Download Print this page

Greenheck Combination Fire Smoke Dampers SSFSD-211 Specification Sheet page 3

Combination fire smoke dampers stainless steel 3v blades ul 555s leakage class i ul555 11⁄2 hour fire resistance rating
Hide thumbs Also See for Combination Fire Smoke Dampers SSFSD-211:

Advertisement

AMCA 5.2 Pressure Drop
12 in. x 12 in. (305mm x 305mm)
Pressure Drop
Velocity (fpm)
(in. wg)
500
0.04
1000
0.14
1500
0.31
2000
0.55
2500
0.86
3000
1.24
3500
1.69
4000
2.20
Figure 5.3
Figure 5.2
Figure 5. 5
24 in. x 24 in. (610mm x 610mm)
Pressure Drop
Velocity (fpm)
(in. wg)
500
0.02
1000
0.07
1500
0.16
2000
0.29
2500
0.45
3000
0.65
3500
0.89
4000
1.16
Greenheck Fan Corporation certifies that the
model SSFSD-211 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with the
R
requirements of the AMCA Certified Ratings Pro-
grams. The AMCA Certified Ratings Seal applies to
air performance ratings only.
5D
36 in. x 36 in. (914mm x 914mm)
Pressure Drop
Velocity (fpm)
(in. wg)
500
0.01
1000
0.04
1500
0.09
2000
0.16
2500
0.25
3000
0.36
3500
0.49
4000
0.64
SSFSD-211
D =
12 in. x 48 in. (305mm x 1219mm)
Pressure Drop
Velocity (fpm)
(in. wg)
500
0.01
1000
0.06
1500
0.13
2000
0.23
2500
0.36
3000
0.52
3500
0.70
4000
0.92
4 (W) (H)
3.14
48 in. x 12 in. (1219mm x 305mm)
Pressure Drop
Velocity (fpm)
(in. wg)
500
0.03
1000
0.10
1500
0.23
2000
0.41
2500
0.63
3000
0.91
3500
1.24
4000
1.62

Advertisement