Download Print this page

Greenheck Combination Fire Smoke Dampers SSFSD-211 Specification Sheet page 4

Combination fire smoke dampers stainless steel 3v blades ul 555s leakage class i ul555 11⁄2 hour fire resistance rating
Hide thumbs Also See for Combination Fire Smoke Dampers SSFSD-211:

Advertisement

AMCA 5.3 Pressure Drop
Figure 5.3
Figure 5.2
Figure 5. 5
12 in. x 12 in. (305mm x 305mm)
Pressure Drop
Velocity (fpm)
(in. wg)
500
0.02
1000
0.09
1500
0.20
2000
0.36
2500
0.56
3000
0.81
3500
1.10
4000
1.44
5D
5D
24 in. x 24 in. (610mm x 610mm)
Pressure Drop
Velocity (fpm)
(in. wg)
500
0.01
1000
0.04
1500
0.09
2000
0.16
2500
0.25
3000
0.35
3500
0.48
4000
0.63
Greenheck Fan Corporation certifies that the
model SSFSD-211 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with the
R
requirements of the AMCA Certified Ratings Pro-
grams. The AMCA Certified Ratings Seal applies to
air performance ratings only.
36 in. x 36 in. (914mm x 914mm)
Pressure Drop
Velocity (fpm)
(in. wg)
500
0.01
1000
0.03
1500
0.06
2000
0.11
2500
0.17
3000
0.24
3500
0.33
4000
0.42
SSFSD-211
6D
4 (W) (H)
D =
3.14
12 in. x 48 in. (305mm x 1219mm)
48 in. x 12 in. (1219mm x 305mm)
Pressure Drop
Velocity (fpm)
(in. wg)
500
0.01
1000
0.04
1500
0.10
2000
0.17
2500
0.27
3000
0.39
3500
0.53
4000
0.70
Pressure Drop
Velocity (fpm)
(in. wg)
500
0.02
1000
0.07
1500
0.16
2000
0.29
2500
0.45
3000
0.64
3500
0.88
4000
1.14

Advertisement

loading