    Safety rules and precautionary measures ....................... 2 About the operation manual ..........................3 Contents manual .............................. 4 Introduction ..........................5 1.1. System description of the F070-A ..................5 Operational ..........................6 2.1. General ..........................6 2.2. Control panel .......................... 6 2.3.
  • Page 5: Introduction

    This manual describes the unit with an analog (0)4-20mA input type from the sensor "-A version". Other versions are available to process a 0-10V sensor signal. One sensor with a passive or active (0)4-20mA signal output can be connected to the F070-A. To power the sensor, several options are available.
  • Page 6: Operational

     Take careful notice of the " Safety rules, instructions and precautionary measures " in the front of this manual. This chapter describes the daily use of the F070-A. This instruction is meant for users / operators. 2.2. CONTROL PANEL The following keys are available: Fig.
  • Page 7: Operator Information And Functions

    SETUP-settings. The signal generated by the connected sensor is measured by the F070-A in the background, whichever screen refresh rate setting is chosen. After pressing a key, the display will be updated very quickly during a 30 second period, after which it will slow-down again.
  • Page 8: Configuration

    Operating Manual before carrying out its instructions.  The F070-A may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
  • Page 9 Page 9 Matrix structure SETUP-level: SCROLLING THROUGH SETUP-LEVEL Selection of function-group and function: SETUP is divided into several function groups and functions. Each function has a unique number, which is displayed below the word "SETUP" at the bottom of the display. The number is a combination of two figures. The first figure indicates the function-group and the second figure the sub-function.
  • Page 10 Page 10 To change or select a value: To change a value, use  to select the digits and  to increase that value. If the new value is invalid, the increase sign or decrease-sign will be displayed while you are programming.
  • Page 11: Overview Functions Setup Level

    CUT-OFF 0.0 - 99.9% CALIBRATE LOW default - calibrate - calibrate set CALIBRATE HIGH default - calibrate - calibrate set OTHERS TYPE / MODEL F070-A SOFTWARE VERSION 03.xx.xx SERIAL NO. xxxxxxx PASS CODE 0000 - 9999 TAGNUMBER 0000000 - 9999999...
  • Page 12: Explanation Of Setup-Functions

    Page 12 3.2.3. EXPLANATION OF SETUP-FUNCTIONS 1 - LEVEL SETUP - 11 determines the measurement unit for the displayed level. MEASUREMENT UNIT The following units can be selected: L - m3 - kg - lb. - GAL - USGAL - bbl - _ (no unit). Alteration of the measurement unit will have consequences for operator and SETUP-level values.
  • Page 13: Height

    Page 13 2 - HEIGHT If desired the height of the level column can be calculated and displayed. SETUP - 21 determines the measurement unit for height. MEASUREMENT UNIT The following units can be selected: mm - cm - m - mtr - inch - ft - mmwk - mmwc - cmwk - cmwc - mwk - mwc - inwc - ftwc - mbar - bar - psi - no unit.
  • Page 14: Display

    When used with the internal battery option, the user can expect reliable measurement over a long period of time. The F070-A has several smart power management functions to extend the battery life time significantly. Two of these functions can be set:...
  • Page 15: Sensor

    The analog output signal of a sensor does mirror the actual level. This FILTER signal is measured several times a second by the F070-A. The value measured is a "snap-shot" of the real level as it will be fluctuating. With the help of this digital filter a stable and accurate reading can be obtained while the filter level can be set to a desired value.
  • Page 16: Others

    For support and maintenance it is important to have information about the TYPE OF MODEL characteristics of the F070-A. Your supplier will ask for this information in the case of a serious breakdown or to assess the suitability of your model for upgrade considerations.
  • Page 17: Installation

    Operating Manual before carrying out its instructions.  The F070-A may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
  • Page 18: Dimensions- Enclosure

    Page 18 4.3. DIMENSIONS- ENCLOSURE Aluminum enclosures: 75 mm (2.95") 112 mm (4.40") 130 mm (5.12") 12mm 12mm 30mm 30mm 24mm 24mm M20 x 1,5 6 x M12 36mm 36mm 30mm 30mm M16 x 1,5 M16 x 1,5 1/2"NPT M20 x 1,5 0.12"...
  • Page 19 Page 19 GRP enclosures: 75 mm (2.95") 112 mm (4.40") 130 mm (5.12") HK back box: (flat bottom) 75 mm (2.95") 118 mm (4.65”) 25mm 25mm D=20mm D=20mm 12mm 12mm 30mm 30mm 24mm 24mm D=12mm D=16mm D=16mm D=20mm 36mm 36mm 0.12”...
  • Page 20: Installing The Hardware

     This unit must be installed in accordance with the EMC guidelines (Electro Magnetic Compatibility).  Do ground the aluminum casing properly as indicated, if the F070-A has been supplied with the 115-230V AC power-supply type PM. The green / yellow wire between the back- casing and removable terminal-block may never be removed.
  • Page 21: Terminal Connectors With Power Supply - Type : Pb / Pd / Pl / Px

    REMARKS: TERMINAL CONNECTORS: Terminals 1-2; Sensor input type A: The F070-A requires a (0)4-20mA sensor signal which will be processed 4 times a second with a 16 bits accuracy. The input is not isolated. The screen of the signal wire must be connected to the common ground terminal...
  • Page 22 Connect the "-" to terminal 4 and the "+" to terminal 5. When power is applied to these terminals, the optional internal battery will be disabled / enabled automatically to extend the battery life time. The input loop powered model - type F070-A-PL - does not have this power supply option. Terminal 6: sensor supply voltage - type PD.
  • Page 23: Terminal Connectors With Power Supply - Type : Pf / Pm

    TYPE: A PF / PM ANALOG (0)4-20mA Fig. 9: Overview of terminal connectors F070-A-(PF / PM) and options. SENSOR SUPPLY Type PF-PM: Sensor supply: 8.2V, 12V or 24 V: With this option, a real power supply for the sensor is available. The sensor can be powered with 8.2, 12 or 24 V DC (max.
  • Page 24 400mA@24V DC. Terminals 5-7; Sensor input: The F070-A requires a (0)4-20mA sensor signal which will be processed 4 times a second with a 16 bits accuracy. The input is not isolated. The screen of the signal wire must be connected to the common ground terminal 5.
  • Page 25: Intrinsically Safe Applications

    Safety Instructions  Certificates, safety values, control drawing and declaration of compliance can be found in the document named: “Fluidwell F0..-A-XI - Documentation for Intrinsic Safety”.  For installation under ATEX directive: this intrinsically safe device must be installed in accordance with the Atex directive 94/9/EC and the product certificate KEMA 05ATEX1168 X.
  • Page 26 FWCD-0001. Tamb CSA Certificate nr: CSA.08.2059461 – FM Project ID: 3033306 -40°C ... +70°C Made in Veghel, The Netherlands by Fluidwell bv -40°F ... +158°F KEMA 05ATEX1168 X Battery powered applications: II 1 G Ex ia IIC T4 Replace with certified II 1 D Ex iaD 20 IP 65 / 67 T 100°C...
  • Page 27: Terminal Connectors Intrinsically Safe Applications

    Type PX: as standard, all intrinsically product are supplied with terminal 4 and 5 to power the product externally. 5.3. CONFIGURATION EXAMPLES INTRINSICALLY SAFE APPLICATIONS: Configuration example no. 1 Configuration example IIA - IIB and IIC application - F070-A-PX-XI-ZB HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F0-series = max.
  • Page 28 Page 28 Configuration example no. 2 Configuration example IIA - IIB and IIC application - F070-A-PL-XI-ZB HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F0-series = max. 30 V Power supply Supply backlight = max. 200 mA Backlight option: type ZB For example = max.
  • Page 29: Battery Replacement Instructions

    Page 29 5.4. BATTERY REPLACEMENT INSTRUCTIONS FW-LiBAT-001 - INST001 Fig. 18: Battery replacement instructions Intrinsically Safe Battery. HF070AEN_v0403_03 Atex_IECEx_CSA_FM...
  • Page 30: Maintenance

    Operating Manual before carrying out its instructions.  The F070-A may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
  • Page 31: Appendix A: Technical Specification

    Page 31 APPENDIX A: TECHNICAL SPECIFICATION GENERAL Display Type High intensity reflective numeric and alphanumeric LCD, UV-resistant. Digits 5 ½ 26mm (1") and eleven 8mm (0.31"). Various symbols and measuring units. Piegraph 10 segment range indication in relation to its measuring range 0-100% Refresh rate User definable: 8 times/sec - 30 secs.
  • Page 32 Page 32 Type PB / PC / PL / PX Sensor supply not available. Type PD As connected power supply voltage (internally linked) Type PF / PM Sensor supply voltage 8.2, 12 and 24V DC - max. 400mA@24V DC Terminal connections Type: Removable plug-in terminal strip.
  • Page 33 Page 33 OPERATIONAL Operator functions Displayed functions • top line: level, height or percentage. • bottom line: height, level, percentage or no indication. • piegraph: 10 segment display related to the input signal. Level Digits 5 ½ digits. Units L, m3, GAL, USGAL, KG, lb, bbl, no unit. Decimals 0 - 1 - 2 or 3.
  • Page 34: Appendix B: Problem Solving

    APPENDIX B: PROBLEM SOLVING In this appendix, several problems are included that can occur when the F070-A is going to be installed or while it is in operation. Level / height displays "0 / zero" while a higher signal is available: Check: ...
  • Page 35: Index Of This Manual

    Fig. 7: Grounding aluminum enclosure with type PM 115-230V AC..........20 Fig. 8: Overview of terminal connectors F070-A-(PB / PD / PL / PX) and options......21 Fig. 9: Overview of terminal connectors F070-A-(PF / PM) and options........... 23 Fig.
  • Page 36 64 pass code 0000 65 tagnumber 0000000 Fluidwell bv HF070AEN_v0403_03 Atex_IECEx_CSA_FM PO box 6 Voltaweg 23 Website: www.fluidwell.com 5460 AA Veghel 5466 AZ Veghel Find your nearest representative: www.fluidwell.com/representatives The Netherlands The Netherlands Copyright Fluidwell bv - 2012 - HF110AEN_v0501_03...